OUTPUT
Output Volt Amp
Capacity (VA)
3000
Output kVA capacity
(kVA)
3
Output Watt Capacity
(watts)
2400
Output kW capacity
2.4
Output power factor
0.8
Nominal Output
Voltage(s) Supported
120V
Frequency compatibility
60 Hz
Output voltage
regulation (line mode)
-13% / +5%
Output voltage
regulation (Battery
mode)
+/- 5%
Built-in UPS output
receptacles
4 5-15R outlet(s); 4 5-15/20R outlet(s)
Built-in controllable
switched load banks
Three switchable single-outlet 5-15R load banks
Output circuit breaker
15A branch rated (x2) - each breaker protects 4 outlets
Output AC waveform
(AC mode)
Sine wave
Output AC waveform
(battery mode)
PWM sine wave
INPUT
Rated input current (at
maximum load)
22A
Nominal Input
Voltage(s) Supported
120V AC
UPS input connection
type
L5-30P
UPS Input cord length
(ft.)
8
UPS Input cord length
(m)
2.4
Recommended
Electrical Service
30A 120V
Input cord length (ft.)
8
Input cord length (m)
2.4
BATTERY
Full load runtime
(minutes)
7 min. (2400w)