7
Buttons (Front Panel)
Basic Operation
“ON/OFF/STANDBY” Button
• To turn the UPS ON:
With the UPS plugged into a live AC wall outlet*,
press and hold the “ON/OFF/STANDBY” button for one second.** Release
the button. If utility power is absent, you can “cold-start” the UPS
(i.e.: turn it ON and supply power for a limited time from its batteries***)
by pressing and holding the “ON/OFF/STANDBY” button for one second.**
• To turn the UPS OFF:
With the UPS ON and receiving utility power, press
and hold the “ON/OFF/STANDBY” button for one second.** Then unplug
the UPS from the wall outlet. The UPS will be completely OFF.
* After you plug the UPS into a live AC outlet, the UPS (in ”Standby” mode) will
automatically charge its batteries, but will not supply power to its outlets until it is
turned ON.
** The alarm will beep once briefly after the indicated interval has passed.
*** If fully charged.
“MUTE/TEST” Button
To Silence (or “Mute”) UPS Alarms:
Briefly press and release the MUTE/
TEST button.
Note:
To permanently disable audible UPS alarms: Contact Tripp Lite support for
instructions.
To Run a Self-Test:
With your UPS plugged in and turned ON, press and
hold the MUTE/TEST button. Continue holding the button until the alarm
beeps several times and the UPS performs a self test. See “Results of a
Self-Test” below.
Note:
you can leave connected equipment on during a self-test. Your UPS, however,
will not perform a self-test if the UPS is not turned on (see “ON/OFF/STANDBY” Button
description).
CAUTION! Do not unplug your UPS to test its batteries. This will
remove safe electrical grounding and may introduce a damaging
surge into your network connections.
Results of a Self-Test:
The test will last approximately 10 seconds as the
UPS switches to battery to test its load capacity and battery charge.
• If the red “OUTPUT LOAD LEVEL” LED remains lit and the alarm continues
to sound after the test, the UPS’s outlets are overloaded. To clear the
overload, unplug some of your equipment and run the self-test repeatedly
until the red “OUTPUT LOAD LEVEL” LED is no longer lit and the alarm is
no longer sounding.
CAUTION! Any overload that is not corrected by the user immediately
following a self-test may cause the UPS to shut down and cease
supplying output power in the event of a blackout or brownout.
• If the “BATTERY WARNING” LED remains lit and the alarm continues to
sound after the test, the UPS batteries need to be recharged or replaced.
Allow the UPS to recharge continuously for 12 hours, and repeat the self-
test. If the LED remains lit, contact Tripp Lite for service. If your UPS
requires battery replacement, visit www.tripplite.com to locate the specific
Tripp Lite replacement battery for your UPS.
12-10-307-93-3181.indb 7
11/2/2012 9:27:47 AM