TriangleTube INSRKIT100 Manual Download Page 3

Instinct

Condensate Pan Replacement

3

Air Inlet Elbow

Blower

Gas Valve

Igniter

2 in 1 Insulation

Venturi 

Inlet Pipe

Burner

Fig. 2:  Instinct 155 Burner Assembly

Air Inlet 

Elbow

Blower

Gas Valve

Igniter

2 in 1 Insulation

Venturi 

Inlet Pipe

Burner

Fig. 3:  Instinct 199 Burner Assembly

6.  Remove the two screws on securing the gas valve 

bracket to the heat exchanger mounting plate. Do 

not discard these screws as they will be reused. Re-

move the gas valve and bracket from the boiler.  

WARNING

!

Inspect the gas valve to ensure they are not damaged. 
Contact Triangle Tube right away if damaged in any 
way. 

Fig. 4:  Blower Bolt Holes

7.  The two hard to reach bolt holes under the blower 

housing are slotted, see Fig. 4. Fully remove the two 

other 8mm bolts securing the blower to the burner 

mounting plate. Unscrew the other two bolts only 

as much as is needed to remove the blower/venturi 

assembly.  

8.  Slide the blower/Venturi forward to disengage the 

rear bolts and remove the blower/venturi from the 

boiler. Do NOT discard the blower gaskets. Do NOT 

discard the bolts as they will be reused. 

WARNING

!

Inspect the blower and venturi to ensure they are not 
damaged. Contact Triangle Tube right away if either is 
damaged in any way. 

9.  Remove the two Phillips head screws securing the 

burning mounting plate to the rear jacket panel. 

These screws are for shipping protection and can 

be discarded. 

10. Remove the 10 mm burner plate mounting nuts 

mounting the plate to the heat exchanger. Do not 

discard the nuts as they will be reused. 

11. Lift the combustion chamber insulation and burn-

er mounting plate together. Remove the insula-

tion/burner straight up from the heat exchanger 

body to ensure the igniter and burner head are not 

damaged.

Summary of Contents for INSRKIT100

Page 1: ...or death WARNING Failure to follow instructions below can result in severe personal injury or damage if ignored Instructions are for a qualified installer ser vice technician only Read all instruction...

Page 2: ...ining of the boiler remove the air vent at the top of the unit or manually lift open the pressure relief valve WARNING Water from the boiler drain connection may be ex tremely hot To avoid personal in...

Page 3: ...wer to the burner mounting plate Unscrew the other two bolts only as much as is needed to remove the blower venturi assembly 8 Slide the blower Venturi forward to disengage the rear bolts and remove t...

Page 4: ...Instinct Condensate Pan Replacement 4 Fig 5 Instinct 110 Fig 6 Instinct 155 Solo Fig 7 Instinct 199 Solo Fig 8 Instinct 155 Combi...

Page 5: ...card the seals as they will be reused 5 Removal of Flue Tube 1 Disconnect the molex plug connected to the flue temperature sensor in the flue tube 2 Remove the flue temperature sensor by pulling it st...

Page 6: ...9 Install New Condensate Pan 1 Seat the new flue tube gasket in the flue tube seat 2 Seat the new condensate pan gasket in the recess as shown in Fig 12 with the side with less ribs fac ing upward 3 I...

Page 7: ...ain nipple See Fig 10 2 Push the condensate trap onto the condensate nipple as far as it will go 3 Tighten the retaining nut to the condensate trap to secure the condensate trap 4 Pull the condensate...

Page 8: ...of the unit at the main manual shutoff valve to the unit Check and test all gas connections for leaks Repair leaks if found WARNING Do not check for gas leaks with an open flame Use a bubble test Fai...

Page 9: ...dequate CH load must be present to dissipate the heat generated during the combustion test If an adequate CH load is not available an indirect water heater can be used to dissipate the heat by creatin...

Reviews: