Rear Panels

1. Manual Bypass Switch:

This dial is used in one step of putting the UPS in "BYPASS” mode, which must be done before performing

any maintenance on the UPS with the connected load supported. [See “Operation (Special Conditions)” for step-by-step instructions for
going into “BYPASS.”] While this switch is on “BYPASS,” connected equipment will receive filtered AC mains power, but will not receive
battery power in the event of a blackout.

2. Input Terminal Block:

Use these terminals to connect your UPS to the AC main power input. Unscrew and remove terminal block plate

for access.

3. Output Terminal Block:

Use these terminals to connect your UPS to equipment. A plate covering the terminal block must be unscrewed

and removed for access.

4. External Battery Terminal Block:

Use this to connect a Tripp Lite battery module to the power module. Remove the cover for access.

The power module will not start without a connection to a charged battery module.

5. Exhaust Fans:

These cool and ventilate the inside of the UPS.

6. AS-400 Interface Port:

This female DB9 port connects your UPS to an IBM AS-400 computer interface via the AS-400 Cable includ-

ed. It uses AS-400 communications to report UPS status and power conditions. Using this port, an IBM AS-400 computer can automati-
cally save open files and shut down its operating system during a blackout. See “Communications” for details.

7. “Smart” RS-232 Interface Port:

This female DB9 port connects your UPS to a workstation or server. It uses RS-232 communications

to report UPS and power conditions. It is used with Tripp Lite software and the included RS-232 Cable to monitor and manage network
power and to automatically save open files and shut down equipment during a blackout. See “Communications” for details.

8. Dry Contact Interface Port:

This female DB9 port sends contact-closure signals to indicate line-fail and low-battery status. See

“Communications,” for details.

9. Accessory Slot:

Remove the small cover panel and use optional accessories to remotely control and monitor your UPS. Contact Tripp

Lite Customer Support for more information and a list of available SNMP, network management and connectivity products.

10. “Battery Start” Switch:

This momentary rocker switch allows you to “cold-start” your UPS and use it as a stand-alone power source

when utility-supplied AC power is not present. The switch enables the UPS’s DC/AC Inverter.  Before “cold-starting” your UPS, make sure
your power module and external battery module(s) are properly installed.  Press and hold the “Battery Start” Switch and then press the “ON”
button to turn your UPS ON. To turn it OFF after “cold-start,” press the “OFF” button.

11.  AC Input Switch:

One triple-pole circuit breaker controls input power to the UPS during normal operation.

12.  Bypass AC Input Switch: 

One triple-pole circuit breaker controls input power to the UPS during “BYPASS” operation.

13.  Remote “Emergency Power OFF” (EPO) Connector:

This modular jack allows remote emergency shutdown. See

“Communications” for details.

20kVA & 30kVA Battery Module Rear Panel

Model: BP240V33

20kVA and 30kVA Power Modules Rear Panel 

Models: SU20K3/3INTPM and SU30K3/3INTPM

 

 

Summary of Contents for SmartOnline 220/380

Page 1: ...240 415V AC 3 4 wire plus ground wye User selectable For all UPS system modules power module and battery module sold either separately or combined Select UPS system modules may include separate instr...

Page 2: ...UPS for any reason There are no user serviceable parts inside Because the batteries present a risk of electrical shock and burn from high short circuit current batteries should be changed only by trai...

Page 3: ...er LED This green light will illuminate constantly to indicate the UPS s AC DC converter is activated 9 BATTERY LED This red light will flash when the UPS is discharging the battery to provide connect...

Page 4: ...ion or server It uses RS 232 communications to report UPS and power conditions It is used with Tripp Lite software and the included RS 232 Cable to monitor and manage network power and to automaticall...

Page 5: ...e out for removal Fuses must be removed before any maintenance is performed 16 Cables for Battery Tray Interconnection internal connect the battery trays to supply DC battery power to a connected UPS...

Page 6: ...improper size may damage your equipment and cause fire hazards NOTE when shipped from the factory bypass input and main input wires are connected N2 N1 T2 R1 S2 S1 R2 T1 G G UPS BATTERY MODULE HARDWIR...

Page 7: ...TWARE The UPS s output voltage is factory set at 220 380V AC If you require output voltage of 230 400V AC or 240 415V AC you must change the UPS s output voltage via the included software interface Th...

Page 8: ...TPUT R XXXV R XXX XV S XXXV S XXX XV T XXXV T XXX XV Bypass Output Voltage OUTPUT LOAD R XXX XXX XA S XXX XXX XA T XXX XXX XA Output Load Current MAINS INVERTER R XXXV R XXX XV S XXXV S XXX XV T XXXV...

Page 9: ...ditions OPERATION ON BYPASS VOLTAGE OUT OF RANGE While in Bypass Mode the UPS monitors the input voltage which on Bypass equals the output voltage If the output voltage passes out of an acceptable ran...

Page 10: ...ent will receive filtered AC mains power but will not receive battery power in the event of a blackout SWITCHING UPS TO BYPASS MODE Press the OFF button Turn the Manual Bypass Switch clockwise from NO...

Page 11: ...Operation on inverter Pin 9 Operation on battery AS 400 INTERFACE TABLE Pin 6 5 Pin 7 5 Pin 8 5 Pin 9 5 Battery OFF ON ON Low Battery OFF ON ON ON Direct Mains Supply ON OFF OFF OFF Inverter OFF ON I...

Page 12: ...869 1234 for details International customers should contact Tripp Lite support at intlservice tripplite com THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUS...

Page 13: ...ications are subject to change without notice This product designed and engineered in the USA Regulatory Compliance Identification Numbers For the purpose of regulatory compliance certifications and i...

Page 14: ...1111 W 35th Street Chicago IL 60609 USA 773 869 1234 USA 773 869 1212 International www tripplite com...