16
4. Operation
Method 2:
1) If the UPS indicates a bypass abnormal error code, you cannot remove the UPS without interruption and must first power down the
load and the UPS system.
2) Make sure the bypass setting is enabled in each UPS, then turn off the running system. All UPS systems will transfer to Bypass mode.
Remove all the maintenance bypass covers and set the maintenance switches from “UPS” to “BPS”. Turn off all input breakers and
battery breakers in the parallel system.
3) Turn off the output breaker and remove the parallel cable and share current cable of the UPS to be removed, then remove the unit
from the parallel system.
4) Turn on the input breaker of the remaining UPS system(s). The system(s) will transfer to Bypass mode. Set the maintenance switches
from “BPS” to “UPS” and reattach the maintenance bypass covers.
5) Turn on the remaining UPS systems.
4.6 LCD Panel Abbreviations
Abbreviation
Display content
Meaning
ADD
Add
ATO
Auto
BAT
Battery
CF
Freq. Converter mode
CHE
Check
DIS
Disable
ENA
Enable
FBD
Forbidden
N.L
Neutral line loss
NCF
Normal mode (not Freq. Converter mode)
OFF
Off
ON
On
OP.V
Output voltage
OPN
Allow
PAR
Parallel, 001 means the first UPS
RES
Reserved
RN
First phase
RS
First line
SN
Second phase
ST
Second line
SUB
Subtract
TN
Third phase
TR
Third line
Summary of Contents for SmartOnline AG-0149 Series
Page 99: ...99 1 Tripp Lite SmartOnline SVTKX 3 10 20 30 SVT20KX SVT30KX ECO SNMP SmartOnline SVTKX...
Page 101: ...101 2 2 4 2 5 2 6 2 7 TN 3...
Page 108: ...108 4 H M S 3 9 VAC VDC Hz 0 25 26 50 51 75 76 100 ECO 0 25 26 50 51 75 76 100 VAC VDC Hz...
Page 118: ...118 4 4 8 1 3 An bn Cn 3 Ab bC CA 2 PAR 2 3 001 002 003...
Page 119: ...119 4 ECO ECO...
Page 120: ...120 4 Freq Converter CF 50 60 4...
Page 121: ...121 4 2 Freq Converter Test 0 5 3 4 11 123...
Page 125: ...125 7 7 1 7 24 3 7 2 BUS 7 3 Tripp Lite SVTKX 1 0 40 C 2 25 C 3 24 7 4 TrippLite...