background image

True on-line, double-conversion UPS provides perfectly regulated sine wave output within 2% of 110/120V (user selectable) under all usage

conditions

Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time

Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other

UPS types

Corrects line voltage conditions as low as 65V and as high as 138V back to selectable 110/120V (+/-2%) values 

Standard internal battery set offers 14 minutes runtime at half load (1200W) and 5 minutes at full load (2400W)

Optional BP72V28-3UNAFTA external battery packs offer expandable battery runtime

Space saving upright tower format

Fault tolerant auto-bypass maintains continuous utility output to connected equipment, even in cases where the UPS suffers internal failure

and requires maintenance

Network interfaces support simultaneous communications via built-in USB, DB9 serial/contact-closure and SNMPWEBCARD slot

HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. 

Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus

any number of additional servers over IP

UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current,

battery capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS

nominal voltage adjustment and UPS line to battery power voltage setpoints

Built-in Emergency Power Off (EPO) interface with cable 

NEMA L5-30P input plug/NEMA 5-15/20R, L5-20R & L5-30R output receptacles 

Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (each

bank has four outlets)

Front panel LEDs offer current monitoring and battery charge level information

UPS ships fully assembled in full compliance with DOT regulations; no time consuming connection of internal batteries by user required

Single line TEL/DSL or network ethernet line surge suppression

2 year manufacturer's product warranty; $250,000 

Ultimate Lifetime Insurance

Specifications

SYSTEM OVERVIEW

Voltage
compatibility

120V AC (110/120V)

Frequency
compatibility

50/60 Hz compatible (auto-sensing)

OUTPUT

Output VA

3000

Output watts

2400

Output nominal
voltage

120V AC (110/120V)

Output voltage
regulation

Maintains full-time sine wave output within 2% of selected nominal, less than 3% total harmonic distortion (linear load) /
5% total harmonic distortion (computer load) (Less than 5% THD on-line and on-battery)

Output frequency
regulation

Regulates line frequency to 50/60Hz +/- 0.05Hz

Outlet quantity /
type

4 NEMA 5-15R, 4 NEMA 5-15/20R, 1 NEMA L5-30R

Customized load
management
receptacles

2 controllable load banks support load shedding and remote reboot on demand of locked network devices (bank 1 has 4
outlets / bank 2 has 2 outlets)

Overload
protection

Via 40A input breaker

INPUT

Maximum input
amps

24A (120V) / 26.2A (110V)

Input connection
type

NEMA L5-30P

Input cord length

10ft / 3m