15
Try these remedies for common APS problems before calling for help. Call Tripp Lite Customer Service at (773)
869-1234 before returning your APS for service.
SYMPTOM
PROBLEMS
CORRECTIONS
APS does not provide
APS not properly connected to
Connect APS to utility power.
AC output (AC input present)
utility power.
Circuit breaker is tripped.
Reset circuit breaker.
APS shutdown due to excessive
Turn APS “OFF”. Wait 1 minute and
battery voltage, indicating possible
switch to “AUTO/REMOTE”.
charger failure. Line disconnected
to prevent permanent battery
damage.
APS is set to “OFF”
Set APS to “AUTO/REMOTE” or
“CHARGE-ONLY”.
APS does not provide
Circuit breaker is tripped.
Reset circuit breaker.
AC output (AC input absent)
Operating Mode Switch is set
Set Operating Mode Switch to
to “CHARGE ONLY”.
“AUTO/REMOTE.”
Load or High Temperature fault.
Turn APS “OFF”. Wait 1 minute.
Remove overload. Switch to
“AUTO/REMOTE”.
Excessive battery discharge.
Check battery condition.
APS will not charge the
Connected batteries are dead.
Check and replace old batteries.
battery (AC input present)
Battery fuse* is blown.
Check and replace fuse.
Battery cabling* is loose or degraded. Check and tighten or replace cabling.
APS charger failure.
Turn APS “OFF”. Wait 1 minute and
switch to “AUTO/REMOTE”. If
automatic shutdown occurs, call
Tripp Lite Customer Service.
All APS Indicator Lights are
This is normal if the APS is set
—
OFF (AC input absent)
to “CHARGE-ONLY”
All APS Indicator Lights are
Excessive battery discharge.
Use an auxiliary charger* to raise
OFF (AC input is present or
battery voltage. Check external
absent)
battery connections and fuse.
Automatically resets when condition
is cleared.
All APS Battery Indicator
Excessive battery discharge.
Use an auxiliary charger* to raise
Lights are slowly flashing.
battery voltage. Automatically resets
when condition is cleared.
APS “LOAD” Battery Light
Inverter shutdown because battery
Reset by cycling control switch to
flashing
voltage dropped too low for more
“OFF” position then to “AUTO/
than 5 seconds. Protects battery
REMOTE”.
from permanent damage.
All APS Battery Lights are
High battery voltage shutdown
Check all charging sources. Reset by
rapidly flashing
during Charge mode.
cycling control switch to “OFF” then
to “AUTO/REMOTE” or “CHARGE-
ONLY”.
APS “LOAD” Indicator Light
Inverter overload caused by
Reset by reducing load and cycling
is rapidly flashing
excessive load or short circuit.
control switch to “OFF” position then
If sustained for more then 5
to “AUTO/REMOTE”.
seconds the Inverter is shutdown.
* User supplied
Troubleshooting