TREND VSD2H Datasheet Download Page 12

12 

VSD2H Variable Speed Drives Data Sheet TA201104 Issue 3, 08-Oct-2013

VSD2H 

Data Sheet

Please send any comments about this or any other Trend technical publication to [email protected]

© 2013

 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls 

Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation 

to notify any person of such revisions or changes.

trend control Systems limited

Albery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com

trend control System uSA

6670  185th  Avenue  NE,  Redmond,  Washington  98052,  USA.  Tel:(425)  869-3900  Fax:(425)  869-8445  www.trend-americas.com

SPeciFicAtionS 

(continued)

Protective Functions

Overcurrent 

:Trip limit 4.0 x I

L

 instantaneously

Overvoltage trip limit  :911 V

Undervoltage trip limit   :351 V

Earth fault protection  :Protects drive from earth fault in motor 

or cable

Mains supervision 

:Trips if any input phase is missing

Motor phase supervisor: Trips if any output phase is missing

Other 

:Unit overtemperature protection, motor 

overload protection, stall protection, 

motor underload protection, short 

circuit protection of +24 V and +10 V 

reference voltages

inputs and outputs

Analogue inputs 

:2 inputs (AI1, AI2) can be set to either 

voltage  or  current  by  DIP  switches. 

Resolution 0.1 %, accuracy ±1 %

Voltage 

:0 (2) to +10 V, R

in

 = 200 kohm,

Current 

:0 (4) to 20 mA, R

in

= 250 ohm

 

The lower range (0 or 2 for voltage, 0 

or  4  for  current)  set  by  configuration 

parameters M3.5.2.3 for AI1, M3.5.2.9 

for AI2.

Digital inputs 

:6  inputs  (DI1  to  DI6)  with  positive  or 

negative logic, 0 to 5 Vdc =0, 15 to 30 

Vdc=1

Motor thermistor input  :(TI1)  R

TRIP

=4k7ohm  (PTC)  with 

measuring voltage of 3.5 V

Analogue output 

:1  output  (AO1)  can  be  set  to  either 

voltage  or  current  by  DIP  switch.  R

L

 

<500  ohm,  resolution  0.1  %,  accuracy 

±2 %. Short circuit protected. 

Voltage 

0(2) to 10 V

Current 

0(4) to 20 mA, 

 

The lower range (0 or 2 for voltage, 0 

or  4  for  current)  set  by  configuration 

parameter M3.5.4.1.3.

Relay outputs 

:2  outputs  (RO1,  RO2)  isolated 

changeover  relay  contacts.  Switching 

capacity 24 Vdc/8 A, 250 Vac/8 A, 125 

Vdc/0.4 A. Minimum switching load 5 V/ 

10 mA.

Auxiliary voltage out  :+24  Vdc  ±10  %,  250  mA  max.  Short 

circuit protected. Available from two 

terminals.

Auxiliary voltage in 

:+24 Vdc ±10 %, 100 mA max. Backup 

power  enables  parameter  setting  and 

keeps  control  unit  active  during  mains 

failure.

10 V reference voltage out 

:(e.g.  for  potentiometer)  +10 

Vdc, +3% 10 mA max.

environmental

Operating temperature :-10 °C (no frost) to +40 °C. up to 50 °C 

with derating

Storage temperature  :-40 °C to +70 °C

Relative humidity 

:0  to  95  %RH  non-condensing, 

non-corrosive, no dripping water

Air quality 

:Tested  according  to  IEC  60068-2-60 

Test  Ke:  Flowing  mixed  gas  corrosion 

test, Method 1 [H

2

S and SO

2

]

Chemical vapours  :IEC 60721-3-3, unit in operation class 

3C2

Mechanical particles 

:IEC60721-3-3, unit in operation 

class 3S2

Altitude 

100% load capacity (no derating) up to 

1000  m.  1%  derating  for  each  100  m 

above 1000 m (max. 4500 m)

 

Allowed voltage for I/O signals

 

Up to 2000 m: max 240 V

 

200 to 4000 m: max 120 V

Mechanical vibration  :5  to  150  Hz.  EN61800-5-1  and 

EN60068-2-6

 

Displacement amplitude 1mm (peak) at 

5 to 15.8 Hz

 

Max acceleration amplitude 1 G at 15.8 

to 150 Hz

Mechanical shock 

:UPS  drop  test  (for  applicable  UPS 

weights)

 

EN61800-5-1 and EN60068-2-27

 

Storage and shipping: max 15 G, 11 ms 

(in package)

Enclosure class 

:IP21/Type 1 or IP54/Type 12 available 

over  entire  kW/HP  range.  Note  that 

IP54  is  only  fulfilled  with  keypad  in 

place.

EMC immunity 

:EN61800-3  (2004)  first  and  second 

environment  (industrial  and  public 

electrical works)

EMC emissions 

:EN61800-3  (2004)  Category  C2 

(suitable for public electricity networks 

such as buildings)

Harmonics emissions  :EN61000-3-12

Safety 

:EN61800-5-1 (2007), 

 

UL 508C CE, cUL,

 

(check unit nameplate for details)

Noise levels 

:Average noise level (cooling fan) sound 

power level in dB(A). MR4: 65, MR5: 70, 

MR6: 77, MR7: 77, MR8: 86, MR9: 87

Summary of Contents for VSD2H

Page 1: ...s multi pump cascade control Features 380 to 480 Vac 3 phase current rating range from 3 A to 310 A IP21 and IP54 models available optional Trend system network interfaces NXNI or NXIP application con...

Page 2: ...ving in installation costs switchgear is eliminated motor cables are reduced from 6 to 3 wires for larger drives power factor correction capacitors are not required size and cost of cabling and fuses...

Page 3: ...ctors identified by letters A B D E of the control board When the frequency converter is delivered from the factory the control unit includes the standard complement of two basic boards the Basic I O...

Page 4: ...on 4 AI2 Analogue input voltage or current DIP switch 3 selects V or mA Differential input if not connected to ground PID actual value 1 4 to 20 mA 5 AI2 Analogue input c2 ommon 6 24 Vout 24 V auxilia...

Page 5: ...to be mounted in the panel door connected to the VSD by a 2 m cable RS485 AO1 AI2 AI1 OFF ON Current RS485 fieldbus termination resistor Current Current Voltage Voltage Voltage Default positions are...

Page 6: ...e clock the drive fan keypad settings and fieldbus RS485 or Ethernet parameters User settings Language application parameter backup and restore to and from keypad Favourites advanced commissioning key...

Page 7: ...lso to high inertia loads High Switching Frequency The VSD2H is capable of providing the maximum power with high switching frequency Benefit Low audible noise from the motor Prohibit frequency Overrid...

Page 8: ...ed motor cables is recommended they should be routed as far away from other cables as possible and cross other cables at right angles The motor cable shield should be grounded at both the VSD2H drive...

Page 9: ...lt settings RJ45 USB Note that the NXNI interface connects the drive directly to the an IQ system current loop Lan and the NXIP connects the drive to an IQ system Lan on Ethernet They both enable the...

Page 10: ...Laninterface see NXNI data sheet NXIP NXvariablespeeddriveIQsystemLanonEthernetinterface see NXIP data sheet ACC VSD2H DOOR MOUNTING KIT Kit to mount keypad unit on door includes 2 m cable ACC VSD2H H...

Page 11: ...fications Electrical Supply voltage 380 to 480 Vac 10 3 phase Frequency 50 to 60 Hz 5 10 Connection to mains once per minute or less Starting delay 4 s MR4 to MR6 6 s MR7 to MR9 Motor voltage 0 to sup...

Page 12: ...logue output 1 output AO1 can be set to either voltage or current by DIP switch RL 500 ohm resolution 0 1 accuracy 2 Short circuit protected Voltage 0 2 to 10 V Current 0 4 to 20 mA The lower range 0...

Reviews: