background image

FIGURE 4.  WIRING DIAGRAM  

(CONNECTED TO 24V POWER USING COMPATIBLE FACP WITH “SOUNDER BASE STANDBY POWER MONITORING” ENABLED)

FIGURE 5. WIRING DIAGRAM (CONNECTED TO NAC OR 24V POWER; OPTIONAL EOL DEVICES FOR CONSTANT SUPERVISION)

(+) SLC

(–) SLC

(–) CONSTANT POWER

(–) NAC

(+) CONSTANT POWER

(+) NAC

U

.L.

 LISTED COMP

ATIBLE

CONTR

OL P

ANEL

OPTIONAL REMOTE

ANNUNCIATOR MODEL

TR-RA100Z

CLASS A OPTIONAL WIRING

FIRST

SOUNDER

BASE

SECOND

SOUNDER

BASE

LAST

SOUNDER

BASE

N

OT

USED

SLC +

EXT –

EXT +

RA

SLC –

N

OT

USED

SLC +

EXT –

EXT +

RA

SLC –

N

OT

USED

SLC +

EXT –

EXT +

RA

SLC –

(+)

(+)

(+)

(–)

(–)

(–)

EOL

A SEPARATE SYNCHRONIZATION MODULE MAY BE USED TO PROVIDE
THE SYNCHRONIZATION PULSES  (SEE FIGURE 6)

/

/

HORN

HORN

HORN/STROBE

FIRST

SOUNDER

BASE

SECOND

SOUNDER

BASE

LAST

SOUNDER

BASE

N

OT

USED

SLC +

EXT –

EXT +

RA

SLC –

N

OT

USED

SLC +

EXT –

EXT +

RA

SLC –

N

OT

USED

SLC +

EXT –

EXT +

RA

SLC –

(+) SLC

(–) SLC

(–) NAC OR CONSTANT POWER*

(+) NAC OR CONSTANT POWER*

(+) NAC

(–) NAC

OPTIONAL REMOTE

ANNUNCIATOR MODEL

TR-RA100Z

(+)

(+)

(+)

EOL

A SEPARATE SYNCHRONIZATION MODULE MAY BE 
USED TO PROVIDE THE SYNCHRONIZATION PULSES

HORN

HORN/STROBE

UL LISTED COMP

ATIBLE

CONTR

OL P

ANEL

UL LISTED 24V  PO

WER  SUPPL

*WHEN USING 24V CONSTANT POWER
(AUX POWER), ADDITIONAL POWER
SUPERVISION RELAYS AND MODULES WILL
BE REQUIRED FOR PROVIDING SUPERVISION
WHEN THE SOUNDER BASES ARE INACTIVE.

CLASS A OPTIONAL WIRING

(–)

(–)

(–)

/

/

EOL

/

/

HORN

C0474TRG-24

C0474TRG-25

NOTE: Only use this wiring diagram when connecting to 24VDC power using a FACP listed in the table on page 1. Please consult your FACP manufacturer for 
panel-specific wiring configurations and special cases.
Additional Audible Visible devices may be connected to the same power supply or the the NAC output of the Fire Alarm Control Panel (FACP) to provide a syn-
chronized communication of the alarm signal.

(SEE FIGURE 6)

NOTE: Only use this wiring diagram when connecting to a NAC or a 24V power supply that does not support “sounder base standby power monitoring”  
(see page 1). 

I56-4151TRG-005 

4/22/2021

Summary of Contents for TR-B200S-LF-WH

Page 1: ...setting 15 mA maximum 33 0 VDC 90 mA maximum 24 0 VDC 20 mA maximum 24 0 VDC 140 mA maximum 16 0 VDC 25 mA maximum 16 0 VDC SLC Electrical Ratings SLC Operating Voltage 15 to 32 VDC SLC Standby Current 300 μA maximum base only refer to applicable sensor specification Sound Output High Volume Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet 3 1m 24 Volts in continuous tone L...

Page 2: ...6 Install a compatible smoke sensor as described in the installation manual for the sensor CAUTION Do not over tighten mounting plate screws this may cause mounting plate to flex TAMPER RESISTANT FEATURE NOTE Do not use the tamper resist feature if the removal tool is to be used This detector base includes a tamper resist feature that prevents its removal from the base without the use of a tool To...

Page 3: ...AC OPTIONAL REMOTE ANNUNCIATOR MODEL TR RA100Z E O L A SEPARATE SYNCHRONIZATION MODULE MAY BE USED TO PROVIDE THE SYNCHRONIZATION PULSES HORN HORN STROBE UL LISTED COMPATIBLE CONTROL PANEL UL LISTED 24V POWER SUPPLY WHEN USING 24V CONSTANT POWER AUX POWER ADDITIONAL POWER SUPERVISION RELAYS AND MODULES WILL BE REQUIRED FOR PROVIDING SUPERVISION WHEN THE SOUNDER BASES ARE INACTIVE CLASS A OPTIONAL ...

Page 4: ...90 02 NOTE Wiring shown for System Sensor MDL Series Sync Module For additional wiring configurations see your sync module manual FACP 1 EOL 1 HORN CONTROL ZONE 1 IN ZONE 2 IN SLAVE IN ZONE 1 OUT ZONE 2 OUT NAC SLAVE IN SLAVE OUT TEMP JUMP OFF NAC 1 B B NAC 2 B B NAC 3 B B TO NEXT DEVICE OR EOL 1 TO NEXT DEVICE OR EOL 1 2 CLASS B ZONES MASTER SOUNDER BASE SOUNDER BASE OPTIONAL Triga is a trademark...