12

Operation 

(continued)

Configuration Menu

The UPS output voltage is set at 208/120V~ when the UPS is shipped from the factory. In order to change the output voltage of the UPS, you 
first need to enter “ON BATTERY MODE” by cold-starting the UPS. (The battery must be at least partially charged for this operation to 
succeed.) If the UPS is on, press and hold the “OFF” button until you hear a beep, disconnect any connected equipment and disconnect the 
UPS from its AC power input. After the UPS is disconnected from AC power, press the “ON/MUTE” button until you hear a beep. The LCD 
screen will show “ON BATTERY MODE” and an alarm will sound periodically to inform you that the UPS is using battery power. Silence 
the alarm by pressing the “ON/MUTE” button.

After the UPS has entered “ON BATTERY MODE”, press the SCROLL UP and SCROLL DOWN buttons simultaneously for longer than 

 

1 second. The UPS will beep and the LCD will show the SET-UP screen (1). Press the SCROLL UP/SELECT button to enter the “UPS SET-UP”

 

procedure  (2).  Press  the  SCROLL  UP/SELECT  button  again  to  enter  the  “OUTPUT  SELECT”  procedure  (3). There  are  3  output  voltage 
selections. Press the SCROLL DOWN button to scroll to the desired output voltage selection (3)-(5) and then press the SCROLL UP/SELECT 
button to select it. The LCD will return to the “OUTPUT SELECT” screen (2). Press the SCROLL DOWN button to reach the SET-UP screen 
(1) and press the SCROLL DOWN button again to exit the SET-UP procedure. The LCD should be back to “ON BATTERY MODE”. Press 
the “OFF” key until you hear a beep, and the UPS will save the selected output voltage parameter. Restore the AC power input of the UPS and 
press the “ON” key to turn on the UPS and use the SCROLL DOWN button to scroll through the basic power conditions displays and confirm 
that the output voltage has been changed to the desired value.

Economy Mode (ECO) is a high-efficiency operating mode in which the double conversion process is suspended. Incoming power is filtered, 
and if the input voltage is /- 10% of the nominal voltage, it is passed through to connected equipment. If the input voltage goes outside 
of this acceptable range, the unit automatically returns to its Online Mode to provide a highly regulated output derived from the system’s 
inverter. If voltage subsequently returns to the acceptable range, the unit will return to its high efficiency mode.

note:
208 / 120V<120D 

Output Voltage (L1-L2)=208V, Output Voltage (L1,L2)=120V and L1 leads L2 120 degrees

208 / 120V<240D 

Output Voltage (L1-L2)=208V, Output Voltage (L1,L2)=120V and L2 leads L1 120 degrees

240 / 120V<180D 

Output Voltage (L1-L2)=240V, Output Voltage (L1,L2)=120V and L1 leads L2 180 degrees

Self-Test Is Running

TESTING BATTERY

LOAD1 = XXX% X.XKW

additional self-test

If a self-test is initiated after startup, the LCD will display a message.

i

ECO

Scroll

Disable

Select

ECO

Exit

Enable

Select

ii

i

ECO

Scroll

Disable

Select

ECO

Exit

Enable

Select

ii

Summary of Contents for SmartOnline SU16000RT4U

Page 1: ...and SU16000RT4UHW Important Safety Warnings 2 Features 3 Mounting 7 Connection 8 Optional Connection 9 Manual Bypass Procedure 15 Operation 10 Storage Service 17 Warranty Warranty Registration 17 111...

Page 2: ...ergy source battery The output terminals may be live even when the UPS is not connected to an AC power source Do not connect surge suppressors or extension cords to the output of the UPS This might ov...

Page 3: ...and hold it until you hear a beep The UPS will display the following message Switch to Bypass N ON Y OFF if it is safe to do so Pressing OFF again will put the UPS in Bypass still providing power to...

Page 4: ...stem s battery charge rate The switch is set to the left the position labeled NORMAL by default If you connect more than one external battery pack to the UPS system set the Battery Charge Level Switch...

Page 5: ...ss the terminals unscrew and remove the terminal block cover Diagram shows cover removed The UPS must be connected to a dedicated circuit of sufficient amperage split phase rated in accordance with th...

Page 6: ...t connect or disconnect battery packs while the UPS is running on battery power the BATTERY LED will be lit on the control panel Warning Always use the connector retention brackets to secure the batte...

Page 7: ...rack and rack enclosure types and may not be appropriate for all applications WARNING The UPS system is extremely heavy Use caution when lifting and mounting User must properly stabilize the UPS when...

Page 8: ...lone power source when AC input power is unavailable i e during a blackout you can cold start the UPS and power connected equipment from the battery The battery must be at least partially charged for...

Page 9: ...rd to the second and so on Note When daisy chaining multiple battery packs they should be identical models of similar age and level of wear Make sure that cables are inserted fully into connectors Sma...

Page 10: ...AC Input DIAGNOSTIC MODE INPUT AC OK DIAGNOSTIC MODE INPUT AC BAD DIAGNOSTIC MODE BATTERY OK DIAGNOSTIC MODE BATTERY OK DIAGNOSTIC MODE CHARGER OK DIAGNOSTIC MODE AC DC OK DIAGNOSTIC MODE AC DC OK DI...

Page 11: ...wn if AC power is interrupted If solid the UPS is in Economy Mode ECO See page 12 for details The second line of the LCD Display shows basic power conditions Push the SCROLL buttons to browse through...

Page 12: ...h the SET UP screen 1 and press the SCROLL DOWN button again to exit the SET UP procedure The LCD should be back to ON BATTERY MODE Press the OFF key until you hear a beep and the UPS will save the se...

Page 13: ...on on its LCD and stops supplying output power to its load Bypass Voltage Conditions L1 15 Higher Than Nominal Voltage L2 15 Higher Than Nominal Voltage L1 20 Lower Than Nominal Voltage L2 20 Lower Th...

Page 14: ...VERLOAD XXX OP S HORTCIRCUIT LOAD1 XX X X XKW OP1 SHORTCIRCUIT LOAD1 XX X X XKW OP2 SHORTCIRCUIT LOAD1 XX X X XKW REMOTE C OMMAND LOAD1 XX X X XKW EMERGENCY STO P LOAD1 XX X X XKW SITE WIR ING F AULT...

Page 15: ...re and disconnect all communication cable s from the communication port s A on the UPS power module STEP 3 Press the UPS s OFF Button B if the UPS is powered until you hear a beep and see a Switch to...

Page 16: ...ts are live Do not let these contacts touch any surface A Contacts on Detachable PDU WARNING High voltage Risk of electrical shock If AC is present and Bypass Switch is set to Bypass these contacts ar...

Page 17: ...pproved by the party responsible for compliance could void the user s authority to operate the equipment Made in China Regulatory Compliance Identification Numbers For the purpose of regulatory compli...

Reviews: