Installation

UPS LOCATION

Move your UPS over short distances using its wheels. Stabilize the UPS by releasing the stabilizers on each side of the unit. NOTE: Do not
stack the UPS System power module or external battery modules.

UPS POWER MODULE INPUT AND OUTPUT HARDWIRE CONNECTION

In addition to the instructions listed below, follow all warnings found in the Safety section prior to connection.

WIRING SELECTION

Choose appropriate cabling (rated VW-1, FT-1 or better) to connect your UPS Power Module to an AC power supply and your equipment.

UPS System Model

Wiring Size

20kVA

8 AWG / 8 mm

2

30kVA

6 AWG / 14 mm

2

Maximum Cable Length: 10 m (32.8 ft)

WIRING CONNECTION

Connect your wiring to the input and output terminal blocks located on the lower rear panel of your UPS (see figure below).  

CAUTION!

Qualified personnel should follow all procedures prescribed by N.E.C. and other local codes for hardwiring devices to a utility source.

Ensure that cables are fitted with cable sleeves and are secured by connector clamps. Tighten connections with a torque of not less

than 35 inch-pounds. Observe the appropriate cable connection regulations [e.g. National Electrical Code (NEC) in the U.S.] at all

times. Using cables of improper size may damage your equipment and cause fire hazards. 

NOTE: when shipped from the factory, bypass input and main input wires are connected.

N

2

N

1

T

2

R

1

S

2

S

1

R

2

T

1

G

G

UPS BATTERY MODULE HARDWIRE CONNECTION

In addition to the instructions listed below, follow all warnings found in the Safety section prior to connection.

WARNING! 

Before attempting to connect the UPS Power Module to the UPS Battery Module, qualified personnel must remove all fuses from all

UPS Battery Modules.

CAUTION!

Make certain that your UPS Power Module and UPS Battery Module use the same DC voltage before connecting them. When 

connecting multiple Battery Modules to a single Power Module, the Battery Modules should be approximately the same age. Do not

connect or disconnect Battery Modules while the Power Module is operating on battery power, due to the possibility of dangerous arcing.

The UPS Power Module will not start without a connection to a charged UPS Battery Module. If you plan to store your Battery
Module(s) for an extended period of time, fully recharge its batteries every three months by connecting it for at least 12 hours to a UPS
Power Module that is connected to AC input.

WIRING SELECTION

Choose appropriate cabling (rated VW-1, FT-1 or better) to connect your UPS Battery Module to your UPS Power Module.

UPS System Model

Wiring Size

20kVA

4 AWG / 22 mm

2

30kVA

2 AWG / 38 mm

2

Maximum Cable Length: 10 m (32.8 ft)

Summary of Contents for SmartOnline 220/380

Page 1: ...240 415V AC 3 4 wire plus ground wye User selectable For all UPS system modules power module and battery module sold either separately or combined Select UPS system modules may include separate instr...

Page 2: ...UPS for any reason There are no user serviceable parts inside Because the batteries present a risk of electrical shock and burn from high short circuit current batteries should be changed only by trai...

Page 3: ...er LED This green light will illuminate constantly to indicate the UPS s AC DC converter is activated 9 BATTERY LED This red light will flash when the UPS is discharging the battery to provide connect...

Page 4: ...ion or server It uses RS 232 communications to report UPS and power conditions It is used with Tripp Lite software and the included RS 232 Cable to monitor and manage network power and to automaticall...

Page 5: ...e out for removal Fuses must be removed before any maintenance is performed 16 Cables for Battery Tray Interconnection internal connect the battery trays to supply DC battery power to a connected UPS...

Page 6: ...improper size may damage your equipment and cause fire hazards NOTE when shipped from the factory bypass input and main input wires are connected N2 N1 T2 R1 S2 S1 R2 T1 G G UPS BATTERY MODULE HARDWIR...

Page 7: ...TWARE The UPS s output voltage is factory set at 220 380V AC If you require output voltage of 230 400V AC or 240 415V AC you must change the UPS s output voltage via the included software interface Th...

Page 8: ...TPUT R XXXV R XXX XV S XXXV S XXX XV T XXXV T XXX XV Bypass Output Voltage OUTPUT LOAD R XXX XXX XA S XXX XXX XA T XXX XXX XA Output Load Current MAINS INVERTER R XXXV R XXX XV S XXXV S XXX XV T XXXV...

Page 9: ...ditions OPERATION ON BYPASS VOLTAGE OUT OF RANGE While in Bypass Mode the UPS monitors the input voltage which on Bypass equals the output voltage If the output voltage passes out of an acceptable ran...

Page 10: ...ent will receive filtered AC mains power but will not receive battery power in the event of a blackout SWITCHING UPS TO BYPASS MODE Press the OFF button Turn the Manual Bypass Switch clockwise from NO...

Page 11: ...Operation on inverter Pin 9 Operation on battery AS 400 INTERFACE TABLE Pin 6 5 Pin 7 5 Pin 8 5 Pin 9 5 Battery OFF ON ON Low Battery OFF ON ON ON Direct Mains Supply ON OFF OFF OFF Inverter OFF ON I...

Page 12: ...869 1234 for details International customers should contact Tripp Lite support at intlservice tripplite com THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUS...

Page 13: ...ications are subject to change without notice This product designed and engineered in the USA Regulatory Compliance Identification Numbers For the purpose of regulatory compliance certifications and i...

Page 14: ...1111 W 35th Street Chicago IL 60609 USA 773 869 1234 USA 773 869 1212 International www tripplite com...

Reviews: