TREND VSD2H Datasheet Download Page 9

VSD2H Variable Speed Drives Data Sheet TA201104 Issue 3, 08-Oct-2013

 

9

Data Sheet 

VSD2H

L1 L2 L3

DC-

V

W

U

L1 L2 L3

M

3~

R-

R+

Power connections

3 phase mains supply

motor connection

control connections

Connect according to configuration

uSB

(connection to PC)

2

3

8

6

23

22

26

25

AI1+

AI1-

DI1

RO1/2 COM

RO1/3 NO

RO2/2 COM

RO2/3 NO

+24 V

AO SIG

AO 0 V

DO NO

DO COM

DI SIG

n

DI COM

n

DI

SIG

n+1

DI

COM

n+1

Voltage

Start forward

Running

Fault

Analogue Output 

0 to 10V

Digital 

Output

Digital 

Input

Digital 

Input

IQ Controller

VSD2H Drive

e.g connections to IQ Controller with default settings

RJ45

USB

Note that the NXNI interface connects the drive 

directly to the an IQ system current loop Lan, and 

the NXIP connects the drive to an IQ system Lan on 

Ethernet. They both enable the drive to be monitored 

and controlled by IQs (IC comms) and Supervisors 

(Text comms) - see order codes for details. Note that 

the NXNI allows the unit to be monitored by all Trend 

IQ controllers, but it can only be written to by IQ3, 

IQ4, or IQeco controllers.

ACC/VSD2H/USB-PC/CABLE

connectionS

rS485

 (BACnet over MS/TP or MODBUS RTU)

8    9   10  11

19  30 A B

-

+

Ensure correct polarity

Use  STP  (Shielded  Twisted 

Pair),  type  Belden  cable 

9841 or similar.

ethernet

 

(BACnet over IP or MODBUS TCP)

Connect to hub, or use crossover adaptor

Standard Ethernet cable

RJ45

RJ45

XCITE/XA

crossover adaptor

Summary of Contents for VSD2H

Page 1: ...s multi pump cascade control Features 380 to 480 Vac 3 phase current rating range from 3 A to 310 A IP21 and IP54 models available optional Trend system network interfaces NXNI or NXIP application con...

Page 2: ...ving in installation costs switchgear is eliminated motor cables are reduced from 6 to 3 wires for larger drives power factor correction capacitors are not required size and cost of cabling and fuses...

Page 3: ...ctors identified by letters A B D E of the control board When the frequency converter is delivered from the factory the control unit includes the standard complement of two basic boards the Basic I O...

Page 4: ...on 4 AI2 Analogue input voltage or current DIP switch 3 selects V or mA Differential input if not connected to ground PID actual value 1 4 to 20 mA 5 AI2 Analogue input c2 ommon 6 24 Vout 24 V auxilia...

Page 5: ...to be mounted in the panel door connected to the VSD by a 2 m cable RS485 AO1 AI2 AI1 OFF ON Current RS485 fieldbus termination resistor Current Current Voltage Voltage Voltage Default positions are...

Page 6: ...e clock the drive fan keypad settings and fieldbus RS485 or Ethernet parameters User settings Language application parameter backup and restore to and from keypad Favourites advanced commissioning key...

Page 7: ...lso to high inertia loads High Switching Frequency The VSD2H is capable of providing the maximum power with high switching frequency Benefit Low audible noise from the motor Prohibit frequency Overrid...

Page 8: ...ed motor cables is recommended they should be routed as far away from other cables as possible and cross other cables at right angles The motor cable shield should be grounded at both the VSD2H drive...

Page 9: ...lt settings RJ45 USB Note that the NXNI interface connects the drive directly to the an IQ system current loop Lan and the NXIP connects the drive to an IQ system Lan on Ethernet They both enable the...

Page 10: ...Laninterface see NXNI data sheet NXIP NXvariablespeeddriveIQsystemLanonEthernetinterface see NXIP data sheet ACC VSD2H DOOR MOUNTING KIT Kit to mount keypad unit on door includes 2 m cable ACC VSD2H H...

Page 11: ...fications Electrical Supply voltage 380 to 480 Vac 10 3 phase Frequency 50 to 60 Hz 5 10 Connection to mains once per minute or less Starting delay 4 s MR4 to MR6 6 s MR7 to MR9 Motor voltage 0 to sup...

Page 12: ...logue output 1 output AO1 can be set to either voltage or current by DIP switch RL 500 ohm resolution 0 1 accuracy 2 Short circuit protected Voltage 0 2 to 10 V Current 0 4 to 20 mA The lower range 0...