Operating Elevation
(m)

0-3000 m

COMMUNICATIONS

Communications
interface

USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface

Network monitoring
port description

Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI
installation requires removal of panel containing USB ports

PowerAlert software

Included

Communications
cable

USB, DB9 serial and EPO cables included

WatchDog
compatibility

Supports Watchdog application, OS and hard-reboot restart options for remote applications

LINE / BATTERY TRANSFER

Transfer time

No transfer time (0 ms.) in online, double-conversion mode

Transfer time
(economy mode)

8 ms. typical power failure response in optional economy mode

Low voltage transfer
to battery power
(setpoint)

100V

High voltage transfer
to battery power
(setpoint)

300V

SPECIAL FEATURES

Cold Start (startup in
battery mode during
a power failure)

Cold-start operation supported

Economy mode
operation

Optional economy mode enables high-efficiency bypass operation with a maximum output voltage variation of
+/-10%. Double conversion mode is automatically restored as mains voltage varies /-10% with less than 1
millisecond transfer time between modes.

High availability UPS
features

Automatic inverter bypass; Manual bypass switch; Detachable hot-swap PDU; Hot swappable UPS power module;
Hot swappable batteries

Green & high
efficiency features

High efficiency economy mode operation; Schedulable daily hours of economy mode operation

CERTIFICATIONS

UPS Certifications

Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); CE; Meets FCC Part 15 Category A
(EMI)

UPS Certification
details

IEC 61000-4-5 1995 B Surge Immunity

WARRANTY

Product Warranty
Period (Worldwide)

2-year limited warranty

Connected
Equipment
Insurance (U.S.,
Canada & Puerto
Rico)

$250,000 

Ultimate Lifetime Insurance

Related Items

Optional Products

Summary of Contents for SmartOnline SU8000RT3U

Page 1: ...l for advanced networking applications in data centers computer rooms network closets and rugged industrial locations Package Includes SU8000RT3UPM 3U UPS power module BP240V10RT3U external battery pa...

Page 2: ...d contact closure outputs for custom event notification Optional RELAYIOMINI interface module offers three configurable hard contact closure outputs for custom event notification requires removal of U...

Page 3: ...1 8A 220V 40A 230V 38 3A 240V Nominal Input Voltage s Supported 200V AC 208V AC 220V AC 230V AC 240V AC UPS input connection type Hardwire UPS input connection description 3 wire single phase input L1...

Page 4: ...scrolling LCD functions bundled PDU includes bypass switch to enable hot swap UPS power module replacement SURGE NOISE SUPPRESSION UPS AC suppression response time Instantaneous EMI RFI AC noise suppr...

Page 5: ...8 x 31 5 x 23 UPS Shipping dimensions height x width x depth cm 101 x 80 x 58 4 Shipping weight lbs 331 Shipping weight kg 150 3 Cooling method Fan UPS housing material Steel ENVIRONMENTAL Operating...

Page 6: ...PECIAL FEATURES Cold Start startup in battery mode during a power failure Cold start operation supported Economy mode operation Optional economy mode enables high efficiency bypass operation with a ma...

Page 7: ...U Power Distribution Unit supports real time remote monitoring of load level voltage and frequency with options for remote environmental and security monitoring 1 PDUMNV30HV Monitored PDU Power Distri...