Tridonic 89800578 Manual Download Page 8

www.tridonic.com

8

Subject to change without notice. Information provided without guarantee.

Data sheet 07/20-EM079-10

Emergency lighting units

EM converterLED

4. Mechanical values

4.1 Housing properties

•  Casing manufactured from polycarbonate.
•  Type of protection: IP20
•  Max. torque at the mounting screws: 0.8 Nm

4.2 Mechanical data accessories

 

LED status indicator
•  Green
•  Mounting hole 6.5 mm diameter, 1 – 1.6 mm thickness
•  Lead length 0.3 m / 0.6 m / 1.0 m
•  Insulation rating: 90 °C
•  Plug connection

Test switch
•  Mounting hole 7.0 mm diameter
•  Lead length 0.55 m
•  Plug connection

Battery connection
•  Plug connection 0.3 m
•  Extension 0.5 m

3.6 Maximum lead length

LED 

 

3 m (6 m loop)

1

Status indication LED  1 m
Batteries   

0.8 m

3.7 Use of different phases

The use of different phases for switched line and unswitched line is allowed. 
When using different phases, the unswitched line must fail if the switched 
line fails. This is required to assure correct switching into emergency mode. It 
can be realised with a relay.

3.4 Loose wiring

Loosen wire through twisting 
and pulling or using a Ø  1 mm 
release tool

3.5 Wiring guidelines

•  The LED terminals, battery, indicator LED and test switch terminals are clas-

sified as SELV (output voltage < 120 V DC). Keep the wiring of the input ter-
minals separated from the wiring of the SELV classified terminals or consider 
special wiring (double insulation, 6 mm creepage and clearance) when these 
connections should be kept SELV.

•  The output to the LED is DC but has high frequency content, which should be  

considered for good EMC compliance.

•  LED leads should be separated from the mains connections and wiring for 

good EMC performance.

•  Maximum lead length on the LED terminals is 3 m. For a good EMC 

performance keep the LED wiring as short as possible.

•  The secondary wires (LED module) should be routed in parallel to ensure 

good EMC performance.

•  Maximum lead length for the Test switch and Indicator LED connection is 1 m. 

The test switch and Indicator LED wiring should be separated from the LED 
leads to prevent noise coupling.

•  Battery leads are specified with 0.5 mm cross section and a length of 0.8 m
•  To avoid the damage of the control gear, the wiring must be protected against 

short circuits to earth (sharp edged metal parts, metal cable clips, louver, etc.)

To ensure that a luminaire containing LED emergency units complies with  
EN 55015 for radio frequency conducted interference in both normal and emer-
gency mode it is essential to follow good practice in the wiring layout.

Within the luminaire the switched and unswitched 50 Hz supply wiring must be 
routed as short as possible and be kept as far away as possible from the LED 
leads.Through wiring may affect the EMC performance of the luminaire.

The length of LED leads must not be exceeded. Note that the length of the 
leads from the EM converterLED to the LED modules is added to the length of 
the leads from the LED Driver to the EM converterLED module when conside-
ring the max. permitted lead length of the LED Driver. Leads should always be 
kept short as possible.

1

 Note: The length of LED leads to the LED module must not be exceeded. Note that the length 

of the EM converterLED leads is added to the length of the leads from the LED Driver to the EM 
converterLED module when considering max. permitted lead length of the LED Driver. Leads 
should always be kept as short as possible.

Summary of Contents for 89800578

Page 1: ...ole technology 2 pole LED module changeover and delayed power switching for the LED Driver Automatic shutdown of output if LED load is out of range Constant power output Maximum light output for all LED modules Electronic charge system Deep discharge protection Short circuit proof battery connection Polarity reversal protection for battery provided by 3 pole connector Automatic detection of the co...

Page 2: ...tent charge is used Value 1 is for 4 min charge on Value 2 is for 16 min charge off In case of LiFePO4 batteries voltage dependent constant current charging is used EL Technical data Rated supply voltage 220 240 V AC voltage range 198 264 V Mains frequency 50 60 Hz LED module forward voltage range 40 97 V Output current see chapter 5 3 Time to light 0 5 s from detection of emergency event Overvolt...

Page 3: ... 89800269 25 pc s 200 pc s 0 015 kg LED EM green HO 1 0 m CON 89800271 25 pc s 200 pc s 0 015 kg LED EM green 0 6 m CON 89800472 25 pc s 200 pc s 0 009 kg LED EM green HO 0 6 m CON 89800473 25 pc s 200 pc s 0 009 kg LED EM green 0 3 m CON 89800270 25 pc s 200 pc s 0 005 kg LED EM green HO 0 3 m CON 89800272 25 pc s 200 pc s 0 005 kg Product description For connection to the emergency lighting unit...

Page 4: ...ug connection for LED Driver Connection Cable NiMH ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc CONNECTION CABLE NiMH 500mm 28002462 10 pc s 200 pc s 0 015 kg Product description Extension cable for LiFePO4 batteries Cable length 500 mm 3 pole plug connection Extension Cable LiFePO4 ACCES SORIES Ordering data Type Article number Packaging bag Packagin...

Page 5: ...urs Expected life time with NiMH batteries EM converterLED BASIC 203 MH LiFePO4 90V tc 65 C 70 C 75 C life time 100 000 h 100 000 h 82 000 h EM converterLED BASIC 204 MH LiFePO4 90V tc 65 C 70 C 75 C life time 100 000 h 100 000 h 82 000 h Expected life time with LiFePO4 batteries EM converterLED BASIC 203 MH LiFePO4 90V tc 65 C 70 C 75 C life time 100 000 h 100 000 h 89 000 h EM converterLED BASIC...

Page 6: ...M converterLED BASIC with one LED module for non maintained emergency operation P O Lout Lin N L EM converterLED BASIC Neutral Un Switched Line Test switch Indicator LED Not connected Not connected Control gear LED LED Control gear Battery Battery LED Module Emergency EM converterLED BASIC with a standard LED Driver and series operation of LED modules One LED module is operated in emergency mode A...

Page 7: ...M converterLED BASIC Battery Battery One LED module is operated in emergency mode All LED modules are operated in mains mode 8 9 mm wire preparation 0 5 1 5 mm 3 2 Wiring type and cross section Solid wire with a cross section of 0 5 1 5 mm Strip 8 9 mm of insulation from the cables to ensure perfect operation of terminals Wiring LED module LED Driver supply 3 3 Battery connection LiFePO4 Direct co...

Page 8: ...ated from the mains connections and wiring for good EMC performance Maximum lead length on the LED terminals is 3 m For a good EMC performance keep the LED wiring as short as possible The secondary wires LED module should be routed in parallel to ensure good EMC performance Maximum lead length for the Test switch and Indicator LED connection is 1 m The test switch and Indicator LED wiring should b...

Page 9: ...ak EM converterLED BASIC 203 MH LiFePO4 90V Article number 89800578 NiMH battery 3 6 V battery voltage 840 900 mA battery discharge current tolerance LiFePO4 battery 3 2 V battery voltage 955 1025 mA battery discharge current tolerance VLED V LED current mA EM converterLED BASIC 204 MH LiFePO4 90V Article number 89800579 NiMH battery 4 8 V battery voltage 830 890 mA battery discharge current toler...

Page 10: ...llowed output voltage of the associated LED Driver applied to the EM converterLED output is 450V voltage withstand between adja cent contact of the single switching relay of the EM converterLED The max allowed LED load of the associated LED Driver is 150 W in operation The load must be an LED module Check compatibility with short function tests duration of several seconds 6 Functions 6 1 Duration ...

Page 11: ...ttery will be charged below 0 9 V The EM converterLED will indicate a battery fault The emergency lighting LED Driver will recharge the battery normally after running the test of 61347 2 7 CL 22 3 abnormal operating conditions 7 2 Battery charge discharge data EM converterLED BASIC 1 3 h Type EM converterLED BASIC 203 MH LiFePO4 90V EM converterLED BASIC 204 MH LiFePO4 90V Article no 89800578 8980...

Page 12: ...30 470 mA Fast recharge 250 290 mA 430 470 mA 250 290 mA 430 470 mA Trickle charge1 250 290 mA 0 mA 430 470 mA 0 mA 250 290 mA 0 mA 430 470 mA 0 mA Discharge current 955 1 025 mA 955 1 025 mA 1 350 1 450 mA 1 350 1 450 mA Charge voltage range2 2 0 3 65 V Discharge voltage range 3 65 2 60 V 1 Automatic recharge when battery voltage falls below 3 4 V Charger off 0 mA when battery voltage exceeds 3 6...

Page 13: ...cycles of the associated LED driver 8 2 Battery replacement After a battery replacement and a subsequent full charge cycle 24 h a duration test is mandatory to prove that with the new battery the rated duration is achieved 8 3 Additional information Additional technical information at www tridonic com Technical Data Guarantee conditions at www tridonic com Services Life time declarations are infor...

Reviews: