2

important safety Warnings

saVe tHese instrUCtiOns. this manual contains important instructions and warnings that should be 

followed during the installation and maintenance of this UPs system. the battery pack owner's manual 

also contains important instructions and warnings. read the battery pack owner's manual before 

attempting to install the UPs system.

UPs Location Warnings

•  The UPS is extremely heavy. Use caution when lifting and installing.
•  Install the UPS indoors, away from excess moisture or heat, direct sunlight, dust and conductive contaminants.
•  Install the UPS in a structurally sound area. 
•  Only operate the UPS at indoor temperatures between 32° F and 104° F (between 0° C and 40° C). For best results, keep indoor 

 

  temperatures between 62° F and 84° F (between 17° C and 29° C).
•  Leave adequate space around all sides of the UPS for proper ventilation. Do not obstruct its ventilation fans or openings.
•  Do not install the UPS near magnetic storage media, as this may result in data corruption.
•  If you are installing the UPS in a stack configuration, always stack the power module above the battery module(s).
• 

Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this manner will seriously inhibit the  

  unit's internal cooling, eventually causing product damage not covered under warranty.

UPs Connection Warnings

•  The power supply for this unit must be split-phase rated in accordance with the equipment nameplate. It also must be suitably grounded.
•  Connect the UPS system only to a four-wire input power connection (L1, L2, N, G). This UPS requires an input neutral connection.
•  Connect the UPS to a properly grounded AC power source. Do not modify the input connection in a way that would eliminate the  

 

  connection to ground. 
•  Do not use adapters that eliminate the connection to ground.
•  Do not connect the UPS input to its output; this will damage the UPS and void the warranty.
•  If you are connecting the UPS to a motor-powered AC generator, the generator must provide filtered, frequency-regulated 

 

  computer-grade output. Connecting the UPS to a generator will void its Ultimate Lifetime Insurance.

equipment Connection Warnings

•  Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the 

 

  life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence 

 

  of a flammable anesthetic mixture with air, oxygen or nitrous oxide
•  The UPS is connected to a DC energy source (battery). The output terminals may be live even when the UPS is not connected to an 

 

  AC power source.
•  Do not connect surge suppressors or extension cords to the output of the UPS. This might overload the UPS and will void the surge 

 

  suppressor and UPS warranties.

Maintenance Warnings

•  The UPS does not require routine maintenance. Do not open the UPS for any reason. There are no user-serviceable parts inside.

Battery Warnings

•  Do not operate the UPS without connecting the power module to an external battery module.
•  Connect only Tripp Lite battery packs to the battery connectors. Connect battery packs of the correct voltage and type.
•  The internal batteries in the battery pack are recyclable. Refer to local codes for disposal requirements, or in the USA call 

 

  800-SAV-LEAD (800-728-5323) or 800-8-BATTERY (800-822-8837), or go to www.rbrc.com for complete recycling information. 

 

  CAUTION: Do not dispose of the batteries in a fire, as this could cause the batteries to explode. 
•  Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions. Do not dispose of the 

 

  batteries in a fire. Do not open the UPS or batteries. Do not short or bridge the battery terminals with any object. Unplug and turn off the 

 

  UPS before performing battery replacement. Use tools with insulated handles. There are no user-serviceable parts inside the UPS. Battery 

 

  replacement should be performed only by authorized service personnel using the same number and type of batteries (Sealed Lead-Acid). 

 

  The batteries are recyclable. Refer to your local codes for disposal requirements or in the USA only call 1-800-SAV-LEAD or 

 

  1-800-8-BATTERY (1-800-822-8837) or visit www.rbrc.com for recycling information. Tripp Lite offers a complete line of UPS System 

 

  Replacement Battery Cartridges (R.B.C.).Visit Tripp Lite on the Web at www.tripplite.com/support/battery/index.cfm to locate the 

 

  specific replacement battery for your UPS.
•  Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes, and may be toxic.
•  Fuses should be replaced only by factory-authorized personnel. Blown fuses should be replaced only with fuses of the same number and type.
•  Service and repair should be performed only by trained personnel. During any service work to the UPS, it should be turned off or placed 

 

  into manual bypass mode (see 

Manual Bypass Procedure

). 

Note: Potentially lethal voltages exist within this unit as long as the  

  battery supply is connected.

•  Do not connect or disconnect external battery pack(s) while the UPS is operating from the battery supply.
•  During hot-swap battery pack replacement, the UPS will not provide backup power in the event of a blackout or other power interruption.

Summary of Contents for SmartOnline SU16000RT4U

Page 1: ...and SU16000RT4UHW Important Safety Warnings 2 Features 3 Mounting 7 Connection 8 Optional Connection 9 Manual Bypass Procedure 15 Operation 10 Storage Service 17 Warranty Warranty Registration 17 111...

Page 2: ...ergy source battery The output terminals may be live even when the UPS is not connected to an AC power source Do not connect surge suppressors or extension cords to the output of the UPS This might ov...

Page 3: ...and hold it until you hear a beep The UPS will display the following message Switch to Bypass N ON Y OFF if it is safe to do so Pressing OFF again will put the UPS in Bypass still providing power to...

Page 4: ...stem s battery charge rate The switch is set to the left the position labeled NORMAL by default If you connect more than one external battery pack to the UPS system set the Battery Charge Level Switch...

Page 5: ...ss the terminals unscrew and remove the terminal block cover Diagram shows cover removed The UPS must be connected to a dedicated circuit of sufficient amperage split phase rated in accordance with th...

Page 6: ...t connect or disconnect battery packs while the UPS is running on battery power the BATTERY LED will be lit on the control panel Warning Always use the connector retention brackets to secure the batte...

Page 7: ...rack and rack enclosure types and may not be appropriate for all applications WARNING The UPS system is extremely heavy Use caution when lifting and mounting User must properly stabilize the UPS when...

Page 8: ...lone power source when AC input power is unavailable i e during a blackout you can cold start the UPS and power connected equipment from the battery The battery must be at least partially charged for...

Page 9: ...rd to the second and so on Note When daisy chaining multiple battery packs they should be identical models of similar age and level of wear Make sure that cables are inserted fully into connectors Sma...

Page 10: ...AC Input DIAGNOSTIC MODE INPUT AC OK DIAGNOSTIC MODE INPUT AC BAD DIAGNOSTIC MODE BATTERY OK DIAGNOSTIC MODE BATTERY OK DIAGNOSTIC MODE CHARGER OK DIAGNOSTIC MODE AC DC OK DIAGNOSTIC MODE AC DC OK DI...

Page 11: ...wn if AC power is interrupted If solid the UPS is in Economy Mode ECO See page 12 for details The second line of the LCD Display shows basic power conditions Push the SCROLL buttons to browse through...

Page 12: ...h the SET UP screen 1 and press the SCROLL DOWN button again to exit the SET UP procedure The LCD should be back to ON BATTERY MODE Press the OFF key until you hear a beep and the UPS will save the se...

Page 13: ...on on its LCD and stops supplying output power to its load Bypass Voltage Conditions L1 15 Higher Than Nominal Voltage L2 15 Higher Than Nominal Voltage L1 20 Lower Than Nominal Voltage L2 20 Lower Th...

Page 14: ...VERLOAD XXX OP S HORTCIRCUIT LOAD1 XX X X XKW OP1 SHORTCIRCUIT LOAD1 XX X X XKW OP2 SHORTCIRCUIT LOAD1 XX X X XKW REMOTE C OMMAND LOAD1 XX X X XKW EMERGENCY STO P LOAD1 XX X X XKW SITE WIR ING F AULT...

Page 15: ...re and disconnect all communication cable s from the communication port s A on the UPS power module STEP 3 Press the UPS s OFF Button B if the UPS is powered until you hear a beep and see a Switch to...

Page 16: ...ts are live Do not let these contacts touch any surface A Contacts on Detachable PDU WARNING High voltage Risk of electrical shock If AC is present and Bypass Switch is set to Bypass these contacts ar...

Page 17: ...pproved by the party responsible for compliance could void the user s authority to operate the equipment Made in China Regulatory Compliance Identification Numbers For the purpose of regulatory compli...

Reviews: