CS-INST2-0.002 Model: CaterSense 02
Page 1
07-11
CaterSense -02
GAS SUPPLY CONTROL with
GAS PRESSURE PROVING
AND INTELLIGENT FLOW DETECTORS
INSTALLATION and COMMISSIONING
INSTRUCTIONS
Page 1: ...se the Intelligent answer CS INST2 0 002 Model CaterSense 02 Page 1 07 11 CaterSense 02 GAS SUPPLY CONTROL with GAS PRESSURE PROVING AND INTELLIGENT FLOW DETECTORS INSTALLATION and COMMISSIONING INSTR...
Page 2: ...g details 1 03 Cable entry 1 04 Electrical connections 1 05 System mode and set up locations 2 0 Set up and commissioning 2 01 Initial Set up 2 02 Mode Set up 2 03 Functional Operation 2 04 Troublesho...
Page 3: ...de at the bottom of the enclosure and lift off each side panel in turn by first pulling the bottom towards you This will reveal the four facia plate fixing screws 3 Unscrew these four screws and lift...
Page 4: ...dge of the main PCB circuit board Terminals 1 to 22 are the smaller terminals 1 5 mm cable and are used for the sensors Screened cable must be used Terminals 29 to 34 are the larger terminals 4 mm cab...
Page 5: ...OADING OF THE CATERSENSE AND PLANT ITEMS N L E E L N LOCAL 240Vac SWITCHED FUSED POWER SUPPLY See Note 3 POWER SUPPLY N L E OUT GAS VALVE N L E LOCAL ISOLATOR See Note 1 GAS VALVE GAS VALVE OUTPUT WIT...
Page 6: ...ard The CaterSense also has a unique Self set system commissioning tool which makes for easy system commissioning These devices are located on the left hand side of the main PCB under the side cover a...
Page 7: ...etailed on the wiring diagram for your installation b Input Jumpers Ensure that the correct input jumpers have been removed as detailed on the System Mode page for your installation c Sensor Links If...
Page 8: ...The CaterSense 02 has an inbuilt facility to open the gas valve for a maximum of 5 minutes to allow for system checking The gas valve will open for a maximum of 5 minutes to allow for system checking...
Page 9: ...n is monitored via an external source and the fan healthy signal is provided from a volt free contact ensure that the contact is closed The set up is now complete and the system is ready to run Note P...
Page 10: ...ote start stop opening and closing the enable contact On systems with remote start stop if the local SYSTEM STOP pad is pressed the system stops immediately This can be reset by either pressing SYSTEM...
Page 11: ...alve output will be deactivated Solution Ensure remote knock off button has been released Check wiring to remote knock off button The system must be reset by pressing STOP before it can be restarted 2...
Page 12: ...The system must be reset by pressing STOP before it can be restarted 2 047 GAS PRESSURE FAULT 2 Cause The gas pressure has dropped below 12mbar during normal running Solution See above 2 048 EMERGENC...
Page 13: ...ly checked and problems identified If the current is at a fault level for longer than 30s a system fault would occur during normal operation It is normal for current draw to fall outside normal levels...
Page 14: ...CaterSense the Intelligent answer CS INST2 0 002 Model CaterSense 02 Page 14 07 11 Notes...
Page 15: ...CaterSense the Intelligent answer CS INST2 0 002 Model CaterSense 02 Page 15 07 11 Notes...
Page 16: ...S SAFE iii If in doubt ask contact us on or by any of the above iv Ensure that the client has been shown how to operate the system and that they have been handed the users guide TRENT PRODUCTS Trent H...