     4.5 Wiring the ACP 200BWM

 

4.5.1 Line to Neutral Protection using the ACP 200BWM Connect 

 

the source 240Vac phase wire to the terminal marked L1. Connect 

 

the source neutral wire to the terminal marked L2/N. The terminals  

 

marked NC are not used.

 

4.5.2 Line to Line Protection using the ACP 200BWM: Connect a  

 

120Vac phase wire to the terminal marked L1. Connect a second  

 

120Vac phase wire to the terminal marked L2/N. The terminals      

 

marked NC are not used.

 

     1. These products are intended for use only on 15A 120Vac & 10A or 

     15A 240Vac circuits as specified in Section 4.

     2. Warning! Disconnect power upstream from the device when wiring 

     to avoid shock hazard.

     3. Mounting the ACP Hardwire Series:  See Figure 1.

     4. Wiring the ACP Hardwire Series

 

4.1 Wiring the ACP 100BW3 & 100BWN3:  Connect the source    

              

 

120Vac phase wire to the terminal marked LINE.  Connect the 

 

phase wire of the equipment to be protected to the terminal 

 

marked LOAD. Connect the source and equipment neutral wires 

 

to either terminal marked NEUTRAL.  The provided NEUTRAL 

 

connections are internally bonded within the suppressor.

 

4.2 Wiring the ACP 100BW3R:  Follow the directions from 

 

Section 4.1 for phase wiring.  The provided relay contacts are 

 

rated for 20Vac and 1 amp.  When the suppressor is functional, 

 

the COM and NC relay contact are connected under energized 

 

conditions.  In the event of suppressor failure, the state of the 

 

relay will change causing he COM and NO contacts to be 

 

connected under energized conditions. 

 

4.3 Wiring the ACP 200BW3: Connect the source 240Vac phase 

 

wire to the terminal marked LINE. Connect the phase wire of the 

 

equipment to be protected to the terminal marked LOAD. Connect 

 

the source and equipment neutral wires to either terminal 

 

marked neutral.

 

4.4 Wiring the ACP 200BWN3:  This product is intended for 

 

international use only on 10A 240Vac circuits. See Section 4.3 

 

for phase wiring.

1200-139  REV E

mm

5.75"

146.05

mm

2.25"

69.85 

CLEARANCE FOR NO. 8 SCREW

FIGURE 1

MOUNTING DIMENSIONS ACP HARDWIRE SERIES

mm

mm

0.4"

10.16

0.37"

9.40