IQ3../.../XNC/... Controller/Interface Installation Instructions TG200911 Issue 1/D 03/09/07

IQ3../.../XNC/...

Installation Instructions

Connect Serial Interface 

(continued)

2

0V

T

A

T

B

RA

RB

0V

A
B

0V

A
B

0V

A
B

0V

A
B

Cabinet A

0V

A B

0V

A B

0V

A B

0V

A B

0V

AB

0V

AB

Cabinet B

Isolating
Repeater

Isolating
Repeater

Surge
Protection

Surge
Protection

terminate at far end

terminate at far end

Backbone Bus

to more cabinets

Surge Ground or Earth Bond

Surge Ground
or Earth Bond

Multiple Cabinets

If the IQ3/XNC/SER controller and its  slave units are in different cabinets or use different power supplies (e.g. different
UPSs), the cabinets should be isolated from each other. If the bus is likely to suffer from surge and grounding problems,
surge protection should be added. The isolator should be connected to the earth (ground) of the nearest device, the 0V
of the isolator and the surge protector should be connected together, and earth (ground) of the surge protector’s exposed
side (e.g. backbone bus) should be connected as directly as possible to the surge ground or earth bond.

1 Installation - Mounting 

(continued)

RS485 2 wire, RS485 4 wire, or RS422 

(continued)

Summary of Contents for IQ3 series

Page 1: ...wo RS232 connectors can be used at a time 0V T A T B RA RB 0V A B 0V A B 0V A B 120ohm terminator Terminator switch ON IQ3 SER XNC either RS485 2 wire RS485 4 wire or RS422 2 part connector with 5 scr...

Page 2: ...ple Cabinets If the IQ3 XNC SER controller and its slave units are in different cabinets or use different power supplies e g different UPSs the cabinets should be isolated from each other If the bus i...

Page 3: ...to convenient input channel screen terminal Using 2 wire method 25 26 27 N 0 1 2 3 4 1 2 3 4 IQ LAN IQ LAN T T R R T T R R 1 2 3 4 1 2 3 4 T T R R T T R R IN OUT Using 4 wire method polarity independe...

Page 4: ...4 45 15 46 47 48 46 47 48 16 100 240 V OK RX P 0 P 0 P 0 P 0 P 0 P 0 P 0 P 0 P 0 P 0 P 0 TX RX RTS TXEN CTS RXEN RS485 RS232 terminator in circuit terminator out of circuit RS485 4 wire RS485 2 wire R...

Page 5: ...RX a TX c OK Network Address 0 2 3 or 119 IQ3 LAN XNC O I 1 2 3 4 1 2 3 4 IQ LAN IQ LAN T T R R T T R R 1 2 3 4 1 2 3 4 T T R R T T R R 1 2 3 4 1 2 3 4 IQ LAN IQ LAN T T R R T T R R 1 2 3 4 1 2 3 4 T...

Page 6: ...l interface auxiliary board fitted 4 5 6 4 5 6 2 7 8 9 7 8 9 3 10 11 12 4 13 14 15 5 16 17 18 6 19 20 21 7 22 23 24 8 25 26 27 9 28 29 30 10 0 0 0 0 0 0 0 0 0 1 2 3 1 2 3 1 0 0 0 V 24 V 24 V 34 35 36...

Page 7: ...voltages 417 IEC 5036 Remove Auxiliary Board Cover 4 a b c d CR 2032 CR 2032 Remove battery if replacing battery 5 Replace Auxiliary Board Cover 7 Warning Thelithiumbatterymustnotberecharged disassem...

Page 8: ...ion from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes Trend Control Systems Limited P O Box 34 Horsham West Sussex RH12 2YF...

Reviews: