background image

PRESTIGE Venturi

Replacement Kit 

Instructions

1.  Turn power to the unit “OFF”.

2.  Remove the front jacket panel. Swing away the

Control Module panel (MCBA) or tilt down the
Control Module panel (TriMax).

3.  Shut off gas supply to the Prestige boiler at the

main manual shutoff valve.

4.  Disconnect  the  gas  piping  at  the  brass  union

located  near  the  gas  valve  inside  the  boiler
enclosure.

5.  Using a Phillips screwdriver disconnect the rec-

tifier cable to the gas valve (MCBA).

6. Remove Molex plug from gas valve (TriMax).

7.  Remove the air inlet elbow from the venturi.

Note the orientation of the venturi / gas valve
assembly  and  the  venturi  gasket  in  relation
to  the  blower  housing  when  disassembling
the venturi / gas valve assembly.

8.  Using the #25 Torx wrench from the kit remove

the  2  venturi  mounting  screws  attaching  the
venturi / gas valve assembly to the blower, see
Fig. 2.  Remove the venturi / gas valve assem-
bly from the blower.

There is a gasket between the venturi and the
blower housing.  If the gasket “sticks” to the
blower housing use a flat blade putty knife to
remove any gasket material.  Make sure not
to scratch or score the mating surface on the
blower housing.

9.  Remove the three screws attaching the gas valve

to  the  venturi  as  shown  in  Fig.  3.    Use  Torx
wrench  supplied  in  kit  to  remove  screws.    Note
orientation of the venturi to the old gas valve for
reassembly of the new venturi on the gas valve.

10. Reassemble the gas valve, using the existing three

Torx screws to the venturi. See Fig. 3.

Ensure the gas valve/orifice gasket is in place
before reassembling the gas valve and venturi.
Failure  to  do  so  can  result  in  death,  serious
injury or substantial property damage.

For  propane  installations  a  brass  orifice  is
located  inside  the  gas  valve/orifice  gasket.
This orifice must be placed inside of the new
gas valve/orifice gasket before reassembly.

Failure to insert the propane brass orifice, on
propane  installations,  before  reassembling
the  gas  valve  and  venturi  can  result  in  the
production  of  carbon  monoxide  due  to
incomplete  combustion  and  may  result  in
death, serious injury or substantial property
damage.

NOTICE

NOTICE

WARNING

NOTICE

WARNING

2

Venturi/Gas

 Valve Assembly

Venturi

Mounting Screw

Venturi

Mounting Screw

Fig. 2: Venturi/Gas Valve Assembly