VMS-1655M
LIT-12013297
14
Configuring display module settings
BACnet objects
The following table itemizes the list of points available for integration in a building management system (BMS). This table
contains the objects for open BACnet integration.
*
Can only be set if you enable the option at the VMS-1655M User Interface.
Module settings
Options dipswitch (S1): internal use only
1. Graphics Chip Mode Selection
OFF = Programming Mode
ON = Run Mode
2. Touchscreen Calibration Mode
OFF = Force calibration
ON = Auto calibration
3. Reserved
4. Reserved
Options dipswitch (S2): mode configuration 1
1. Product Type
OFF = VMS-1655M
ON = Invalid
2. Reserved
3. Mode Select
OFF = Invalid
ON = VMS-1655M
4. Operational Mode
OFF = Demo Mode
ON = Run Mode
Push button Switch (SW1):
Reset Button
Push button Switch (SW2):
Reserved
Object instance
Functional description
Read or Write
Analog inputs
AI - 1
Analog Input 1 (Fume Hood Face Velocity)
Read-only
AI - 2
Analog Input 2 (Exhaust Air Flow)
Read-only
Analog outputs
AO - 1
Analog Outputs (Actuator Position %)
Read-only
Object instance
Functional description
Read or Write
Analog inputs
AV - 1
Face Velocity Low Alarm Setpoint
Read/Write
AV - 2
Face Velocity Low Warning Setpoint
Read/Write
AV - 3
Face Velocity High Warning Setpoint
Read/Write
AV - 4
Face Velocity High Alarm Setpoint
Read/Write
AV - 5
Face Velocity Deadband percentage
Read/Write
Multistate objects
MSO - 1
Operating Mode: 1 = occupied, 2 unoccupied*, 3 = decom
Read/Write
MSO - 2
Alarm Status: 1 = normal, 2 = warning, 3 = alarm
Read-only