Diodes that are used as blocking diodes must have: 

 

Rated  Average  Forward  Current  [IF  (AV)]  above  the  maximum  system  current  at  the  highest  module  operating 
temperature. 

 

Rated  Repetitive  Peak  Reverse  Voltage  [VRRM]  above  the  maximum  system  voltage  at  the  lowest  module 
operating temperature. 

 

13.

 

WARNING 

These solar modules do not contain any user serviceable parts, 
If you suspect that your installation is not working properly, then contact your installer immediately. 

1.

 

Contact your installer 

2.

 

Contact Trina Solar after sales service team at:

 

http://customerservice.trinasolar.com

 

3.

 

Submit the Customer Feedback form at:

 

www.trinasolar.com

, one of our technical service representatives will 

contact you as quickly as possible. A username and password is required to send feedback from the 
customer service link 

WARNING:  For any electrical  maintenance,  the  PV  system  must  first be shut down. Improper maintenance 
can cause lethal electric shock and/or burns. 

 

14.

 

CHANGE HISTORY 

Installation Manual of Dual Glass (Hook 4x150/4x240)_20160414_Rev A 

Summary of Contents for DUOMAX

Page 1: ...G5 47 TSM PDG14 40 TSM PDG14 47 Duomax TSM PEG40 40 TSM PEG40 47 TSM PEG5 40 TSM PEG5 47 TSM PEG14 40 TSM PEG14 47 Duomax M Plus TSM DEG40 40 TSM DEG40 47 TSM DEG5 40 TSM DEG5 47 TSM DEG14 40 TSM DEG14 47 TSM DEG40 40 II TSM DEG40 47 II TSM DEG5 40 II TSM DEG5 47 II TSM DEG14 40 II TSM DEG14 47 II ...

Page 2: ...L CONDITIONS AND SITE SELECTION 4 5 1 CLIMATE CONDITION 4 5 2 SITE SELECTION 4 6 MOUNTING INSTRUCTIONS TRINA HOOK 4 6 1 COMPONENTS OVERIEW 4 6 2 MOUNTING METHODS 5 6 3 REMARKS OF INSTALLATION 6 7 MODULE WIRING 8 8 MODULE TILT ANGLE 8 9 MECHANICAL DRAWING OF PV MODULE 8 10 MAINTENANCE AND CARE 9 11 SPECIFICATIONS 9 12 BYPASS DIODES AND BLOCKING DIODES 9 13 WARNING 10 14 CHANGE HISTORY 10 ...

Page 3: ...e sure that the polarity of each module or a string is not reversed relative to the other the modules or strings 14 Artificially concentrated sunlight should not be used on the PV module 15 In markets conforming to IEC standard maximum system voltage must not exceed 1500V DC In markets conforming to UL standard maximum system voltage must not exceed 1000V DC For roof use the maximum system voltage...

Page 4: ...by buildings trees chimney etc at any time of the day 3 Do not install in corrosive environments such as beaches or landfill that can be easily flooded 4 Do not install PV modules in a location where modules could be immersed in water or continually exposed to water from a sprinkler or fountain 5 Do not install PV modules over naked flames or flammable materials 6 Interspaces the clearance between...

Page 5: ...e beginning the installation Also be sure that the site has been completely prepared before beginning the installation STEP 1 Install the specified bolts Setting the specified bolts into the hook STEP 2 Insert the bolt hole 1 Lift up the module ensure the bolt over the racking 2 Aim the bolt to racking 3 Insert the bolt hole STEP 3 Tighten the nut M8 Tighten to a torque of 16 20N m M10 Tighten to ...

Page 6: ...il 2016 Doc No PS M 0433 Ver A Page 6 of 10 Tighten the nut 16N m 20N m STEP 4 Install the module Repeat steps 1 3 install the module 6 3 REMARKS OF INSTALLATION Keep more than 10 mm gap between each module Gap ...

Page 7: ...ead of the insert place As shown above Note For PV module landscape installation the supporting rails need change as shown in below add two rails For 60 cell Duomax module For 72 cell Duomax module Note Please consult with Trina Solar engineers to confirm whether the rail match Trina hook or not ...

Page 8: ...Datasheet Specifications for the maximum electrical rating of series fuse 8 MODULE TILT ANGLE Trina Solar PV modules connected in series should be installed at the same orientation and angle Different orientation or angle may cause loss of output power because each module may be exposed to different amounts of solar irradiation Trina Solar PV modules produce the most power when they are perpendicu...

Page 9: ...Association Through the pre financed PV Cycle program Trina Solar PV modules will be taken back and treated in an environmentally sustainable manner WARNING For any electrical maintenance the PV system must first be shut down Improper maintenance can cause lethal electric shock and or burns 11 SPECIFICATIONS For module specifications please see the Datasheet included in the shipment carton and vis...

Page 10: ...allation is not working properly then contact your installer immediately 1 Contact your installer 2 Contact Trina Solar after sales service team at http customerservice trinasolar com 3 Submit the Customer Feedback form at www trinasolar com one of our technical service representatives will contact you as quickly as possible A username and password is required to send feedback from the customer se...

Reviews: