Installation Instructions
800.882.9110 | 208.772.8515 | www.transtector.com
1. The ALPU SERIES is intended to be installed indoors or outdoors, on wall or pole
mount applications. The unit features mounting feet on the sides that mount on 4” center-
to-center holes with #10 sized hardware. The mount foot also adapts to 4” diameter pole
mounting kits with a 4.5” center-to-center holes and larger hardware. Refer to Figure 1
for mechanical requirements and connector locations. The optimum ground connection on
the metal enclosure unit at the mounting flange on either side is shown in Figure 2. Use
minimum 8AWG wire for a ground reference attachment. Communication cables with the
RJ45 connectors already installed can feed directly into the enclosure. Be sure to install the
cables with the unprotected cable installed into the left “in” jack and the protected equipment
cable in the right “out” jack. The enclosure features a built in cable retention that grips the
cable with a screw down bracket.
A pole mount adapter kit (pn 1000-1164) is available to meet installations on a wide range of
pole diameters from 2” metal fence poles to 10” diameter utility poles.
Model
Name
Description
MCOV
Line Current
Operating
Temp.
Temp.
Class
1101-935 ALPU-1000BT-CS-M ALPU GbE
6 Vdc
1A (4A total) -40°C to +70°C T6
1101-933 ALPU-POE-60V-M
ALPU 10/100 PoE 60 Vdc 1A (4A total) -40°C to +70°C T6
1101-959 ALPU-PTP-M
ALPU GbE PoE
85 Vdc 1A (4A total) -40°C to +70°C T6
2. Mount the device as close to the equipment to be protected as possible using the provided
hardware. Mount the unit in the orientation shown, with the strain reliefs facing the ground.
INSTALLATION INSTRUCTIONS
1. Remove the cover by removing the screw on the front of the unit.
2. Mount the unit to an outside surface using the two mounting holes shown in Figure 1.
3. Connect the Ethernet cable between the indoor unit and the suppressor using the
RJ45 jack.
4. Connect one Ethernet cable between the outdoor unit and the suppressor using an
RJ45 jack.
5. Attach appropriate wire gauge 8AWG as short as possible (less than 3 feet) between
the unit and the site grounding point using 1/4” hardware provided in the location shown
in Figure 2. Torque to 40-45 in-lbf. Refer to local codes and equipment manufacturers
standards before installation
6. Replace cover and secure with the two screws removed in step 1. Torque to 40-45 in-lbf.
CABLE REQUIREMENTS
If the ALPU SERIES is used in a Hazardous Location, the following cable requirements must
be met:
1. The cable must be 8 conductor (4 twisted pairs), 24AWG, Outdoor Rated
(-40°C to +80°C), Cat5e
2. The outer diameter of the cable must be .250-.300 inches.
3. The outer jacket material must be PVC
USAGE AND MAINTENANCE
The SPD should be scheduled for periodic inspection to ensure the SPD is operational and
all wire connections are tight.
If the SPD is damaged, contact Transtector for replacement.
Figure 1. Mechanical outline drawing (inches)
Figure 2. Ground Cable Installation
ALPU
1200-463 Rev C