TriangleTube PSRKIT84 Manual Download Page 3

Venturi Replacement Kit 

for PRESTIGE 399

3

Do  not  check  for  gas  leaks  with  an  open
flame. Use a bubble test. Failure to check for
gas  leaks  can  cause  severe  personal  injury,
death or substantial property damage

12. Reconnect the wires to the gas valve as shown

in Fig.4.

13. Reattach the air inlet elbow to the venturi.

14. Reposition the Control Module panel and reat-

tach the front jacket panel.

15.  Turn  power  supply  to  the  Prestige  “ON”  and

return the unit to service.

COMBUSTION TEST/ADJUSTMENT

The  installer  MUST  perform  a  complete  combus-
tion check to ensure the following combustion lev-
els are met at high and low input firing rates and the
burner is operating at optimum conditions.

The  combustion  testing  and  adjustments
must  be  performed  by  a  qualified  installer,
service  agency  or  the  gas  supplier. All  com-
bustion measurements must be perform with
calibrated equipment to ensure proper read-
ings and accuracy.

Failure  to  perform  a  complete  combustion
test  at  both  high  and  low  input  rates  may
result in incomplete combustion and the pro-
duction  of  carbon  monoxide,  which  can
cause  severe  personal  injury,  death  or  sub-
stantial property damage.

MCBA Instructions

1. Manually  place  the  boiler  into  High  fire  mode

by pressing the MODE button with  “+”  button
simultaneously  on  the  control  panel  display
while in the standby (STBY) mode.

The control panel will display an H followed
by  the  current  boiler  temperature  when
placed into High fire test mode.

2. If  the  combustion  levels  during  High  fire  are

outside  the  recommended  combustion  settings
adjust the THROTTLE SCREW (see Fig. 4) as
follows:

Counter-clockwise  adjustment  of  the  THROT-
TLE SCREW at high fire:

O2 decreases and C02 increases

Clockwise  adjustment  of  the  THROTTLE
SCREW at high fire:

O2 increases and CO2 decreases

Table 1: Recommended Combustion Levels

3. Once  the  combustion  level  is  set  at  High  fire,

manually place the boiler into Low fire mode by
pressing  the  MODE  button  with  “-”  button
simultaneously  on  the  control  display  while  in
the standby (STBY) mode.

The  control  panel  will  display  a  L  followed
by  the  current  boiler  temperature  when
placed into low fire test mode.

WARNING

WARNING

NOTICE

WARNING

NOTICE

Natural Gas

Propane

O2 Min.

2.30%

3.70%

O2 Max.

5.30%

5.20%

CO2 Min.

8.80%

10.00%

CO2 Max.

10.50%

11.00%

CO Max.

100 ppm

100 ppm