VSD2H Variable Speed Drives Data Sheet TA201104 Issue 3, 08-Oct-2013
VSD2H
Data Sheet
Please send any comments about this or any other Trend technical publication to [email protected]
© 2013
Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls
Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation
to notify any person of such revisions or changes.
trend control Systems limited
Albery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com
trend control System uSA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-americas.com
SPeciFicAtionS
(continued)
Protective Functions
Overcurrent
:Trip limit 4.0 x I
L
instantaneously
Overvoltage trip limit :911 V
Undervoltage trip limit :351 V
Earth fault protection :Protects drive from earth fault in motor
or cable
Mains supervision
:Trips if any input phase is missing
Motor phase supervisor: Trips if any output phase is missing
Other
:Unit overtemperature protection, motor
overload protection, stall protection,
motor underload protection, short
circuit protection of +24 V and +10 V
reference voltages
inputs and outputs
Analogue inputs
:2 inputs (AI1, AI2) can be set to either
voltage or current by DIP switches.
Resolution 0.1 %, accuracy ±1 %
Voltage
:0 (2) to +10 V, R
in
= 200 kohm,
Current
:0 (4) to 20 mA, R
in
= 250 ohm
The lower range (0 or 2 for voltage, 0
or 4 for current) set by configuration
parameters M3.5.2.3 for AI1, M3.5.2.9
for AI2.
Digital inputs
:6 inputs (DI1 to DI6) with positive or
negative logic, 0 to 5 Vdc =0, 15 to 30
Vdc=1
Motor thermistor input :(TI1) R
TRIP
=4k7ohm (PTC) with
measuring voltage of 3.5 V
Analogue output
:1 output (AO1) can be set to either
voltage or current by DIP switch. R
L
<500 ohm, resolution 0.1 %, accuracy
±2 %. Short circuit protected.
Voltage
0(2) to 10 V
Current
0(4) to 20 mA,
The lower range (0 or 2 for voltage, 0
or 4 for current) set by configuration
parameter M3.5.4.1.3.
Relay outputs
:2 outputs (RO1, RO2) isolated
changeover relay contacts. Switching
capacity 24 Vdc/8 A, 250 Vac/8 A, 125
Vdc/0.4 A. Minimum switching load 5 V/
10 mA.
Auxiliary voltage out :+24 Vdc ±10 %, 250 mA max. Short
circuit protected. Available from two
terminals.
Auxiliary voltage in
:+24 Vdc ±10 %, 100 mA max. Backup
power enables parameter setting and
keeps control unit active during mains
failure.
10 V reference voltage out
:(e.g. for potentiometer) +10
Vdc, +3% 10 mA max.
environmental
Operating temperature :-10 °C (no frost) to +40 °C. up to 50 °C
with derating
Storage temperature :-40 °C to +70 °C
Relative humidity
:0 to 95 %RH non-condensing,
non-corrosive, no dripping water
Air quality
:Tested according to IEC 60068-2-60
Test Ke: Flowing mixed gas corrosion
test, Method 1 [H
2
S and SO
2
]
Chemical vapours :IEC 60721-3-3, unit in operation class
3C2
Mechanical particles
:IEC60721-3-3, unit in operation
class 3S2
Altitude
100% load capacity (no derating) up to
1000 m. 1% derating for each 100 m
above 1000 m (max. 4500 m)
Allowed voltage for I/O signals
Up to 2000 m: max 240 V
200 to 4000 m: max 120 V
Mechanical vibration :5 to 150 Hz. EN61800-5-1 and
EN60068-2-6
Displacement amplitude 1mm (peak) at
5 to 15.8 Hz
Max acceleration amplitude 1 G at 15.8
to 150 Hz
Mechanical shock
:UPS drop test (for applicable UPS
weights)
EN61800-5-1 and EN60068-2-27
Storage and shipping: max 15 G, 11 ms
(in package)
Enclosure class
:IP21/Type 1 or IP54/Type 12 available
over entire kW/HP range. Note that
IP54 is only fulfilled with keypad in
place.
EMC immunity
:EN61800-3 (2004) first and second
environment (industrial and public
electrical works)
EMC emissions
:EN61800-3 (2004) Category C2
(suitable for public electricity networks
such as buildings)
Harmonics emissions :EN61000-3-12
Safety
:EN61800-5-1 (2007),
UL 508C CE, cUL,
(check unit nameplate for details)
Noise levels
:Average noise level (cooling fan) sound
power level in dB(A). MR4: 65, MR5: 70,
MR6: 77, MR7: 77, MR8: 86, MR9: 87