background image

 

[

6

]

 

 

 3 – Battery Cabinet Installation

 (continued)

 

 

 

 3-4 Internal Wiring (Typical) 

 

 

Battery cabinets use multiple 6 VDC or 12 VDC batteries connected in series to provide nominal DC voltages ranging from 
240 VDC to 480 VDC. 

 

Internal cabling is sized for specific application load currents. The insulated cables can be 2 AWG, 4 AWG, 2/0 AWG, 4/0 
AWG or dual 2/0 AWG. 

 

Each battery cabinet includes a specific wiring diagram. Some battery cabinets may contain series-parallel battery strings. 
Others may require a single series string that occupies more than one cabinet. The installer must complete the series 
connections between separate cabinets when the series string occupies more than one cabinet. The cables, hardware and 
instructions required to complete the connection will be inside one of the cabinets. 

 

Battery cabinets that include a molded case circuit breaker may or may not use a fuse. 

 

All fuses, disconnect switches and circuit breakers are in the top tier of the battery cabinet. 

 

Terminal blocks, copper bussing or direct circuit breaker connections for connecting to the load are in the top tier of the 
battery cabinet. 

 

All load connection polarities will be marked by a POS (+) or NEG (-) label. 

 

Some battery cabinets are provided with a two-pole branch circuit overcurrent protection device. These cabinets may be 
wired directly to the load or UPS. 

 

Some battery cabinets are not provided with branch circuit overcurrent protection. The installer must supply an easy-access 
disconnect and branch circuit overcurrent protection device rated in accordance with all applicable electrical codes. 

WARNING: To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent protection 
rated in accordance with the National Electrical Code (NEC), ANSI/NFPA 70.

 

 

If the battery cabinet includes an integrated battery charger (“C” models only), the internal cabinet wiring will be preinstalled 
and the charger will include fusing for 120 VAC input. 

The charger input must be connected to a separate AC supply 

circuit (30 A, 120 VAC, 60 Hz), not the UPS system.

 

 

 3-5 Preliminary Electrical Check 

 

1.

 

Measure the battery cabinet output voltage at the output load connection points. (Measure voltage with a digital voltmeter.) 

2.

 

The measured voltage should approximately match the voltage listed on the battery cabinet nameplate. The battery cabinet 
output voltage will be equal to the number of individual batteries installed in series multiplied by the unit voltage. (For 
example: 40 batteries x 12.84 VDC = 513.6 VDC output; 40 batteries x 6.42 VDC = 256.8 VDC output.) 

3.

 

If the measured voltage is significantly different than anticipated, determine the cause (e.g. low charge, shorted cell, reversed 
battery, faulty wiring) and correct the voltage disparity before proceeding. 

 

 3-6 Battery Cabinet Placement 

 

Place the battery cabinet in a cool location with free airflow that is away from direct heat sources. The lifespan of a battery can be 
affected dramatically by elevated temperature, decreasing 50% for each 15° above 77° F. 

 

1.

 

Prepare the surface where the cabinet will be placed. The surface must be clean, flat and able to support the battery cabinet 
and other equipment installed nearby. (See 

Section 7-1

 for floor loading specifications.) 

2.

 

Allow adequate clearance around the battery cabinet for ventilation and maintenance. The front panel must be accessible and 
removable to allow easy access to internal batteries, internal fuses and other overcurrent protection devices. (See 

Section 7-1

 

for dimensions. See 

Section 6-1 or 6-2

 for detailed battery cabinet measurements.) 

3.

 

If the cabinet will be anchored to the floor, install appropriate anchor bolts in the mounting hole at the bottom of the cabinet. 
Use washers to create a level surface between the mounting areas around the anchor bolts. 

4.

 

Using extreme caution, remove the bolts securing the battery cabinet to the shipping pallet. 

5.

 

Forklift forks should be at maximum width within the cabinet clearance opening and fully inserted to prevent tipping. Lift 
cabinet from bottom only. Be careful not to damage the sheet metal floor of the cabinet with the forks. 

6.

 

If the battery cabinet will be secured to the floor, carefully align and lower the battery cabinet down on the floor anchor bolts 
and secure it in place. 

7.

 

If the cabinet will not be secured to the floor, lower it into the designated space and then level it using shims. (Leveling does 
not affect performance but does align the battery cabinet with other equipment in the facility.) 

 

Summary of Contents for 3-Phase Battery Cabinet Extended-Run

Page 1: ...Check 4 Operation and Charging 4 1 Determine Charging Voltages 4 2 Initial Charge 4 3 Operational Check 4 4 Acceptance Test Optional 5 Maintenance 5 1 Maintenance Schedule 5 2 Fuse Replacement 6 Diag...

Page 2: ...ropriate ventilation and convection cooling of the individual batteries is provided via inch spacing between batteries Front and rear vents allow the free flow of warmer air out of the battery cabinet...

Page 3: ...e support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recom...

Page 4: ...h any object Do not lay tools or metal parts on top of batteries Replace batteries with equivalent batteries same number and type available from Tripp Lite The batteries are recyclable Refer to local...

Page 5: ...Fully extend forks under load Spread forks to maximum possible width under load Lift cabinet from bottom only Wear safety shoes Confirm that load limits for freight elevators handling equipment and f...

Page 6: ...the output load connection points Measure voltage with a digital voltmeter 2 The measured voltage should approximately match the voltage listed on the battery cabinet nameplate The battery cabinet out...

Page 7: ...4 The top and sides of the battery cabinet include knockouts for load connection cable entry Punch out the appropriate knockout and connect the conduit or cable bushing 5 The output terminal blocks f...

Page 8: ...attery terminals 2 Measure and record the system float current using a clamp on ammeter 3 Measure and record the float voltage of individual battery units 4 Measure and record the temperature of sever...

Page 9: ...annual check 2 Use insulated tools to tighten all connections to the recommended torque See Section 7 2 for recommended torque values 3 Optional Measure inter battery connection resistance 5 2 Fuse Re...

Page 10: ...s are in inches Conduit Knockouts Conduit Knockouts Breaker Mounting Plate 79 4 5 4 38 15 75 6 4 5 2 25 22 8 25 24 75 16 16 16 4 11 75 5 5 40 25 30 25 6 6 34 5 17 25 Side View Side View Front View Sid...

Page 11: ...e All dimensions are inches 58 Front of Cabinet Front of Cabinet Breaker Mounting Plate Conduit Knockouts Conduit Knockouts 15 75 2 25 Side View Side View Side View Side View Bottom View Top View Fron...

Page 12: ...0 VDC Breaker is UL listed and rated for 150 A 600 VDC 25 KAIC Cabinets with breakers are shipped with the breaker in the off open position Battery arrangements shown are typical but may vary dependin...

Page 13: ...250 A 600 VDC 25 KAIC Cabinets with breakers are shipped with the breaker in the off open position Battery arrangements shown are typical but may vary depending on cabinet and battery type Shelf 1 Bo...

Page 14: ...suitable for 120 VAC input Temperature compensation with remote battery temperature sensor Auxiliary output circuit for Charger OK indicator 6 25 MAX 0 5 12 5 13 5 Terminal Block Detail Input Voltage...

Page 15: ...cm 2284 lb 1038 kg 271 lb ft 2 1322 kg m 2 BP348V78 4 40 25 x 30 25 x 79 inches 102 2 x 76 8 x 200 7 cm 2545 lb 1157 kg 301 lb ft 2 1474 kg m 2 BP348V103 4 40 25 x 30 25 x 79 inches 102 2 x 76 8 x 20...

Page 16: ...rs should contact Tripp Lite support at intlservice tripplite com THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUSE OR NEGLECT SELLER MAKES NO EXPRESS WARRA...

Reviews: