TRENT CaterSense-02 Installation And Commissioning Instructions Download Page 8

CaterSense 

the Intelligent answer

 

 

CS-INST2-0.002 
Model: CaterSense 02  

Page 8 

07-11 

2.02  Mode Set-up 

 
Once the above has been carried out, the system is now ready to be powered up.  
 
The CaterSense-02 unit is pre-set to close the gas solenoid valve if it detects gas pressure 
below 12 mbar.  The unit also tests the integrity of the pipework during every start up by 
opening the gas valve for 10 seconds, and then closing it for 30 seconds.  If a significant drop 
in pressure is detected during this time, the CaterSense unit will not open the valve.  The 
CaterSense-02 has an inbuilt facility to open the gas valve for a maximum of 5 minutes to 
allow for system checking.

  

 

 

 

 

 

The gas valve will open for a maximum of 5 minutes to allow for system checking.  The 
internal gas pressure test can then be activated.  
 

 

 

 

Ensure the fans are running at the lowest speed. Allow system to run and settle. 
 
If the fan is monitored via an external source, and the "fan healthy" signal is provided from a 
volt-free contact, ensure that the contact is closed. 

4) 

PRESS   

 

 

SYSTEM CONDITION 

 

 

 

 

 

GAS VALVE 

 

 

 

 

 

FAN 

 

 

 

 

 

 

 

 

All other LEDs 

3) 

PRESS   

 

 

GAS VALVE 

 

 

 

 

 

 

 

 

 

 

 

 

GAS VALVE 

 

 

 

 

 

 

 

 

 

 

 

 

SYSTEM CONDITION 

 

 

 

 

 

GAS PRESSURE   

 

 

 

START 

RESET / GPT 

10 sec 

30 sec 

2) 

PRESS   

 

 

GAS VALVE 

 

 

 

 

START 

RESET / GPT 

1) 

PRESS   

 

 

SYSTEM CONDITION 

 

(Hold for 3 secs) 

 

 

GAS VALVE 

 

 

 

 

 

GAS PRESSURE 

 

 

 

 

 

FAN 

 

 

 

 

 

All other LEDs 

Summary of Contents for CaterSense-02

Page 1: ...se the Intelligent answer CS INST2 0 002 Model CaterSense 02 Page 1 07 11 CaterSense 02 GAS SUPPLY CONTROL with GAS PRESSURE PROVING AND INTELLIGENT FLOW DETECTORS INSTALLATION and COMMISSIONING INSTR...

Page 2: ...g details 1 03 Cable entry 1 04 Electrical connections 1 05 System mode and set up locations 2 0 Set up and commissioning 2 01 Initial Set up 2 02 Mode Set up 2 03 Functional Operation 2 04 Troublesho...

Page 3: ...de at the bottom of the enclosure and lift off each side panel in turn by first pulling the bottom towards you This will reveal the four facia plate fixing screws 3 Unscrew these four screws and lift...

Page 4: ...dge of the main PCB circuit board Terminals 1 to 22 are the smaller terminals 1 5 mm cable and are used for the sensors Screened cable must be used Terminals 29 to 34 are the larger terminals 4 mm cab...

Page 5: ...OADING OF THE CATERSENSE AND PLANT ITEMS N L E E L N LOCAL 240Vac SWITCHED FUSED POWER SUPPLY See Note 3 POWER SUPPLY N L E OUT GAS VALVE N L E LOCAL ISOLATOR See Note 1 GAS VALVE GAS VALVE OUTPUT WIT...

Page 6: ...ard The CaterSense also has a unique Self set system commissioning tool which makes for easy system commissioning These devices are located on the left hand side of the main PCB under the side cover a...

Page 7: ...etailed on the wiring diagram for your installation b Input Jumpers Ensure that the correct input jumpers have been removed as detailed on the System Mode page for your installation c Sensor Links If...

Page 8: ...The CaterSense 02 has an inbuilt facility to open the gas valve for a maximum of 5 minutes to allow for system checking The gas valve will open for a maximum of 5 minutes to allow for system checking...

Page 9: ...n is monitored via an external source and the fan healthy signal is provided from a volt free contact ensure that the contact is closed The set up is now complete and the system is ready to run Note P...

Page 10: ...ote start stop opening and closing the enable contact On systems with remote start stop if the local SYSTEM STOP pad is pressed the system stops immediately This can be reset by either pressing SYSTEM...

Page 11: ...alve output will be deactivated Solution Ensure remote knock off button has been released Check wiring to remote knock off button The system must be reset by pressing STOP before it can be restarted 2...

Page 12: ...The system must be reset by pressing STOP before it can be restarted 2 047 GAS PRESSURE FAULT 2 Cause The gas pressure has dropped below 12mbar during normal running Solution See above 2 048 EMERGENC...

Page 13: ...ly checked and problems identified If the current is at a fault level for longer than 30s a system fault would occur during normal operation It is normal for current draw to fall outside normal levels...

Page 14: ...CaterSense the Intelligent answer CS INST2 0 002 Model CaterSense 02 Page 14 07 11 Notes...

Page 15: ...CaterSense the Intelligent answer CS INST2 0 002 Model CaterSense 02 Page 15 07 11 Notes...

Page 16: ...S SAFE iii If in doubt ask contact us on or by any of the above iv Ensure that the client has been shown how to operate the system and that they have been handed the users guide TRENT PRODUCTS Trent H...

Reviews: