background image

Prestige SOLO 399 Boiler

Natural to Propane Instructions

3

13. Install the brass natural gas orifice and o-ring gas-

kets between the gas valve extension pipe and the
venturi.  Ensure that the orifice and gaskets are in-
side the retaining ring cast into the venturi.

Taper on gas orifice should face the gas valve ex-
tension pipe. See Figs. 1 & 2.

Table 1: Propane Gas Orifice

Failure to retain the O-ring gaskets between venturi
and gas valve extension pipe will cause an improper
seal resulting in a potential risk of a gas leak.  Any
potential gas leakage may result in death, serious
injury or substantial property damage.

14. Reassemble the gas valve extension pipe onto the

venturi using the four T-25 Torx head screws.  En-
sure that the gas valve extension pipe is properly
oriented with the venturi.

There  is  a  gasket  between  the  venturi  and  the
blower housing.  This gasket must be reinstalled.
Use care not to damage the gasket.

15. With  the  venturi  /  blower  O-ring  in  place,  re-

assemble the venturi / gas valve assembly to the
blower housing using the six T-40 Torx screws.

For the reassembly process do not use adhesive on
the venturi / blower gasket.

Use  care  in  the  reassembly  of  the  venturi  /  gas
valve to the blower housing not to cross thread the
mounting screws.  Support the weight of the ven-
turi  /  gas  valve  assembly  when  threading  the
mounting screws.

16. Reconnect the wiring to the gas valve as shown

in Fig. 3.

17.  Reconnect  and  tighten  the  internal  gas  supply

union  using two wrenches and open the external
manual gas shut off valve.  Before placing the
Prestige boiler back into operation check and test
all  gas  connections  for  leaks.    Repair  leaks  if
found.

Do not check for gas leaks with an open flame.
Use a bubble test.  Failure to check for gas leaks
can cause severe personal injury, death or substan-
tial property damage.

NOTICE

NOTICE

WARNING

WARNING

NOTICE

WARNING

Model

Orifice Size

Solo 399

0.339” (8.6 mm)

Throttle 

Screw 

Brown Wire 

Offset Cover Screw

Brown Wire 

Ground “Open” 

Blue Wire 

Blue Wire 

Fig. 3: Prestige 399 Gas Valve 