smartSWITCH HF 5DP f
INSTALLATION
article number/Artikelnummer: 28002214 / 28002235
01/18-
15011865
-1 We reserve the right to make technical changes without prior notice.
Tridonic GmbH & Co KG, www.tridonic.com, [email protected], Tel. +43 5572 395-0
0,5 – 1,5 mm
2
10 mm
58 64,5 70
4,2
36,5
23,5
24,5
23
Erfassungsbereich
Detection range
Zone de couverture
Raggio d'azione
Área de detección
Detekteringsområde
Диапазон обнаружения
Abstand
Distance
Éloignement
Distanza
Distancia
Avstånd
Расстояние
eindrähtig/feindrähtig
solid/fine-stranded
monobrin/fil fin
a filo unico/a fili sottili
monofilar/hilo fino
entrådig/fintrådig
однопроводной/тонкопроводной
h
d
0,5 m
0,5 m
1,0 m
1,0 m
1,5 m
2,0 m
2,0 m
4,0 m
2,5 m
6,0 m
3,0 m
7,0 m
3,5 m
6,0 m
4,0 m
5,0 m
4,5 m
4,0 m
5,0 m
3,0 m
min. 1,5 m
58
23,5
24,5
23
4,2
36,5
43
48,5
smartSWITCH HF 5DP f (28002214)
smartSWITCH HF 5DP S f (28002235)
L
N
PE
230/240 V AC
50/60 Hz
smartSWITCH
HF 5DP f
smartSWITCH
HF 5DP S f
L’
N
L
N
PE
corridorFUNCTION
Standard
L L’ N
LCA one4all PRE
SEC
PRI
+ LED
– LED
Isel2-2 (GND)
DA/N
DA/L
~
Isel2-1
~
LCA one4all PRE
SEC
PRI
+ LED
– LED
Isel2-2 (GND)
DA/N
DA/L
~
Isel2-1
~
h
d
150°
h
d
150°
Deckenmontage
Ceiling mounted
Montage au plafond
Soffitto monte
Soporte de techo
Takmontering
Монтаж на потолке
Wandmontage
Wall mounted
Montage mural
Montaggio a parete
Montaje en la pared
Väggmontering
Монтаж на стене
Motion detector for installation in luminaires.
Technical Data
Rated supply voltage
220 – 240 V
Mains frequency
50 Hz
Power consumption
< 0.5 W
Frequency
5.8 GHz (� 75 MHz)
Transmission power
< 0.2 mW
Load resistive
800 W
Load capacitive
400 VA
Detection angle
30 – 150°
Max. detection area at 3 m mounting height
ø = 7 m
Max. mountint height
5 m
Dimension L x W x H (28002214)
70 x 36.5 x 24.5 mm
Dimension L x W x H (28002235)
58 x 48.5 x 24.5 mm
tc temperature
85 °C
Ambient temperature ta
-20 ... +70 °C
Storage temperature ts
-20 ... +70 °C
Humidity
min. 5 % ... max. 85 % at 30 °C
Type of protection
IP20
Protection class
Class II
Casing material
PC, halogen free
Casing colour
RAL 9016 (white)
Installation
• Not for use with phase cut dimmers
• The sensor must protrude over the light sources
• The power supply must be disconnected before installation
• Suitable for installation only in indoor luminaires (e.g. corridors and closed
parking garage) without vibrations
• Opening angle of the sensor: must be at least 45 %
• Motion detection: only possible when thin housing material is used (e.g. plastic or
glass), do not use metal housing
• Light sensor: must be able to detect reflected artificial light and reflected daylight
• Reflected HF waves (e.g. of walls, floors, ceilings or furniture) from other
transmitters affect motion detection
Setting up
Setting the detection area
The detection area can be restricted to prevent the lighting system being switched
on unnecessarily, as would be the case if the area were too large. The detection
area indicates the diameter within which motion is detected.
Setting the switch-off delay
To prevent the lighting system being switched on and off unnecessarily you can
set a switch-off delay. The delay starts after the last motion in the
detection area. If a further motion is detected in the detection area during this
delay then the delay is retriggered. At the end of the delay the light will be
switched off or the corridorFUNCTION is started.
Setting the daylight threshold value
A threshold value can be set to prevent the lighting system from being
switched on when there is already adequate illuminance. The threshold value indi-
cates the illuminance value below which detected motion causes the
lighting system to be switched on.
Note:
To ensure the sensor switches on in conjunction with the corridorFUNCTION you
should set the threshold value to I = Disable. If the threshold value disabled the
sensor will always switch on.
corridorFUNCTION
The corridorFUNCTION can be activated by applying a voltage of 230 V for
5 minutes at the switchDIM connection of the control gear or via
corridorFUNCTION Plug.
Note: To apply a voltage of 230 V for 5 minutes at the switchDIM input of
the control gear the sensor must detect motion for more than 5 minutes or a
switch-off delay longer than 5 minutes must be set.
Hereby, Tridonic declares that the radio equipment type SWITCH Sensor HF 5DP
(28002214 and 28002235) is in compliance with Directive 2014/53/EU.
The full text is available at the following internet address:
http://www.tridonic.com/ta601
Safety instructions
• The device may only be used for the applications specified.
• The relevant safety and accident prevention regulations must be observed.
• The power supply must be switched off before handling the device.
• Installation of this device may only be carried out by specialist staff who have
provided proof of their skills.
UK
7
8
9
Daylight sensor
I
●
●
●
Disable (default)
II
○
●
●
50 Lux
III
○
●
○
20 Lux
IV
○
○
●
5 Lux
V
○
○
○
2 Lux
●
○
1
2
3
Sensitivity
I
●
●
●
100 % (default)
II
○
●
●
75 %
III
○
●
○
50 %
IV
○
○
●
30 %
V
○
○
○
10 %
●
○
4
5
6
Hold time
I
●
●
●
5 s (default)
II
●
○
●
30 s
III
●
○
○
1 min
IV
○
●
●
5 min
V
○
●
○
10 min
VI
○
○
●
20 min
VII
○
○
○
30 min
●
○