Mounting / Wiring
Function Descriptions
FMS-1650L
-
11
-
TRIATEK reserves the right to change product specifications without notice.
Function
Description
AUX Power Output
Power supply outputs used for power auxiliary devices. Each is supply limited to 100
ma.
LON Communications
LON FTT-10A Free Topology Network building automation system can access the sta-
tus and the configuration of the unit. Also used by configuration software to configure
unit.
Analog Output
Unit has 4 Analog Outputs which can be configured for 0-5 VDC or 0-10VDC.
Analog Input
Unit has 4 Analog Inputs which can be configured for 4-20 mA, 0-5VDC, or 0-10VDC.
Power
The FMS-1650L Series can be powered by either 24 VAC or 24 VDC. A 120 VAC to
24 VAC Step Down Isolation Transformer is provided and recommended. This power
must be from a Class 2 supply only.
Digital Input
The unit has 4 Digital Inputs with selectable pull-up voltages of 0V, +5V and +18V.
Relay Output
The unit has 4 SPDT Relay outputs with normally open contacts.