Trianco EuroStar Premier 100/125 Condensing User, Installation, Commissioning & Servicing Instructions Download Page 19

INSTALLATION NOTES

(a)  Balanced-flue condensing boilers are designed 

to operate at low noise levels. During operation, 
a plume of condensation will be produced at 
certain times from the terminal. When positioning,
these factors should be taken into consideration
to ensure that they do not cause a nuisance to 
neighbouring properties. It should also be 
positioned to avoid the products of combustion 
from entering the building.

(b)  Keep the terminal clear of infrared sensing 

devices such as these used to control security 
lighting.

(c)  Positioning of flues under balconies and carports

should be avoided.

(d)  As the system operates under positive pressure,

it is essential that all flue joints are sealed correctly.

(e)  Only 28 sec. Kerosene Class C2 to BS 2869 is 

permitted for use with this appliance.

Note  Trianco balanced flue kits have been designed
exclusively for use with Trianco boilers and as such,
compatibility with other makes of boiler cannot be
guaranteed.

Balanced Flue Systems  
(optional extra)

The Trianco balanced flue system offers much greater
flexibility for siting, the boiler compared with a 
conventional chimney.  The only requirement is for a 
suitable outside wall to fit the horizontal discharge 
terminal or, alternatively, a single storey roof for a vertical
discharge. 

In addition to the siting benefit, the performance of 
balanced flue boilers is virtually unaffected by high wind
conditions since the wind pressures are applied equally
to both air intake and flue gas discharge, thus creating a
balanced condition.

Whereas some balanced flue boilers rely on case sealing
to achieve a room seal, Trianco  boilers have a sealed air
duct system which maintains the room sealed
performance even when the casing door is removed for
burner commissioning or adjustments.

The use of the balanced flue principle also enhances the
overall thermal efficiency of the boiler since the incoming
air extracts waste heat from the flue and returns it as 
pre-heated air to the burner where it aids combustion.

16

P

O

N

C. D

B

A

E

G

K

F

F

L

H. J

H

M

B

Note (1)

The terminal should be positioned so as to avoid 
products of combustion entering the building.

Note (2)

If the terminal is less than 2 metres above the 
ground level, balcony or place to which any
person has access, the terminal must be 
protected by a guard.

Note (3)

The flue must be positioned so that it does not 
cause nuisance and permits the dispersal of 
combustion products.

RECOMMENDED MINIMUM DISTANCES

FOR TERMINAL POSITION

FIG. 13  TERMINAL POSITION

Appliance burner type - Pressure Jet

Minimum distances to terminals in millimetres as measured from top of chimney 

or the rim of a low level discharge opening

A

Directly below an opening, air brick, window etc

600

B   Horizontally to an opening, air brick, window etc

600

C   Below a gutter, eaves or balcony with protection

75

Below a gutter or balcony without protection 

600

E

From vertical sanitary pipework   

(*600)

300

F

From an internal or external corner

(

*600)

300

G

Above ground or balcony level   

(

*600)

300

H

From a surface or boundary facing the terminal

600

J

From a terminal facing the terminal

1200

K

Vertically from a terminal on the same wall 

1500

L

Horizontally from a terminal on the same wall

750

M

Above the highest point of an intersection with the roof

600

N

From a vertical structure on the side of the terminal

750

O

Above a vertical structure less than 750mm from the side of the terminal

600

P

From a ridge terminal to a vertical structure on the roof

1500

*Scotland 1990

Summary of Contents for EuroStar Premier 100/125 Condensing

Page 1: ...d by householder USER INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS OIL FIRED CENTRAL HEATING BOILERS FOR BALANCED OR CONVENTIONAL FLUE BED 92 42 EEC EMC 89 336 EEC Premier 50 90 Condensing Premie...

Page 2: ...isposable gloves face masks and eye protection After handling wash hands and other exposed parts When disposing reduce dust with water spray ensure parts are securely wrapped GLUES SEALANTS PAINT Glue...

Page 3: ...ilation 8 9 Extractor fan 9 Electrical supply 9 Condensate Drain Connection 10 5 OIL SUPPLY Oil storage tank Steel and Plastic 11 Oil supply line 11 Single pipe oil supply 12 13 Two pipe oil supply 12...

Page 4: ...before contacting your Service Engineer 1 USER INSTRUCTIONS Please note to assist Trianco in improving customer service it is important that the guarantee registration card is returned HOW TO USE YOUR...

Page 5: ...s ensure the oil storage tank is topped up regularly do not wait until the tank is nearly empty before refilling as sludge and water could be sucked into the oil pipe affecting the operation of the bu...

Page 6: ...inted Service Agent must check all his work PRIOR to requesting Trianco to attend PLEASE NOTE Unauthorised invoices for attendance and repair work carried out on this appliance by any third party will...

Page 7: ...BS 7593 requirements Always refer to the manufacturers instructions Failure to flush and add inhibitors to the system will invalidate the appliance warranty The appliance is designed to be fitted to...

Page 8: ...IPE OR ELECTRIC CABLE ENTRY BOTH SIDES RETURN CONNECTION DIA 22MM EACH SIDE FLOW CONNECTION DIA 22MM EACH SIDE Heating Return Cleaning Hole Cleaning Hole Heating Return Heating Flow Condensate drain H...

Page 9: ...36 kW 130 900 btu s 36 36 kW 60 000 btu s 17 58 kW 70 000 btu s 20 51 kW 80 000 btu s 23 44 kW 90 000 btu s 26 37 kW 100 000 btu s 29 3 kW 110 000 btu s 32 2 kW 120 000 btu s 35 2 kW 125 000 btu s 36...

Page 10: ...FIG 5 WIRING DIAGRAM 7...

Page 11: ...Local Water Undertakings By laws OFTEC Installation Requirements for Oil Fired Boilers and Oil Storage Tanks OFST 100 and OFST 200 Health and Safety at Work Act The installer should be aware of his re...

Page 12: ...r ancillary controls See wiring diagram Fig 5 Warning High and Low Voltage In certain parts of the country where there is a known risk of high or low voltage fluctuations the oil burner shall be preve...

Page 13: ...ternal waste drain If the boiler is to be fitted in a position where the external ground level is higher than the boiler and there are no internal drains a condensate pump can be fitted refer to pump...

Page 14: ...t corrode and therefore never need painting c They are easier to handle because of their lower weight d They have a 10 year manufacturer s guarantee Plastic tanks should be fitted with similar compone...

Page 15: ...released from the oil to affect combustion 2 The return pipe must end at the same level as the suction outlet to prevent loss of prime 3 The outlet from the tank should be approximately 75mm 3 in abo...

Page 16: ...ID 10 21 31 41 52 62 73 83 PIPE 8mm ID 33 66 98 100 100 100 100 100 MAXIMUM OIL SUPPLY LINE LENGTH L MAXIMUM LENGTH METRES LIFT H METRES 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 PIPE 6mm ID 48 42 36 30 24 18 1...

Page 17: ...14 FIG 13 DE AERATED OIL SUPPLY INSTALLATION REFER TO MANUFACTURERS INSTRUCTIONS FOR OIL DE AERATOR INSTALLATION DETAILS REMOTE OPERATED FIRE VALVE OIL FILTER...

Page 18: ...the boiler No separate drain at the base of the flue system is required 3 Where an existing chimney is to be used it must be lined with a stainless steel liner that is approved for use on an oil fire...

Page 19: ...t system which maintains the room sealed performance even when the casing door is removed for burner commissioning or adjustments The use of the balanced flue principle also enhances the overall therm...

Page 20: ...5 Take flue socket plate off the top of boiler leaving the flue gasket in position 6 If the flue is to be fitted terminating to the left or right hand side of the boiler the corresponding section of s...

Page 21: ...Fig 19 19 7 18...

Page 22: ...SEALING PLATE 1 8 GASKET SUPPLIED WITH BOILER 9 FLUE PIPE O RING 1 10 JUBILEE CLIP 1 230mm ROUND KIT 2350 2351 Supplied with boiler Supplied with boiler IMPORTANT When installing the flue system it is...

Page 23: ...nditions the system should be drained down Handing Over After completing the boiler installation the installer should make a thorough check of the system to ensure it is completely satisfactory and de...

Page 24: ...tion making gas tight seal using washers and wing nuts previously removed 12 Check condensate trap to ensure the outlet is not obstructed 13 Refit the burner securing the air hose in position using th...

Page 25: ...ell not seeing flame Clean photo cell and ensure it is fully plugged in Air trapped in pump Bleed off air through pressure gauge tapping Solenoid valve faulty Check coil for continuity and replace if...

Page 26: ...OLENTLY Delayed ignition Check electrode setting and adjust to correct gap Check electrodes for damage Check HT leads for damage and positive connection BURNER REPEATEDLY Exhaust gas in combustion air...

Page 27: ...50 4 223330 1 15 Boiler Bottom Baffle 2 223053 1 223336 1 16 Boiler Middle Baffle 2 223333 4 17 Condensing Unit Baffle 2 223076 2 223392 2 18 Boiler Flue Cover 223019 1 223378 1 19 Condensing Unit Flu...

Page 28: ...Copyright in this brochure and the drawings or illustrations contained in it is vested in Trianco Limited and neither the brochure or any part thereof may be reproduced without prior written consent T...

Reviews: