4. If  the  combustion  level  during  Low  fire  is  not

/-0.2% of the combustion level measured
at High fire, adjust the  OFFSET SCREW below
the cap on the gas valve (see Fig. 4) as follows.

Counter-clockwise  adjustment  of  OFFSET
SCREW at low fire:

O2 increases and CO2 decreases

Clockwise  adjustment    of  OFFSET  SCREW at
low fire:

O2 decreases and CO2 increases

5. Press the “+” and “-” buttons simultaneously to

shutdown the burner.

Trimax Instructions

1. Press the round INSTALLER button. See Fig. 5.

2.  Enter  the  installer  access  code  “054”  by  using

the 

LEFT

and 

RIGHT

buttons to select a digit

and the 

UP

and 

DOWN

buttons to change the

digit.  Press the 

OK

button to enter the access

code.

3. Press  the 

RIGHT

button  to  highlight  the

Manual  Operation  icon

then  press  the 

OK

button.

4.  Press  the 

OK

button  while  the  FAN  icon  is

highlighted  to  manually  fire  the  burner  and
power the CH circulator.

An adequate CH load must be present to dis-
sipate the heat generated during the combus-
tion test.  If an adequate CH load is not avail-
able, an indirect water heater can be used to
dissipate  the  heat  by  creating  a  DHW  call
which will enable the DHW circulator.

 

   

 

 

   

 

 

   

 

 

   

 

 

  

 

 

  

 

 

  

 

 

  

  

 

 

NOTICE

4

1

2

2

3

1

5

Fig. 4: Venturi Gas Valve Assembly

1.  Brown (MCBA) Black (TriMax) wire
2. Blue (MCBA) White (TriMax)wire
3. Throttle screw
4. Offset screw
5. Inlet Pressure Tap

Installer
Button

Fig. 5: Trimax Navigation Buttons

Manual Operation

Released

Off

Off

Off

CH

CH1

FAN

DHW

SYS

CH2