SetupTrendAddressing

18

Set up Ethernet Access Across Routers 

(if required)

20

WriteAddressDetailsonLabel

2 CONFIGURATION 

(continued)

If the LAN is to be built across a router(s) details of devices 

(on  each  subnet)  must  be  specified  to  enable  cross-router 

communications.

Use IP Tool – see step 12 – to specify IP settings for up to 20 

devices in the Remote Trend Devices list:

Parameter

Value

IP Address

If using dynamic (DHCP) addressing:

Enter the host name of the remote device.

If using static (fixed) addressing:

Enter the IP Address of the remote device, 

in the format:  xxx.xxx.xxx.xxx

Subnet Mask The subnet mask for the remote device, in 

the format: xxx.xxx.xxx.xxx

IP Tool Manual (TE200638)

It is

 

recommended that 

at least two devices from each subnet 

are  specified.  For  increased  reliability  details  of  additional 

devices should be specified. 

If static IP addressing is being used the list should contain the 

devices with the lowest IP addresses. 

The same list must be copied to other EINC type devices on 

the network. 

Hint: Ticking the check box next to the Remote Trend Devices 

list retains the list in IP Tool, allowing it to be easily copied to 

other devices:

n

q

4

e

y

e

c

p

4

1

2

3

4

5

Q422B_V53440388

O/S

00:10:70:0D:1E:92

MAC Addr

IQ422-1010U5000

Part No:

LAN

IP

Addr

422

IP Tool Manual (TE200638)

IQTool  Addresser  Applet  Manual 

(TE201299)

IfconnectingtoaLANonEthernet(orstandalonemode):

 

Use IP Tool – see step 12 – to set the device address and 

LAN number.

IQ4xx  controllers  are  given  a  default  device  address  and 

LAN number in the factory. The device address is set in the 

range 11 to 119 on a rolling basis with the LAN number set to 

20.  Therefore  it  may  be  necessary  to  set  the  address/LAN 

number as required. 

Parameter

Value

Local Address

1, 4 to 9, 11 to 119

(must be unique on LAN)

Local LAN

1, 4 to 9, 11 to 119

(must  be  the  same  for  all  devices 

required to form a LAN).

Note: Changing the LAN number and/or device address will 

cause the controller to reboot.

IfconnectingtoaLANoncurrentloop(withonlyIQ4type

controllers):

 

Use  SET’s  IQTool  Addresser  Applet,  and  run  the 

Discovery Wizard.

 

Select  either  ‘Automatic  Discovery’  (recommended)  or 

‘Manual  Discovery’.  If  ‘Automatic  Discovery’  is  chosen 

you should then select ‘Duplicate Address Resolution’.

Automatic Discovery: 

The tool will discover the devices, 

and attempt to resolve any duplicate addresses.

Manual Discovery: 

Either  scan  the  bar  code,  or  press 

the Service Button for each controller.

WARNING 

For  /230  variants  hazardous 

voltages exist when the unit is powered. Take 

suitable precautions if pressing service button.

Note: If the LAN is not as expected after discovery it could 

be because of installation related reasons, e.g. wiring faults, 

power failure, etc. Check the devices are operating correctly 

and repeat discovery. If there are duplicate addresses add the 

devices to the grid manually, using network address and serial 

number. If necessary use SET’s System View to set the LAN 

number, and IQTool to set the address.

If connecting to a LAN on current loop (with pre IQ4

controllers):

 

Use SET’s IQTool Addresser Applet to manually add the 

IQ4 to the grid using the serial number and address.

 

Use SET’s System View to set the LAN number.

Device address (O/S)

LAN number

Fixed IP Address 

or Hostname (if DCHP)

Summary of Contents for IQ422

Page 1: ...al TE201299 IQ4 Configuration Manual TE201263 Note PDF copies are included with SET installation in the following folder C Trend Control Systems Documentation IQ422 IQ4NC 00 IQ4NC 12 Installation Instructions Mounting TG201264 SET Manual TE200147 Prepare Ethernet Network if using Ethernet Install DHCP Server If the IP address settings IP address subnet mask default router WINS and DNS servers addr...

Page 2: ...inued Serial Number n q 4 e y e c p 4 1 2 3 4 5 Q422B_V53440388 O S Q422B_V53440388 n q 4 e y e c p 4 1 2 3 4 5 00 10 70 0D 1E 92 MAC Addr IQ411 1010U5000 Part No LAN 422 MAC Addr IP Addr LAN Location S No MAC Addr 00 10 70 00 UD BB S No Q3B____X73010003 IP Addr Location Terminator out of circuit Terminator in circuit IQ422 IQ4NC 00 IQ4NC 12 Installation Instructions Mounting TG201264 for details ...

Page 3: ... is required see step 14 SET can connect when on a different subnet Note Other methods of connection are available see Connect to IQ4xx on page 10 Normal operation indication Power Watchdog Fault indications Power Check input power supply Watchdog Device fault Try resetting the IQ4xx to default settings see page 12 10s Normal operation indication OK RX or Fault indications OK Check Ethernet RJ45 St...

Page 4: ...ecommended that link local only be used on a single segment system When set to static fixed addresssing the IP addressing details must be configured manually Note If email alarms are being sent and the email server address is identified by internet domain name then a DNS server must also be specified using Text Comms IP Tool Manual TE200638 Using the PC laptop see step 7 run SET IP Tool 14 Set up ...

Page 5: ...N number 1 4 to 9 11 to 119 BACnet IP Can be disabled Ethernet Internetwork to Current Loop LAN Parameter Notes LAN number 1 4 to 9 11 to 119 BACnet IP Can be disabled BACnet MSTP Can be enabled e g for connection of PEHA devices Ethernet Internetwork to Current loop Internetwork Note Address no longer needs to be 100 Parameter Notes LAN number 1 4 to 9 11 to 119 BACnet IP Can be disabled BACnet M...

Page 6: ...ress and LAN number IQ4xx controllers are given a default device address and LAN number in the factory The device address is set in the range 11 to 119 on a rolling basis with the LAN number set to 20 Therefore it may be necessary to set the address LAN number as required Parameter Value Local Address 1 4 to 9 11 to 119 must be unique on LAN Local LAN 1 4 to 9 11 to 119 must be the same for all de...

Page 7: ...al behaviour for LAN OK indicator to extinguish for up to 1 min after detecting baud rate then illuminate Fault indication Ethernet LAN Unable to communicate on LAN Note Only applies if current loop is disabled or is not fitted Fault indication Current Loop LAN every 15s Longer than 2 minutes indicates LAN internetwork cannot be built Check baud settings of all devices on current loop see step 21 ...

Page 8: ...et connection is required to download both strategy and backdrop files Other connection types only allow download of strategy files Note strategy download is not recommended over current loop with baud rate 9k6 Note SET will set up the controller s date and time to that of the PC during download However they may be set up from a controller configured as timemaster Configure the IQ4xx strategy usin...

Page 9: ...ineering Port Wallbus Port or Ethernet port Connection can also be made over the Trend network over Ethernet or the current loop Use SET to upload the strategy and compare it with the strategy held by SET Note An Ethernet connection is required to upload strategy and backdrop files Other connection types only allow upload of strategy files SET Manual TE200147 O I Switch off Re connect outputs Open...

Page 10: ... PC via Local Supervisor Port RS232 CABLE EJ101442 9 way female D type RJ11 PC Connection to the IQ4xx can be made directly via the RS232 Local Supervisor Port USB Local Engineering Port or Ethernet Port Connection can also be made over a network Ethernet Connection use Notes IPTool SET ü Web Browser Supervisor Connection use Notes IPTool SET ü Web Browser Supervisor ü IQView8 via Local Supervisor...

Page 11: ...lable in a Trend device on the same Ethernet Trend network and connect to the vCNC as described in the supplied documentation Note If connecting with IP Tool the PC should be on the same Ethernet segment as the IQ4xx To make a connection with a web browser run a web browser on the PC and access the IQ4xx IP address or host name XW R IQ wireless sensor receiver via Local Supervisor Port RS232 PC Co...

Page 12: ... indicators will be ON Once this process has completed the Watchdog and LAN OK indicators will go OFF leaving the Power indicator ON This process may take up to 10 minutes depending on controller type Do not switch off the controller until the process has completed 4 RESET TO DEFAULTS Go to step 1 on page 1 Unplug the Ethernet cable and press and hold down the service button While continuing to hol...

Reviews: