27
Parameter
Description
Factory
Setting
Minimum
Setting
Maximum
Setting
Adjusted
Setting
11
Boost feature set point. Use to compensate the
calculated operating temperature.
00
00
30
See pages 22 through 24 for additional information
minutes
minutes
minutes
12
Parallel shift setting. When using the optional
outdoor sensor this setting is a setback feature.
00ºF
00ºF
144ºF
See page 24 for additional information
13
Do Not Adjust this Parameter
53
14
Do Not Adjust this Parameter
00
15
Do Not Adjust this Parameter
53
16
Do Not Adjust this Parameter
00
17
Do Not Adjust this Parameter
19
18
Do Not Adjust this Parameter
00
19
Do Not Adjust this Parameter
36
20
Post pump feature setting for the CH circulator
supplied with the boiler.
01
00
99
See page 24 for additional information
minutes
10 seconds
minutes
21
The DHW circulator post pump time period applied
after the completion of a DHW request. Parameter
setting is multiplied by 10.2 seconds.
03
x 10.2 sec.
00
x 10.2 sec.
30
x 10.2 sec.
See page 11 for additional information
22
Do Not Adjust this Parameter
6
23
Do Not Adjust this Parameter
6
24
Do Not Adjust this Parameter
6
25
Do Not Adjust this Parameter
10