Data sheet 07/20-EM079-10
Emergency lighting units
EM converterLED
7.7 Storage, installation and commissioning
Relevant information about storage conditions, installation and commissioning
are provided in the battery datasheets.
7.6 Wiring batteries
To inhibit inverter operation disconnect the batteries by removing the
connection at battery side.
For further informations refer to corresponding battery datasheet.
7.3 Accu-NiMH
Capacity 4.0 Ah
International designation
HRMU 19/90
Battery voltage/cell
1.2 V
Cell type
LA
Case temperature range
to ensure 4 years design life
+5 °C to +50 °C
Max. short term temperature (reduced life-time)
70 °C
Max. number discharge cycles
4 cycles per year plus
30 cycles during
comissioning
Max. storage time
12 months
at +5 °C to +25 °C
7.4 Accu-LiFePO4
Capacity 1.5 Ah
International designation
lFpR 19/66
Battery voltage/cell
3.2 V
Cell type
18650
Case temperature range to ensure
4 years design life
+55 °C
6 years design life
+45 °C
8 years design life
+35 °C
Max. short term temperature (reduced life-time)
70 °C
Max. number discharge cycles
50 cycles total
Max. storage time
12 months
at +5 °C to +25 °C
Only use Tridonic batteries.
Comply with UN 38.3 and IEC 62133 (safety testing) protected against over
charge, over discharge, charging at excessive temperatures, short-circuit and
over current.
EM converterLED BASIC, 1 / 3 h, LiFePO
4
Type
EM converterLED BASIC
203 MH/LiFePO4 90V
EM converterLED BASIC
204 MH/LiFePO4 90V
Article no.
89800578
89800579
Duration
1 h
3 h
1 h
3 h
Battery charge
time
Initial charge
24 h
Fast recharge
24 h
Trickle charge
continuously and battery voltage controlled
Charging current
Initial charge
250 – 290 mA
430 – 470 mA
250 – 290 mA
430 – 470 mA
Fast recharge
250 – 290 mA
430 – 470 mA
250 – 290 mA
430 – 470 mA
Trickle charge
1
250 – 290 mA / 0 mA
430 – 470 mA / 0 mA
250 – 290 mA / 0 mA
430 – 470 mA / 0 mA
Discharge current
955 – 1,025 mA
955 – 1,025 mA
1.350 – 1,450 mA
1,350 – 1,450 mA
Charge voltage range
2
2.0 – 3.65 V
Discharge voltage range
3.65 – 2.60 V
1
Automatic recharge when battery voltage falls below 3.4 V. Charger off (0 mA) when battery voltage exceeds 3.6 V.
Note: Battery protected against operation at excessive temperatures (charging stopped when battery cell temperature < -5 °C or > 60 °C).
The emergency lighting LED Driver will recharge the battery normally after running the test of 61347-2-7 CL 22.3 (abnormal operating conditions).
2
The battery will not be charged below 2.0 V.
7.5 Safety
7.5.1 Deep discharge protection
When the battery remains connected without charging for a long period of time
after the battery cut off of the driver the battery voltage can still drop. To make
sure the cells are not damaged by this voltage drop, the battery protection
prevents the battery from further discharge below 2.0 V.
7.5.2 Overcharge protection
If in case of an error or the use of a wrong driver the battery gets overcharged
the battery protection will disconnect the battery from the driver at a voltage of
3.9 V. A discharge of the battery is still possible after the protection circuit was
triggered to guarantee emergency operation.
7.5.3 Short-circuit protection
In case of a short circuit the battery protection opens the connection to the
driver and the output is therefore free of voltage. The output will be reactivated
again when the short circuit is removed.
7.5.4 Overtemperature protection
The battery is protected against temporary thermal overheating. If the tempera-
ture limit is exceeded the further charging of the battery is no longer possible.
The temperature protection is activated below approx. 0 °C and above approx.
+60 °C. The discharging of the battery is still possible to guarantee emergency
operation.