Data sheet 10/20-EM091-6

Emergency lighting units

EM converterLED

3.4 Loose wiring

Loosen wire through twisting 
and pulling or using a Ø  1 mm 
release tool

3.5 Wiring guidelines

•  The LED terminals, battery, indicator LED and test switch terminals are clas-

sified as SELV (output voltage < 60 V DC). Keep the wiring of the input termi-
nals separated from the wiring of the SELV equivalent terminals or consider 
special wiring (double insulation, 6 mm creepage and clearance) when these 
connections should be kept SELV.

•  The output to the LED is DC but has high frequency content, which should be  

considered for good EMC compliance.

•  LED leads should be separated from the mains and DALI connections and 

wiring for good EMC performance.

•  Maximum lead length on the LED terminals is 3 m. For a good EMC 

performance keep the LED wiring as short as possible.

•  The secondary wires (LED module) should be routed in parallel to ensure 

good EMC performance.

•  Maximum lead length for the Test switch and Indicator LED connection is 1 m. 

The test switch and Indicator LED wiring should be separated from the LED 
leads to prevent noise coupling.

•  Battery leads are specified with 0.5 mm cross section and a length of 0.8 m
•  DALI terminals are mains proof
•  To avoid the damage of the control gear, the wiring must be protected against 

short circuits to earth (sharp edged metal parts, metal cable clips, louver, etc.)

To ensure that a luminaire containing LED emergency units complies with EN 
55015 for radio frequency conducted interference in both normal and emergency 
mode it is essential to follow good practice in the wiring layout.

Within the luminaire the switched and unswitched 50 Hz supply wiring must be 
routed as short as possible and be kept as far away as possible from the LED 
leads.Through wiring may affect the emc performance of the luminaire.

The length of LED leads to the LED module must not be exceeded. Note that 
the length of the EM converterLED leads to the LED module is added to the 
length of the leads from the LED Driver to the EM converterLED module when 
considering the max. permitted lead length of the LED Driver.

3.6 Maximum lead length

LED 

 

3 m (6 m loop)

1

Status indication LED  1 m
Batteries   

0.8 m

1

 Note: The length of LED leads to the LED module must not be exceeded. Note that the length 

of the EM converterLED leads is added to the length of the leads from the LED Driver to the EM 
converterLED module when considering max. permitted lead length of the LED Driver. Leads 
should always be kept as short as possible.

3.7 Use of different phases

The use of different phases for switched line and unswitched line is allowed. 
When using different phases, the unswitched line must fail if the switched 
line fails. This is required to assure correct switching into emergency mode. It 
can be realised with a relay.

4. Mechanical values

4.1 Housing properties

•  Casing manufactured from polycarbonate.
•  Type of protection: IP20
•  Max. torque at the mounting screws: 0.8 Nm

4.2 Mechanical data accessories

 

LED status indicator
• Bi-colour
• Mounting hole 6.5 mm diameter, 1 – 1.6 mm thickness
• Lead length 0.3 m / 1.0 m
• Insulation rating: 90 °C
• Plug connection

Test switch
• Mounting hole 7.0 mm diameter
• Lead length 0.55 m
• Plug connection

Battery connection
•  Plug connection 0.3 m
•  Extension 0.5 m

Summary of Contents for EM converterLED ST 202 MH/LiFePO4 50V

Page 1: ...D module changeover and delayed power switching for the LED Driver Automatic shutdown of output if LED load is out of range Constant power output Addressing function patented EZ easy addressing Two colour status display LED Electronic charge system Deep discharge protection Short circuit proof battery connection Polarity reversal protection for battery provided by 3 pole connector Automatic detect...

Page 2: ...0 pc s 1 600 pc s 0 07 kg Specific technical data Type Battery technology Rated duration Typ λ at 230 V 50 Hz Typ output power P emergency Mains current in charging operation Rated power in charging operation Initial charge Fast recharge Trickle charge2 Initial charge Fast recharge Trickle charge2 EM converterLED PRO 202 MH LiFePO4 50V NiMH 1 h 0 65C 1 5 W 15 mA 16 mA 15 11 mA 1 9 W 2 2 W 1 9 1 4 ...

Page 3: ...ct description Two colour status display LED Green system OK red fault Plug connection Status indication bi colour LED ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc LED EM bi colour 1 0 m CON 89800273 25 pc s 200 pc s 0 015 kg LED EM bi colour high brightness HO 1 0 m CON 89800275 25 pc s 200 pc s 0 015 kg LED EM bi colour 0 6 m CON 89800474 25 pc s 20...

Page 4: ...g connection for LED Driver Connection Cable NiMH ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc CONNECTION CABLE NiMH 500mm 28002462 10 pc s 200 pc s 0 015 kg Product description Extension cable for LiFePO4 batteries Cable length 500 mm 3 pole plug connection Extension Cable LiFePO4 ACCES SORIES Ordering data Type Article number Packaging bag Packaging...

Page 5: ...ssociated battery In normal mains mode all LED modules are operated by the mains LED Driver Meaning of marking Double or reinforced insulation for built in electronic LED Drivers The control gear relies upon the luminaire enclosure for protection against accidental contact with live parts 2 Thermal details and life time 2 1 Life time Average life time 50 000 hours under rated conditions with a fai...

Page 6: ...ED PRO with a standard LED LED Driver and one LED module for mains and emergency operation EM converterLED PRO with a standard LED LED Driver and series operation of LED modules Neutral P O Lout Lin N Dali Dali L L N EM ConverterLED PRO Neutral Dali Dali Un Switched Line Test switch Indicator LED Switched Line out Switched Line in Control gear LED LED Control gear Battery Battery LED Module Emerge...

Page 7: ...itched Line Switched Line out Switched Line in One LED module is operated in emergency mode All LED modules are operated in mains mode 8 9 mm wire preparation 0 5 1 5 mm 3 2 Wiring type and cross section Solid wire with a cross section of 0 5 1 5 mm Strip 8 9 mm of insulation from the cables to ensure perfect operation of terminals Wiring LED module LED Driver supply 3 3 Battery connection LiFePO4...

Page 8: ...nducted interference in both normal and emergency mode it is essential to follow good practice in the wiring layout Within the luminaire the switched and unswitched 50Hz supply wiring must be routed as short as possible and be kept as far away as possible from the LED leads Through wiring may affect the emc performance of the luminaire The length of LED leads to the LED module must not be exceeded...

Page 9: ...M converterLED PRO MH LiFePO4 50V 90 130 130 130 180 260 260 260 10 A 120 μs 5 Electrical values 5 1 Maximum loading of automatic circuit breakers 5 2 Insulation matrix Mains Switched Live Battery LED Test switch Indicator LED DALI Mains Switched Live Battery LED Test switch Indicator LED DALI Represents basic insulation Represents double or reinforced insulation When using a non SELV LED Driver i...

Page 10: ...tery discharge current tolerance EM converterLED PRO 203 MH LiFePO4 50V Article number 89800628 NiMH battery 3 6 V battery voltage 890 960 mA battery discharge current tolerance LiFePO4 battery 3 2 V battery voltage 770 830 mA battery discharge current tolerance LED current mA VLED V VLED V LED current mA EM converterLED PRO 204 MH LiFePO4 50V Article number 89800629 NiMH battery 4 8 V battery vol...

Page 11: ...mand from the control system If the DALI bus is disconnected the EM converterLED PRO does not revert to self testing mode Note If the battery is connected the DALI communication is only possible after power reset Addressing The EM converterLED PRO includes the EZ easy addressing system which allows addressing and identification by using the bi colour LED Binary address codes given by the LED can b...

Page 12: ...nitiate a 5 seconds function test press 200 ms T 1 s Execute function test as long as switch pressed press 1 s Reset selftest timer adjust local timing press 10 s Rest Mode Inhibit Mode Emergency operation is automatically started when the mains supply is switched off If the Rest Mode is activated the discharging of the battery will be minimized by switching off the LED output If the Inhibit Mode ...

Page 13: ...B CON 28002319 side by side 4 x 1 Accu LiFePO44B CON 28002323 side by side 5 x 1 Accu LiFePO45B CON 28002326 EM converterLED PRO 1 2 3 h NiMH Type EM converterLED PRO 202 MH LiFePO4 50V EM converterLED PRO 203 MH LiFePO4 50V EM converterLED PRO 204 MH LiFePO4 50V Article no 89800627 89800628 89800629 Duration 1 h 2 3 h 1 h 2 3 h 1 h 2 3 h Battery charge time Initial charge 20 h Fast recharge 10 h ...

Page 14: ...n life 5 C to 55 C 6 years design life 5 C to 45 C 8 years design life 5 C to 35 C Max short term temperature reduced life time 70 C Max number discharge cycles 50 cycles total Max storage time 12 months at 5 C to 25 C Only use Tridonic batteries Comply with UN 38 3 and IEC 62133 safety testing protected against over charge over discharge charging at excessive temperatures short circuit and over c...

Page 15: ...arameters provide information about the mains battery LED output and emergency operation The BlackBox can be read out with the masterCONFIGURATOR and deviceANALYSER In order to allow a safe detection of a battery replacement through the Black Box data recording follow the below described process Battery replacement 1 Disconnect mains 2 Disconnect battery 3 Reconnect and disconnect mains while no b...