After the FMS-1650L unit has been installed,
apply power to the unit. On power up, you
will hear two short beeps that indicate the
FMS-1650L display module is communicating
with the main controller module, and has
begun the initialization sequence. The LED
backlighting will cycle through the three unit
status colors (green, yellow, red) as part of
the power-up initialization sequence, followed
by the displaying of the Triatek splash screen
indicating serial number, Neuron ID, firmware
version numbers, and network address
(Figure 1).
This splash screen remains displayed for
approximately 5 seconds and then disappears
to reveal the main display screen. This splash
screen information can also be redisplayed
using the
About This FMS
option on the
Diagnostics
menu.
Figure 1. This splash screen is displayed
briefly following a power up or system reset.
Main Display Screen
All FMS-1650L units come shipped from the
factory in the
Neutral
isolation mode, which is
represented by white text being displayed on
a blue background. Information displayed on
the main screen includes the following (see
Figure 2):
•
Name of monitored isolation room (up to
20 chars)
•
Current room status (occupied,
unoccupied)
•
Current temperature (if temperature
sensor has been installed)
•
Current relative humidity (if humidity
sensor has been installed)
•
Current differential pressure reading in
selected engineering units (default is “WC)
•
Current time and date
Figure 2. The main screen of the FMS-1650L
displays the differential pressure, room status,
temperature and humidity (if so equipped),
along with the time and date along the bottom
of the screen.
As mentioned earlier, the background color of
the main display screen will be blue while set
to
Neutral
isolation mode. However, while in
either
Positive
or
Negative
isolation modes,
the background colors actively represent
that current alarm status of the monitor. A
green background indicates that the current
differential pressure is within allowable limits
of the desired setpoint, as shown in the case
represented by Figure 2. A yellow background
as shown in Figure 3 indicates that the current
differential pressure has drifted outside of the
allowable limits of the desired setpoint, and
is in the caution range. A red background
indicates that the current differential pressure
has reached a critical condition and is
significantly outside of the allowable limits of
the desired setpoint.
Figure 3. When the differential pressure drifts
outside the normal operating range, the main
display background turns yellow to indicate a
warning condition.
FMS-1650L Programming
Basic Programming
FMS-1650L
Due to continuous improvement, TRIATEK reserves the right to change product specifications without notice.
-
30
-
Due to continuous improvement, TRIATEK reserves the right to change product specifications without notice.
Due to continuous improvement, TRIATEK reserves the right to change product specifications without notice.
TRIATEK reserves the right to change product specifications without notice.
TRIATEK reserves the right to change product specifications without notice.