TREND IQ422 Installation Instructions Manual Download Page 7

IQ422, IQ4NC/00, IQ4NC/12 Controllers Installation Instructions - Configuring TG201265 Issue 12, 24-Jul-2018 

7

InstallationInstructions-Configuring

 

IQ422, IQ4NC/00, IQ4NC/12

21

SetCurrentLoopBaudRate

(IQ4NC or ../LAN variants only, if current loop network being used)

22

SetupRS232/USBPortAddressing

(if required)

23

CheckLANOKIndicator

(not IQ4NC)

2 CONFIGURATION 

(continued)

IQTool Monitor Applet Manual (TE201298)

SET Manual (TE200147)

IQ4 Configuration Manual (TE201263)

Parameter

Range

Supervisor port

0, 4 to 9, 11 to 119

Default=0 local access only

USB 

Engineering port

0, 4 to 9, 11 to 119

Default=0 temporarily takes address 125 

Use SET’s IQTool Monitor Applet to set the Supervisor Port or 

USB Engineering Port as required. 

IQTool Monitor Applet Manual (TE201298)

SET Manual (TE200147)

IQ4 Configuration Manual (TE201263)

If  the  IQ4xx  is  to  provide  connection  to  the  network  for 

supervisors  and  tools  it  is  necessary  to  setup  the  RS232 

Supervisor Port or USB Engineering Port as required.

Normal operation indication

  

LAN built OK

   

 

Attempting to build LAN

Note: It is normal behaviour for LAN OK indicator to extinguish 

for up to 1 min after detecting baud rate, then illuminate.

Fault indication (

Ethernet LAN)

 

Unable to communicate on LAN. 

Note: Only applies if current loop is 

disabled or is not fitted.

Fault indication 

(Current Loop LAN)

   

    

every 15s Longer than 2 minutes indicates 

LAN/internetwork cannot be built.

 

Check baud settings of all devices on current loop – see 

step 21, and check all device connections.

 

If still flashing, fit loop back:

85

84

86

87

RX- RX+

TX- TX+

If indicator turns OFF, device is faulty. If ON, reconnect 

network and switch off all other devices on the network.

 

If still OFF, check network cabling for short circuits with 

a multimeter (NOT Megger).

 

If ON switch on other devices in turn until faulty device 

found (i.e. LAN OK goes OFF), inspect that device to 

determine and and correct the fault.

By default the IQ4xx will auto detect the baud rate in use on 

the current loop. If all devices are set to auto detect the baud 

rate chosen cannot be guaranteed, in which case it may be 

necessary to manually set one device to a known rate.

Use  SET’s  IQTool  Monitor  Applet  to  disable  autobaud  and 

specify the baud rate.

Module Parameter

Range

IQ Lan 

network

Autobaud

0 (disabled) or 1 (enabled)

Baud Rate

1k2, 4k8, 9k6, 19k2, 38k4

LANOK

(green)

Summary of Contents for IQ422

Page 1: ...al TE201299 IQ4 Configuration Manual TE201263 Note PDF copies are included with SET installation in the following folder C Trend Control Systems Documentation IQ422 IQ4NC 00 IQ4NC 12 Installation Instructions Mounting TG201264 SET Manual TE200147 Prepare Ethernet Network if using Ethernet Install DHCP Server If the IP address settings IP address subnet mask default router WINS and DNS servers addr...

Page 2: ...inued Serial Number n q 4 e y e c p 4 1 2 3 4 5 Q422B_V53440388 O S Q422B_V53440388 n q 4 e y e c p 4 1 2 3 4 5 00 10 70 0D 1E 92 MAC Addr IQ411 1010U5000 Part No LAN 422 MAC Addr IP Addr LAN Location S No MAC Addr 00 10 70 00 UD BB S No Q3B____X73010003 IP Addr Location Terminator out of circuit Terminator in circuit IQ422 IQ4NC 00 IQ4NC 12 Installation Instructions Mounting TG201264 for details ...

Page 3: ... is required see step 14 SET can connect when on a different subnet Note Other methods of connection are available see Connect to IQ4xx on page 10 Normal operation indication Power Watchdog Fault indications Power Check input power supply Watchdog Device fault Try resetting the IQ4xx to default settings see page 12 10s Normal operation indication OK RX or Fault indications OK Check Ethernet RJ45 St...

Page 4: ...ecommended that link local only be used on a single segment system When set to static fixed addresssing the IP addressing details must be configured manually Note If email alarms are being sent and the email server address is identified by internet domain name then a DNS server must also be specified using Text Comms IP Tool Manual TE200638 Using the PC laptop see step 7 run SET IP Tool 14 Set up ...

Page 5: ...N number 1 4 to 9 11 to 119 BACnet IP Can be disabled Ethernet Internetwork to Current Loop LAN Parameter Notes LAN number 1 4 to 9 11 to 119 BACnet IP Can be disabled BACnet MSTP Can be enabled e g for connection of PEHA devices Ethernet Internetwork to Current loop Internetwork Note Address no longer needs to be 100 Parameter Notes LAN number 1 4 to 9 11 to 119 BACnet IP Can be disabled BACnet M...

Page 6: ...ress and LAN number IQ4xx controllers are given a default device address and LAN number in the factory The device address is set in the range 11 to 119 on a rolling basis with the LAN number set to 20 Therefore it may be necessary to set the address LAN number as required Parameter Value Local Address 1 4 to 9 11 to 119 must be unique on LAN Local LAN 1 4 to 9 11 to 119 must be the same for all de...

Page 7: ...al behaviour for LAN OK indicator to extinguish for up to 1 min after detecting baud rate then illuminate Fault indication Ethernet LAN Unable to communicate on LAN Note Only applies if current loop is disabled or is not fitted Fault indication Current Loop LAN every 15s Longer than 2 minutes indicates LAN internetwork cannot be built Check baud settings of all devices on current loop see step 21 ...

Page 8: ...et connection is required to download both strategy and backdrop files Other connection types only allow download of strategy files Note strategy download is not recommended over current loop with baud rate 9k6 Note SET will set up the controller s date and time to that of the PC during download However they may be set up from a controller configured as timemaster Configure the IQ4xx strategy usin...

Page 9: ...ineering Port Wallbus Port or Ethernet port Connection can also be made over the Trend network over Ethernet or the current loop Use SET to upload the strategy and compare it with the strategy held by SET Note An Ethernet connection is required to upload strategy and backdrop files Other connection types only allow upload of strategy files SET Manual TE200147 O I Switch off Re connect outputs Open...

Page 10: ... PC via Local Supervisor Port RS232 CABLE EJ101442 9 way female D type RJ11 PC Connection to the IQ4xx can be made directly via the RS232 Local Supervisor Port USB Local Engineering Port or Ethernet Port Connection can also be made over a network Ethernet Connection use Notes IPTool SET ü Web Browser Supervisor Connection use Notes IPTool SET ü Web Browser Supervisor ü IQView8 via Local Supervisor...

Page 11: ...lable in a Trend device on the same Ethernet Trend network and connect to the vCNC as described in the supplied documentation Note If connecting with IP Tool the PC should be on the same Ethernet segment as the IQ4xx To make a connection with a web browser run a web browser on the PC and access the IQ4xx IP address or host name XW R IQ wireless sensor receiver via Local Supervisor Port RS232 PC Co...

Page 12: ... indicators will be ON Once this process has completed the Watchdog and LAN OK indicators will go OFF leaving the Power indicator ON This process may take up to 10 minutes depending on controller type Do not switch off the controller until the process has completed 4 RESET TO DEFAULTS Go to step 1 on page 1 Unplug the Ethernet cable and press and hold down the service button While continuing to hol...

Reviews: