overvoltages
Maintaints continuous operation through blackouts, voltage fluctuations and surges
Corrects line voltage conditions as low as 83V and as high as 145 back to selectable 100/110/120V nominal values
Standard internal battery set offers 16 minutes at half load (800w) and 6 minutes at full load (1600w)
Optional BP48V24-2U and BP48V60RT3U external rack/tower battery packs enable extended runtime operation
Compact rackmount form factor installs using only 2 rack spaces (2U) with a maximum installed depth of only 19 inches
Ships with all mounting accessories for 4 post rackmount installation
Optional 2POSTRMKITWM enables 2 post rackmount or wallmount installation
Optional 2-9USTAND accessory enables small-footprint upright tower placement
Network interfaces support simultaneous communications via built-in USB, DB9 serial and SNMPWEBCARD slot
HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, with
the built-in ability to shutdown any number of additional servers over IP
UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current,
battery capacity, AC line frequency, timed inverter sutoff, activate self-test, load bank output power control and remote reboot
Built-in Emergency Power Off (EPO) interface with cable
NEMA 5-20P input plug (user-installable NEMA 5-15P replacement plug included) / NEMA 5-15R & NEMA 5-15/20R output receptacles
Integrated 3 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (Each
bank controls 1 outlet per load bank)
Front panel LEDs offer current monitoring and battery charge level information
UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user required
$250,000 ULtimate Lifetime Insurance
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
2200
Output kVA capacity
(kVA)
2.2
Output Watt Capacity
(watts)
1600
Output kW capacity
1.6
Output power factor
0.7
Nominal Output
Voltage(s) Supported
100V; 110V; 120V
Nominal Voltage details
120V default (voltage selection via back panel dipswitches)
Frequency compatibility
50 / 60 Hz
Output voltage
regulation (line mode)
-14%, +6%
Output voltage
regulation (Battery mode)
+/- 5%
Built-in UPS output
receptacles
4 5-15R outlet(s); 4 5-15/20R outlet(s)
Built-in controllable
switched load banks
Three switchable single-outlet 5-15R load banks
Basic PDU options
PDU1220
(1U / 13 5-15/20R outlets);
PDUNV
(1U / 2 C19, 12 C13 outlets);
PDUV20
(0U / 12 5-15/20R outlets);
PDU40TDUAL
(0U / 40 5-15/20R outlets)
Metered PDU options
PDUMH20
(1U / 13 5-15/20R outlets);
PDUMH20
AT (1U / 16 5-15/20R outlets)*;
PDUMV20
(0U / 16 5-15/20R
outlets);
PDUMV40
(0U / 32 5-15/20R outlets)
Switched PDU options
PDUMH20ATNET
(1U / 16 5-15/20R outlets)*;
PDUMV20NET
(0U / 24 5-15/20R outlets)