background image

Recommended
Electrical Service

120V 30A dedicated circuit

BATTERY

Full load runtime

6 minutes (2400 watts) - expandable

Half load runtime

17 minutes (1200 watts) - expandable

Expandable
battery runtime

Supports extended runtime with optional external battery packs BP72V28-3UNAFTA (multi-pack compatible)

DC system voltage

72VDC

Typical battery
lifespan

3-6 years, depending on usage

Battery recharge
rate

less than 6 hours to 80%

Replacement
Battery Cartridge

RBC96-3U (qty 1)

VOLTAGE REGULATION

Voltage regulation
description

On-line, double-conversion power conditioning maintains output within 2% of 110/120 volts at all times

Overvoltage
correction

Maintains output of selected n/-2% during overvoltages to 138V AC

Brownout
correction

Maintains output of selected n/-2% during undervoltages to 65V AC (at loads greater than 70% undervoltage
correction extends to 80V)

LEDS ALARMS & SWITCHES

Front panel LEDs

LED STATUS DISPLAY: line power (green), online (green), bypass (yellow), on battery (green), overload (red), battery
low (yellow) - 4 LED LOAD / BATTERY LEVEL DISPLAY (100%, 75%, 50%, 25%).

Alarms

Multi-function audible alarm with distinctive ring patterns offer notification of backup operation (2 seconds on / 0.5 seconds
off), low battery warning (1.25 seconds on / 0.5 seconds off), overload (sounds continuously), UPS fault (4.2 seconds on /
1 second off), input voltage out of frequency (2.1 seconds on / 0.14 seconds off) and high input voltage (2.1 seconds on
0.07 seconds off)

Switches

Includes power off/on switch to enable system turn on (press ON switch), UPS battery test (press ON switch during normal
AC operation), buzzer silence (press ON switch during battery operation) and OFF (press OFF switch). All switch functions
require that the switch be pressed and held for longer than 2 seconds, but less than 4 seconds

SURGE / NOISE SUPPRESSION

AC surge
suppression

480 joules

AC suppression
response time

Instantaneous

Dataline
suppression

Set of 8 wire RJ style interface jacks offer surge suppression for network ethernet or TEL/DSL connection. Pins 1,2,3 and
6 offer ethernet protection starting at 7.5V and the center two wires, pins 4 & 5, offer TEL/DSL line suppression starting at
260V

EMI / RFI AC noise
suppression

Yes

PHYSICAL

Shipping weight
(lbs)

75.2

Shipping weight
(kg)

34.1

Shipping
Dimensions
(HWD/in)

15.25 x 13 x 24

Shipping
Dimensions
(HWD/cm)

38.7 x 33 x 61

Unit weight (lbs)

69.3

Unit weight (kg)

31.5

Reviews: