4. ALERT RELAYS

  

ALERT INPUT (when DIP switch 2 is on)

 

  

ALERT RELAY OUTPUT

Both RELAY 1 and RELAY 2 INPUTs are supervised when DIPSWITCH 2 in ON.  

Supervised inputs detect fault or tampering of inputs and send an ALERT RELAY 

activation to the opposite unit (Typically from the Node unit to the Base unit).

Supervised inputs will detect an input shorted to ground (or each other) or an open 

input (loose or cut wire).  Connect the supplied 1K ohm and 2K ohm resistors across 

the device to be monitored as shown.  IMPORTANT:  resistors must be connected at 

the device to be monitored NOT AT THE XRE-100 RELAY INPUT.

When in Supervise Mode, unused inputs must be terminated with the supplied 3K 

ohm resistor.  Simply insert the resistor into the Rx and COM pins on the desired 

connector and tighten screw blocks.

If Supervised Inputs are not desired, simply leave DIPSWITCH 2 OFF and wire your 

contact directly across the Rx and COM pins.

NOTE:

 Communication Loss - If the XRE-100 units stop communicating the Alert 

Relay Output(Black relay) will trigger. Alerting on loss of communication between 

devices.

1

2

2K OHM

3K OHM

3K OHM

1K OHM

BROWN

BLACK

RED

RED

BLACK

RED

ORANGE

BLACK

RED

GOLD

GOLD

GOLD

SUPERVISOR RESISTOR

COLOR CODES

Monitored

Contact

Unused Input

XRE-100

Customer

Wires

1K

2K

Detects: 

  OPEN (cutwires) or,

 

      SHORT (wire to each other or ground)

1. Supervise resistors (supplied) must be at con-

tact.

2. Associated DIPSWITCH SW2 must be ON

3. Connect contact directly, without resistors for 

unsupervised inputs.  SW5 and SW6 = OFF. 

3K

7

Summary of Contents for Reign XRE-100

Page 1: ...2 24 Volts AC DC power and the DRY input closures you want to extend If you would like to survey the range capability before install simply provide power to both units and press the PROG TEST button alternately on each unit Successful transmission and reception will be indicated on the transmit and receive LEDs on each unit as described below v 8 29 18 X R E 1 0 0 RELAY EXTENDER There are two piec...

Page 2: ...2 ...

Page 3: ...Encryption AES 1 POWER DETAILS 4 2 LED INDICATORS 5 3 RELAY DIAGRAM AND WIRING 6 4 ALERT RELAYS 7 5 DIP SWITCHES 8 6 BATTERY BACKUP 9 7 PAIRING IN THE FIELD 9 TROUBLESHOOTING 1 0 POWER INPUT 12 to 24 VOLTS AC DC 1 AMP Minimum Always follow polarity when DC Power is used BATTERY INPUT for 12 Volt Sealed Lead Acid SLA battery only Solid GREEN LED indicates battery charging Momentarily flashing GREEN...

Page 4: ...AST 1AMP POWER SUPPLY POWER INPUT Power Input 12 to 24 VOLTS AC DC Always follow polarity when DC Power is used 1 AMP Minimum BATTERY INPUT Battery Input for 12 Volt Sealed Lead Acid SLA battery only Solid Green LED Battery charging Momentary Flashing LED Battery is fully charged and a trickle conditioning charge is occurring 1 2 2 1 4 ...

Page 5: ... result of an Relay Input change event or handshake STATUS PROG flashes yellow patterns indicating status of the unit pairing error etc RUN flashes ORANGE 1 second ON and 1 second OFF indicating the microprocessor is running POWER LED Glows solid orange when power is present 5 volt relay supply 3 3 volt logic supply and VPA 3 6 volt power amplifier supply 1 3 1 2 3 4 5 4 2 5 5 ...

Page 6: ...XRE 100 A closure on RLY2 COM input will result in a closure on RLY2 NC COM NO output of the paired XRE 100 RELAY OUTPUTS Relay Outputs The Reign XRE 100 comes with 2 relay outputs Each output follows RELAY INPUTS from remote paired XRE 100 When RLY1 or RLY2 INPUTS are closed RLY1 and RLY2 OUTPUTS are energized and connect NC COM NO respectively This relay state is also indicated by the GREEN ACTI...

Page 7: ...d with the supplied 3K ohm resistor Simply insert the resistor into the Rx and COM pins on the desired connector and tighten screw blocks If Supervised Inputs are not desired simply leave DIPSWITCH 2 OFF and wire your contact directly across the Rx and COM pins NOTE Communication Loss If the XRE 100 units stop communicating the Alert Relay Output Black relay will trigger Alerting on loss of commun...

Page 8: ...n XRE 100 to XRE 100 Relay Extension operation PROGRAM TEST BUTTON Program Test Button used with MODE SWITCH 1 to field pair units as described above Functions as a TEST TRANSMIT button during normal operation When pressed the XRE 100 will send a radio test packet and the RED TRANSMIT LED will illuminate If the paired XRE 100 is online it will acknowledge with a radio test packet indicated by a mo...

Page 9: ...1 to ON on both units Press the PROG TEST button on either unit NOTE Observe the STATUS PROG LED flashing Flip Dipswitch 1 to OFF on both units Press PROG TEST and observe TRANSMIT and RECEIVE LEDs operating normally Pairing procedure overwrites any previous units For example if replacing a unit simply follow the above procedure with the existing and replacement unit 7 PAIRING UNIT IN THE FIELD 1 ...

Page 10: ...tary on the green receive LED If you do not see the transmit and receive LED lights activate 1 Power cycle both the XRE units 2 Move the XRE 100 units to a higher location and avoid mounting on in metal objects If you are not getting the desired range between XRE 100 units 1 Ensure that the both devices are powered by their own dedicated power supply 2 Ensure that 1 amp of power draw is available ...

Page 11: ...YER MAKES NO RELIANCE ON ANY REPRESENTATION OF TRANSMITTER SOLUTIONS EXPRESS OR IMPLIED WITH REGARD TO THE GOODS AND ACCEPTS THEM AS IS WHERE IS TRANSMITTER SOLUTIONS SELLS THE GOODS TO BUYER ON CONDITION THAT TRANSMITTER SOLUTIONS WILL HAVE NO LIABILITY OF ANY KIND AS A RESULT OF THE SALE BUYER AGREES THAT TRANSMITTER SOLUTIONS SHALL HAVE NO LIABILITY FOR DAMAGES OF ANY KIND WHETHER DIRECT INCIDE...

Page 12: ...PH 866 975 0101 FX 866 975 0404 www transmittersolutions com ...

Reviews: