16
Specifications
(Corded Models)
CORDED MODELS:
APSINT1012
Weight:
11.9 Kg
INVERTER
Continuous power (@ 20° C):
1000 W
Surge power (5 seconds):
2000 W
Efficiency (Full Load):
88%
Minimum DC Fuse Rating:
170A
DC Input Current @ Nominal V DC
Full Load
95A
No Load
2.6A*
Nominal Input Volts:
12 VDC
DC Input Voltage Range:
10-15 VDC
Nominal Output Volts:
230 VAC ±5%
Nominal Output Frequency:
50† Hz ±.3%
BATTERY CHARGER
Charging Capacity DC:
30 A
Maximum Cable Length
2 ft.
Acceptance Volts VDC:
Selectable
14.4 V**/14.2 V Wet**/Gel
Float Volts VDC (w/gel):
13.3 V (13.6 V)
Input Voltage AC:
230 V
Input Current AC:
3.3 A
LINE VAC OPERATION
Minimum Input AC Volts:
Selectable 144**,163, 182 or 201VAC
Maximum Input AC Volts
(Continuous, Charger at Maximum):
Selectable 259** or 264 VAC
Maximum Input Current
(Continuous, Charger at Maximum):
12.0 A
Input Frequency:
50 Hz ±10%
Maximum Output AC (Continuous):
4.3 A
Automatic Transfer Time:
4-6 ms
* Load sense can reduce this to 1/30 of the listed current. **Factory default setting.
† A technician may be able to convert your UPS to receive 60 Hz ±10%power. Consult Tripp Lite for details.
200106010 230V APS Owners Manual.qxd 1/3/02 5:18 PM Page 16