Q-SERIES DI HEATER OPERATION / MAINTENANCE MANUAL
PAGE 21
Name
Address Type Data Bytes Perm
Value
Alarm Status
003075
Coil Bool
1
R
0-1
Alarm Pressure
003081
Coil Bool
1
R
0-1
Alarm Pressure Status
400641
Reg Short
2
R
1-4
Alarm Liquid Leak
003082
Coil Bool
1
R
0-1
Alarm Liquid Level
003084
Coil Bool
1
R
0-1
Alarm Liquid Level Status
400644
Reg Short
2
R
1-4
Alarm Over Temp
003083
Coil Bool
1
R
0-1
Alarm Thermocouple
003085
Coil Bool
1
R
0-1
Flow Range
003111
Coil Bool
1
RW
0-1
Percent Power
400671
Reg Short
2
R
0-100(%)
Process Temperature
400778
Reg Short
2
R
0-120(°C)
Remote heater Power
003112
Coil Bool
1
RW
0-1
Remote Mode
003113
Coil Bool
1
R
0-1
Remote Set Point
400786
Reg Short
2
RW 10-95(°C)
Table 5-2: Modbus Address Mapping
For example:
To enable the heating of water, a write request must be sent to the
address for the
“Remote Heater Power” coil with a value of 1.
To disable the heating of water, a write request must be sent to the
address for the
“Remote Heater Power” coil with a value of 0.
To monitor the temperature set point, a read request must be sent to
the address for the
“Remote Set Point” register.
To adjust the temperature set point, a write request must be sent to
the address for the
“Remote Set Point” register with a value between
15 and 95.