background image

CHALLENGER

Natural Gas to Propane Instructions

4

Table 2:  Recommended Combustion Levels

Failure  to  perform  a  complete  combustion  test  at  both
high and low input rates may result in incomplete combus-
tion  and  the  production  of  carbon  monoxide,  which  can
cause severe personal injury, death or substantial property
damage.

2.    Manually place the appliance into high fire mode by

pressing both the service button “

”  with “+” but-

ton simultaneously on the control panel display two
times.

The control panel will display a H followed by the current
appliance  temperature  when  placed  into  high  fire  test
mode.

The THROTTLE SCREW on the CHALLENGER’s gas valve
works opposite than the PRESTIGE. If you turn the
CHALLENGER’s throttle screw clockwise you increase the
input, CO2 and CO of the appliance. EXERCISE CARE!

3.    If the combustion levels during high fire are outside

the  recommended  combustion  settings  adjust  the
THROTTLE  SCREW  (see  Figs.  3  &  4  on  page  5)
using a T15 Torx wrench as follows:

      Counter-clockwise  adjustment  of  the  THROTTLE

SCREW at High Fire:

      
      

O2 increases and CO2 decreases

Clockwise  adjustment  of  the    THROTTLE  SCREW
at High Fire:

      
      

O2 decreases and CO2 increases

4.    Once  the  combustion  level  is  set  and  recorded    at

high fire, manually place the appliance into low fire

mode  by  pressing  the  service  button  “

”  with  “-”

button simultaneously on the control display once.

The control panel will display a L followed by the current
appliance  temperature  when  placed  into  low  fire  test
mode.

5.    If the combustion levels during low fire are not within

0.0  to  0.4%  CO2  lower  than  the  combustion  level
measured  at  high  fire,  remove  the  offset  pressure
cover screw and adjust the OFFSET SCREW using
a  T15  Torx  wrench  as  follows  (see  Figs.  3  &  4  on
page 5):

The OFFSET SCREW adjustment on the CHALLENGER’S gas
valve is very sensitive. A small  adjustment will have a sig-
nificant effect.

Counter-clockwise  adjustment  of  the  OFFSET
SCREW at Low Fire:

      O2 increases and CO2 decreases

Clockwise  adjustment  of  the  OFFSET  SCREW  at
Low Fire:

       O2 decreases and CO2 increases 

NOTICE

WARNING

NOTICE

WARNING

WARNING

Combustion Levels

Natural Gas

Propane Gas

H

ig

Fi

re

D

O

O

R

 O

F

F

* CO2 Range

9% to 10.1%

10.5% to 11.1%

CO2 Target

9.0%

10.8%

O2 Range

3.0% - 5.0%

4.1% - 5.0%

O2 Target

5.0%

4.5%

Lo

w

 F

ir

e

CO2 Range

0% - 0.4% < H.F

9.0% min.

0% - 0.4% < H.F

10.5% min.

O2 Range

0% - 0.6% > H.F

5.0% max.

0% - 0.6% > H.F

5.0% max.

CO Max.

100 ppm

150 ppm

* Door On can raise the maximum allowable CO2 by

0.4 or lower the minimum allowable 02 by 0.6.