SDU-Lon

Installation Instructions

SDU-Lon Installation Instructions TG200599 Issue 1/C 20/11/06

6

Mount Unit

14

Standard UK pattress wall box

or panel

60 mm

46 mm

50 mm

Ø 4 mm
(M3.5
screw)

Ø 4 mm
(M3.5
screw)

60 mm

2 off (M3.5 x 35 mm)
screws provided

Install on Lon Management Tool

12

If other IQ System devices on LonWorks are installed on LonWorks Management Tool.

When installing SDU-LON on LonWork Management Tool, push service pin button when requested.

S P

E N G

1

2

3

4

See LonWorks network management tool
manual. See IQ System LonWorks Products
Engineering Manual (TE200292). LonWorks
System integrator must have LonWorks
engineering expertise.

SDU Data Sheet TA200559
for LonWorks network
variables (NVs)

The SDU must also be associated with its IQL using the LMT
The following network variables need to be set up using the LMT:

nciInstallState

: set to CFG_EXTERNAL

nciHostNodeAddr

: set to associated IQL LonWorks node address

nciSubnetAddr

: set to associated IQL LonWorks subnet address

nciMsgCode

: set message code of associated IQL

nciDomainIndex

: set to domain index of associated IQL

service pin button

Associate SDU with its IQL

13

a

b

not if installed on LonWorks Management Tool

SP

ENG

1

2

3

4

Connect to IQ

“Connect to IQ”

SP

ENG

1

2

3

4

Press IQL Service PIN

“Press IQL
Service Pin”

c

d

4 secs

Either use IQLTool2 runing in SET and connected to LonWorks using LCI or use buttons as follows:

3

Installation 

(Continued)

2 4 V a c

I Q

L

 

+

O / S

L A N

L O N

N I D

S t r a t e g y

 

        :           :           :           :           :

D O 1

I N 1

D O 2

D O 3

~

D O 4

D O 5

I N 2

I N 3

2 4 V

C O M

2 4 V

C O M

~

C O M

service pin button

Summary of Contents for SDU-Lon

Page 1: ...hould complywiththeHSEMemorandumofGuidance on Electricity at Work Regulations 1989 ForUSAinstallequipmentinaccordancewith the National Electric Code WARNING Other than removing frontpanel step3 donoto...

Page 2: ...oute Cables 5 b a c Check SDU type 4 Check SDU LON Ifonesideofthe24Vacinputpowerisconnected to 0 V that side must be connected to the SDU negative terminal 24 Vdc 24 Vdc Power Supply SDU 0 Vdc 24 Vac...

Page 3: ...SDU Tool Set up Mode Unrestricted Restricted Home Page Show Don t show Restrictive mode list Select required modules Language Translation of standard text Backup File to Disk S P E N G 1 2 3 4 SDU Dat...

Page 4: ...0 0 m F 5 0 V m i n 1 0 0 m F 5 0 V m i n Do not allow wires to cross on a loop Terminate bus at one end only Terminator e g LONTERMINATOR Terminal size 0 5 to 2 55 mm2 14 to 20 AWG Normal Trend Lan...

Page 5: ...Start Up Reset 10 S P E N G 1 2 3 4 T r e n d S D U V 1 0 Firmware version communications failure or no sensor set up Connect to IQ Check LonWorks Connected 11 LonWorks green SDU faulty Switch on Inp...

Page 6: ...k variables NVs The SDU must also be associated with its IQL using the LMT The following network variables need to be set up using the LMT nciInstallState set to CFG_EXTERNAL nciHostNodeAddr set to as...

Page 7: ...ck Operation Monitor 17 1 2 3 4 Sensor S e n s o r 1 F l o o r 1 S p a c e T e m p 2 0 3 D e g C Knob Switch Driver Digital Input Time Zone Time 1 2 3 4 S e n s o r 1 F l o o r 1 S p a c e T e m p 2 0...

Page 8: ...C 20 11 06 8 3 Installation Continued 1 2 3 4 1 2 3 4 Check Operation Adjust 18 1 2 3 4 Digital ON Analogue if PIN required see step 19 OFF Units 20 32 Tenths 20 32 Knob 1 Room 1 Setpoint 20 01 DegC...

Page 9: ...99 Issue 1 C 20 11 06 9 InstallationInstructions SDU Lon 1 2 3 4 S e n s o r 1 F l o o r 1 S p a c e T e m p 2 0 3 D e g C Enter PIN 19 a PIN 5 b c PIN X 5 d e PIN X X 5 f g PIN X X X 5 h 1 2 3 4 P I...

Page 10: ...tep 3 b Set mode c Replace front panel see step 15 e d o M t e S e g a P e m o H e g a P m r a l A g o L 0 d e t c i r t s e r n U o N o N 1 d e t c i r t s e r n U s e Y o N 2 d e t c i r t s e r n U...

Page 11: ...onth month year daylight saving on day of month month daylight saving off day of month month Calendars Use next Free every Start date Stop date Special day type for the zone SDU Data Sheet TA200559 If...

Page 12: ...ationfromtimetotimeandmakechangestothecontenthereof withoutobligationtonotifyanypersonofsuchrevisionsorchanges Trend Control Systems Limited P O Box34 Horsham WestSussex RH122YF UK Tel 44 0 140321888F...

Reviews: