![TREBING + HIMSTEDT GPA-NS-011236 Manual Download Page 30](http://html1.mh-extra.com/html/trebing-himstedt/gpa-ns-011236/gpa-ns-011236_manual_1154870030.webp)
Appendix
ASCII | 3964R | RK512
28
SPI 3-specific parameters
The following 18 bytes of the parameter telegram (bytes 7 to 24) contain SPI 3-specific
parameters (see table). The specific parameters are valid for SPI 3 release 12 and higher.
Note!
The hex value for character timeout/response timeout must be specified in Mo-
torola format (high byte first).
If you use an RS 485 interface, you must set handshake to NONE.
Bytes 12, 22, 23, and 24 are only available in case of modules with extended
parameters (Release 12 and higher).
Byte
Parameter Value
Hex
code
Default
7…9
Constant
Cannot be changed
0x00
0x00
10
Constant
Cannot be changed
Module-dependent
0x01
(simple param.)
0x08
(extended param.)
Module-dependent
0x01
0x08
11
Data transfer rate
110 Bit/s
300 Bit/s
600 Bit/s
1200 Bit/s
2400 Bit/s
4800 Bit/s
9600 Bit/s
19200 Bit/s
28800 Bit/s
38400 Bit/s
57600 Bit/s
0x00
0x01
0x02
0x03
0x04
0x05
0x06
0x07
0x08
0x09
0x0A
9600 (0x06)
12
Flags
Lock diagnosis alarms
Release diagnosis alarms
0x00
0x01
Release diagnosis
alarms (0x01)
13
Handshake method
Xon/Xoff
RTS/CTS
none
0x00
0x01
0x02
none (0x02)
14
Xon
ASCII code of the Xon character
0…255
0x11
17 (0x11)
15
Xoff
ASCII code of the Xoff character
0…255
0x13
19 (0x13)
16
Parity
none
even
odd
mark
space
0x00
0x01
0x02
0x03
0x04
even (0x01)
17
Data frame
7 data bits
8 data bits
0x07
0x08
8 Bit (0x08)