XPERT-PRO – Operational Manual
TRINITY
[13]
3. In case, your setting is incomplete, precede as above steps 1 and 2.
Setting CT Primary
CT Primary should be selected at site so as to give the actual current for CT
operated meters. The CT Primary can be selected from 5 to 5000.
To retrieve the CT Primary, precede the following instructions.
1. In Run Mode, press
key for about five seconds and then the unit displays
the first programmable parameter, DEMAND ON. Press
keys several
times to retrieve the programmable parameter, CT PRIMARY such as shown
below.
2. Press
key again. Immediately ‘P’ starts blinking which shows that the
parameter can now be selected. Select the CT PRIMARY by pressing
and
keys according to your desire and then press
key to save the
parameter. However, the unit will reset and return into Run Mode.
3. In case, your setting is incomplete, precede as above steps 1 and 2.
Setting CT Secondary
CT Secondary should be selected at site so as to give the actual current for CT
operated meters. CT Secondary can be selected to either 1 or 5.
To retrieve the CT Secondary, precede the following instructions.
1. In Run Mode, press
key for about five seconds and then the unit displays
the first programmable parameter, DEMAND ON. Press
keys several
times to retrieve the programmable parameter, CT Secondary such as shown
below.
2. Press
key again. Immediately ‘P’ starts blinking which shows that the
parameter can now be selected. Select the CT SECONDARY by pressing
CT SEC
5
CT PRIMARY
225