Prestige SOLO 399 Boiler

Natural to Propane Instructions

5

2.   If the combustion levels during high fire is outside

the recommended combustion settings in Table 2,
adjust  the  THROTTLE  SCREW  (see  Fig.  3)
using a flat-blade screwdriver.

The throttle screw is highly sensitive and requires
the use of a combustion analyzer for adjustment.
An adjustment as small as an 1/8 of a turn can pro-
duce a large change in combustion levels.

3.   Once the combustion level is set at high fire, man-

ually place the boiler into low fire mode by press-
ing  the  “MODE”  button  with  “-”  button
simultaneously on the control display while in the
Standby (STBY) mode.

The control panel will display a L followed by the
current boiler temperature when placed into low
fire test mode.

4.   If the combustion levels (O2 or CO2) during low

fire is not /- 0.2 of the combustion level
measured  at  high  fire,  remove  the  offset  cover
screw  and  adjust  the  plastic  OFFSET  SCREW
(see Fig 3) using a T-40 Torx wrench as follows:

Counter-clockwise  adjustment  of  the  OFFSET
SCREW at Low Fire:

      O2 increases and CO2 decreases

Clockwise adjustment of the OFFSET SCREW at
Low Fire:

      O2 decreases and CO2 increases

5.   Press the “+” and “-” buttons simultaneously to

shutdown the burner.

Trimax Control Procedure (TRIMAX)

1.   Press the round INSTALLER button. See Fig. 4.

2.  Enter the installer access code “054” by using the

LEFT

and 

RIGHT

buttons to select a digit and

the 

UP

and 

DOWN

buttons to change the digit.

Press the 

OK

button to enter the access code.

3. Press the 

RIGHT

button to highlight the Manual

Operation icon

then press the 

OK

button.

4.   Press the OK button while the FAN icon is high-

lighted to manually fire the burner and power the
CH circulator.

An adequate CH load must be present to dissipate
the heat generated during the combustion test.  If
an adequate CH load is not available, an indirect
water heater can be used to dissipate the heat by

WARNING

 

   

 

 

   

 

 

   

 

 

   

 

 

  

 

 

  

 

 

  

 

 

  

  

 

 

WARNING

NOTICE

Installer
Button

Fig. 4: Trimax Navigation Buttons

Manual Operation

Released

Off

Off

Off

CH

CH1

FAN

DHW

SYS

CH2