background image

Commissioning

DALI XC_IB 3.0 | 01.2014 | en

16

5.3

Finishing commissioning

1. Hold down momentary-action switch (approx. 10 s).

1 beep sounds after 3 s.

1 beep sounds after another 3 s.

3 beeps sound after another 4 s.

2. Release momentary-action switch.

Programming mode is terminated.

System is ready again.

Figure 6: Finishing commissioning

i

Note

If no momentary-action switches are pressed for 10 minutes in programming mode, this mode is
automatically terminated.

Summary of Contents for LuxControl DALI XC

Page 1: ...luxCONTROL DALI XC ...

Page 2: ...ufacturer Document number Copyright Tridonic GmbH Co KG All rights reserved Tridonic GmbH Co KG Färbergasse 15 6851 Dornbirn Austria Tel 43 0 5572 395 0 Fax 43 0 5572 20176 www tridonic com DALI XC_IB 3 0 01 2014 en ...

Page 3: ... luminaires 16 5 3 Finishing commissioning 17 6 Saving scenes 18 7 Regrouping luminaires 21 8 Operation 21 8 1 Changing intensity 21 Single momentary action switch control 8 1 1 22 Double momentary action switch control 8 1 2 23 8 2 Changing colour temperature 23 8 3 Recalling scenes 24 9 System extension 24 9 1 Starting system extension 26 9 2 Adding or changing luminaires 27 9 3 Adding or changi...

Page 4: ...ter symbol Description 1 Individual steps in the instructions are numbered Single step instructions are indicated by at the beginning of the line After a step has been described a description of the expected results will follow These results are indicated by at the beginning of the line Requirements which need to be checked before carrying out a step are indicated by i Notes can be recognised by i...

Page 5: ...ecified Relevant health and safety regulations must be observed When assembling and installing the device the voltage supply must be disconnected Only qualified personnel may assemble install and commission the device If an error occurs dangerous voltage levels may be present at the DALI terminals and on the DALI control line ...

Page 6: ...Device description DALI XC_IB 3 0 01 2014 en 6 3 Device description Figure 1 DALI XC input device 1 Terminals 2 Config rotary selector switch 3 Mode rotary selector switch ...

Page 7: ... is not turned to a marked position the DALI XC will not function MC operating mode Rotary selector switch position A Single momentary action switches and or double momentary action switches and or standard switches can be used to recall programmed functions The MC operating mode can only be configured using the masterCONFIGURATOR software versions 2 10 and higher The device does not function in M...

Page 8: ...tension is typically started in this operating mode If the lighting system is in programming mode the momentary action switches connected to the DALI XC in GC operating mode can be used to group luminaires A DALI XC device in GC operating mode can replace the DALI GC art No 24033450 Prog operating mode Rotary selector switch position F Commissioning or a system extension can be started and complet...

Page 9: ... of the individual devices can be found in the associated data sheets The following information applies to the use of the DALI XC in the comfortDIM system Assigning groups to inputs DALI XC in GC A or GC operating mode Rotary selector switch position D or E The Config rotary selector switch is used to assign different groups to input T1 and T2 and input T3 and T4 The following table uses the rotar...

Page 10: ...e group can be changed with input T1 and T2 and the colour temperature of Tunable White luminaires in the group can be changed with input T3 and T4 The following table uses the rotary selector switch position to indicate which group is assigned to the DALI XC Rotary selector switch position Group 0 all 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 Table 3 Assigning groups...

Page 11: ...owing table uses the rotary selector switch position to indicate which scene is assigned to the inputs Rotary selector switch position Scene Input T1 Input T2 Input T3 Input T4 0 1 2 3 4 1 2 3 4 5 2 3 4 5 6 3 4 5 6 7 4 5 6 7 8 5 6 7 8 9 6 7 8 9 10 7 8 9 10 11 8 9 10 11 12 9 10 11 12 13 10 11 12 13 14 11 12 13 14 15 12 13 14 15 16 13 14 15 16 1 14 15 16 1 2 15 16 1 2 3 Table 4 Assigning scenes to i...

Page 12: ...er mode so that it can be operated as an input device The device must be accessible in the concealed box for this to take place Alternatively a DALI XC device can be connected to the DALI control line at an accessible point e g the distribution board for commissioning purposes only Commissioning consists of three steps 1 Start commissioning If the DALI XC devices in the lighting system can be acce...

Page 13: ...ld down momentary action switch approx 10 s 2 beeps sound at the beginning 3 beeps sound after another 10 s 2 Release momentary action switch Assignment of all luminaires to groups has been deleted Programming mode is enabled All luminaires are dimmed to the minimum value All luminaires are brightened one after the other All luminaires are then dimmed to the minimum value again 1 beep sounds One l...

Page 14: ...ase momentary action switch 1 beep sounds 3 Hold down momentary action switch approx 3 s 2 beeps sound after 1 s 3 beeps sound after another 2 s 4 Release momentary action switch Assignment of all luminaires to groups has been deleted Programming mode is enabled All luminaires are dimmed to the minimum value All luminaires are brightened one after the other All luminaires are then dimmed to the mi...

Page 15: ... The DALI XC beeps once every time a momentary action switch is pressed 1 Use a momentary action switch to select the desired luminaire Luminaire brightens i Note From now on use the momentary action switch to which the desired group is assigned Section Project design describes how to determine which group is assigned to which input Go to Section Project design 2 Hold down momentary action switch ...

Page 16: ...p sounds after 3 s 1 beep sounds after another 3 s 3 beeps sound after another 4 s 2 Release momentary action switch Programming mode is terminated System is ready again Figure 6 Finishing commissioning i Note If no momentary action switches are pressed for 10 minutes in programming mode this mode is automatically terminated ...

Page 17: ...ry action switch to which the desired scene is assigned Section Project design describes how to determine which scene is assigned to which input Go to Section Project design 1 Hold down momentary action switch approx 10 s 1 beep sounds 2 Release momentary action switch 2 beeps sound The current intensities and colour temperature values for all luminaires are saved as a scene or 2 Hold down the mom...

Page 18: ... assigned to both groups To change the assignment i e move a luminaire from one group to another the existing assignment must first be deleted and the luminaire must then be reassigned to the desired group This process is described in this section 2 Regroup all luminaires re initialisation If more than one luminaire must be regrouped it may be more efficient to delete all assignments first and the...

Page 19: ...ter the other When the last luminaire is selected the first luminaire is selected again in the next step The DALI XC beeps once every time a momentary action switch is pressed 1 Use a momentary action switch to select the desired luminaire Luminaire brightens i Note From now on use the momentary action switch to which the desired group is assigned Section Project design describes how to determine ...

Page 20: ...group is assigned to which input Go to Section Project design 4 Hold down momentary action switch approx 3 s 1 beep sounds 5 Release momentary action switch Selected luminaire is assigned to the desired group Figure 9 Assigning a luminaire to a group i Note A luminaire can be assigned to more than one group Tunable White luminaires and normal luminaires can be assigned to the same group 6 Finish s...

Page 21: ...nputs Section Project design describes which group is assigned to the inputs Go to Section Project design 8 1 1 Single momentary action switch control Requirement DALI XC must be in GC A or GC operating mode Switching lighting on and off Briefly press single momentary action switch The group assigned to the momentary action switch is switched on and off in alternating sequence each time the moment...

Page 22: ...colour temperature of the Tunable White luminaires in the group is set to the last saved value Switching off lighting Briefly press double momentary action switch The group assigned to the momentary action switch is switched off Brightening lighting Hold down double momentary action switch The group assigned to the momentary action switch is brightened The colour temperature of the Tunable White l...

Page 23: ...inaires in the assigned group is continually decreased or Briefly press double momentary action switch The colour temperature of the Tunable White luminaires in the assigned group is decreased by one increment Increasing the colour temperature Hold down double momentary action switch The colour temperature of the Tunable White luminaires in the assigned group is continually increased or Briefly pr...

Page 24: ...ode If the DALI XC devices in the lighting system can no longer be accessed the system extension can be started with a DALI XC in GC operating mode 9 1 Starting system extension Starting system extension with DALI XC in Prog operating mode Briefly press momentary action switch 2 beeps sound Programming mode is enabled All luminaires are dimmed to the minimum value All luminaires are brightened one...

Page 25: ...itch 1 beep sounds 3 Hold down momentary action switch approx 1 s 2 beeps sound 4 Release momentary action switch Programming mode is enabled All luminaires are dimmed to the minimum value All luminaires are brightened one after the other All luminaires are then dimmed to the minimum value again 1 beep sounds One luminaire brightens Figure 11 Starting system extension DALI XC in GC operating mode ...

Page 26: ...other When the last luminaire is selected the first luminaire is selected again in the next step The DALI XC beeps once every time a momentary action switch is pressed 6 Use a momentary action switch to select the new luminaire Luminaire brightens i Note From now on use the momentary action switch to which the desired group is assigned Section Project design describes how to determine which group ...

Page 27: ...xtension Testing settings i Note Section Changing intensity describes how to change the intensity Go to Section Changing intensity Section Changing colour temperature describes how to change the colour temperature Go to Section Changing colour temperature Section Recalling scenes describes how to recall scenes Go to Section Recalling scenes Change the intensity if the device is in GC A or GC opera...

Page 28: ...ep sounds after 3 s 1 beep sounds after another 3 s 3 beeps sound after another 4 s 2 Release momentary action switch Programming mode is terminated System is ready again Figure 12 Finishing system extension i Note If no momentary action switches are pressed for 10 minutes in programming mode this mode is automatically terminated ...

Page 29: ... line DA DA Terminals 0 5 1 5 mm solid or fine stranded Degree of protection IP20 Housing material Polycarbonate PC flame retardant halogen free Installation In concealed box 60 x 61 Ø x D in mm Dimensions 47 7 x 28 2 x 14 6 W x H x D in mm Permissible ambient temperature 0 60 C Permissible relative humidity 20 90 non condensing Weight Approx 12 g Table 5 DALI XC technical data ...

Reviews: