background image

OUTPUT

Output Volt Amp
Capacity (VA)

3000

Output kVA capacity
(kVA)

3

Output Watt Capacity
(watts)

2400

Output kW capacity

2.4

Output power factor

0.8

Nominal Output
Voltage(s) Supported

120V

Frequency compatibility

60 Hz

Output voltage
regulation (line mode)

-13% / +5%

Output voltage
regulation (Battery
mode)

+/- 5%

Built-in UPS output
receptacles

4 5-15R outlet(s); 4 5-15/20R outlet(s)

Built-in controllable
switched load banks

Three switchable single-outlet 5-15R load banks

Output circuit breaker

15A branch rated (x2) - each breaker protects 4 outlets

Output AC waveform
(AC mode)

Sine wave

Output AC waveform
(battery mode)

PWM sine wave

INPUT

Rated input current (at
maximum load)

22A

Nominal Input
Voltage(s) Supported

120V AC

UPS input connection
type

L5-30P

UPS Input cord length
(ft.)

8

UPS Input cord length
(m)

2.4

Recommended
Electrical Service

30A 120V

Input cord length (ft.)

8

Input cord length (m)

2.4

BATTERY

Full load runtime
(minutes)

7 min. (2400w)