NEMA-4 Mounting

Put the unit through the panel cut out (See drawings at the back of this guide). Slide the clamps (packed 
with product) into every hole provided around the case. Tighten the clamping screws in an even pattern 
until the unit is secured in the panel. Screw torque: 3.5-4.7 Nm. This ensures a waterproof seal
and prevents the panel from being deformed.

VESA Mounting

There are 4 holes on back panel for atatching the VESA mount. The screw: M4 0.7mm, length:
shorter then 8.0mm, and screw torque: 4.7 Nm.

 

DO NOT OVER TIGHTEN MOUNTING CLAMPS!

 

To seal to NEMA-4 specifi cations, all supplied mounting clamps must be used and panel cannot 
fl ex more than 0.253mm.

POWER CONNECTIONS

Make sure that all local and national electrical standards are met when installing the unit.
Contact your local authorities to determine which codes apply.

Power Requirements

The 

UNIPLAY

 is powered by d.c. power only. The speci

fi

 ed voltage range is 24±20% Volts d.c. This insures 

compatibility with most controller d.c. systems.
The power conditioning circuitry inside the unit is accomplished by a switching power supply. The peak 
starting current can be as high as 2A.

Fusing Requirements

If the display does not come on within 5 seconds of power up, switch off the power. An internal fuse will 
prevent damage if the polarity of the d.c. power is incorrect. Check wiring to insure proper connections and 
try to power up again.

High Voltage

An Internal fuse will prevent damage for over voltage condition however it is not guaranteed.
D.c. voltage sources should provide proper isolation from main a.c. power and similar hazards.

Emergency Stop

A Hard-wired EMERGENCY STOP should be 

fi

 tted in any system using an 

UNIPLAY

 to comply with ICS Safety 

Recommendations.

Summary of Contents for UNIPLAY

Page 1: ... Please refer to the Motion Coordinator Technical Reference Manual for Full Details HMI UNIPLAY Quick Connection Guide H H IPLAY HM HM PLAY MI MI ...

Page 2: ...it in areas subject to explosion hazards due to flammable gases vapours or dusts The unit should not be installed where large temperature variations and or high humidity is present This will cause condensation in the device Do not install UNIPLAY in environments where have inflammable gases MOUNTING Care should be taken when locating equipment behind the unit to ensure that a c power wiring PLC ou...

Page 3: ...unit Contact your local authorities to determine which codes apply Power Requirements The UNIPLAY is powered by d c power only The specified voltage range is 24 20 Volts d c This insures compatibility with most controller d c systems The power conditioning circuitry inside the unit is accomplished by a switching power supply The peak starting current can be as high as 2A Fusing Requirements If the...

Page 4: ...r screw counterclockwise until the gap is wide open insert the wire all the way in and turn the screw clockwise until tight Connect positive d c line to the 24V terminal and the d c ground to the 0V terminal Grounding Requirements A CHASSIS GROUND MUST BE USED The d c ground is not directly coupled to Earth ground internally It is not advisable to ground the d c negative return to chassis ground a...

Page 5: ...ed to connect the UNIPLAY screen to a Motion Coordinator or Ethernet switch Speaker An external speaker buzzer may be used for greater keypress feedback Connection is via a 3 5mm mono jack plug DIP switch settings SW1 SW2 SW3 SW4 Mode ON OFF OFF ON Touch Screen Calibrate mode OFF ON OFF ON Hide HMI System Setting Bar OFF OFF ON ON Boot Loader mode OFF OFF OFF ON Normal OFF OFF OFF OFF Not Supporte...

Page 6: ... operator HMI screens which are transferred to the UNIPLAY HMI by the Motion Coordinator at runtime Trio recommend using a USB powered switch CONFIGURATION RUNNING Default controller address 192 168 0 250 Default HMI IP address 192 168 0 251 To change the controller IP address the HMI requires use Motion Perfect v3 ...

Page 7: ......

Page 8: ...om3 RS485 Com3 RS232 B Fuse H Com1 RS232 Com2 RS232 C Power connector I Ethernet port D VESA 75mm screw holes J USB Host port E Line out K USB Client port F SD card slot UNIPLAY 7 200 35mm 146 35mm 138mm 192mm 42 55mm R2mm CUTOUT DIMENSIONS A C B D E G F H I K J ...

Page 9: ...UNIPLAY 10 270 97mm 212 97mm 201mm 259mm 50mm R2mm CUTOUT DIMENSIONS A C B D E G F H I K J ...

Page 10: ...quick start v1 July 2012 Trio Motion Technology Ltd Trio Motion Technology LLC Trio Shanghai Trio India WWW TRIOMOTION COM ...

Reviews: