WTK-SVN001-EN

11

Wiring and System Inspection before
Test Run and Condenser Cleaning

Electric wire and ground wire must
comply with each country’s or regional’s
regulation.

1. Wiring

Importance
- Check the unit nameplate for

electrical rating. Make sure that
the wiring is according to local
codes and wiring system diagram.

- A separate power supply

disconnect and a circuit breaker
for overcurrent protection should
be provided in the external power
supply line.

- Always connect ground wire to

condensing unit every time to
prevent an electric shock in case
of an electric leakage.

- Electric wires shall not contact

to refrigerant pipes, compressor,
motor and the other moving parts.

- Manufacturer assumes no liability

for the problems caused by
unauthorized change in the
internal wiring.

- Should tighten up wire connection.
- Electric conductor parts must be

copper only.

2. Electric Wire Connection

- See wiring diagram on page 12
- Slipover electric wire at the end
- After connect electric wire,

check whether all screws are
firmly tightened

The electric wire connection between
outdoor and indoor unit should be
according to the wiring diagram.

To inspect system before test run.

After finished installing
air-conditioning, all system shall be
inspected before starting.

• Check that all brazings are correctly

made.

• Check that units are correctly

installed and there are no other
tools near or on top of the unit.

• Check the tubing and connections

for leak.

• Check that unit has a proper

ground wiring.

• Check for proper voltage and fuse

size.

• Check electrical wire size used is

as specified.

• Check all field wiring for tight

connection.

• Make sure that electrical wires

inside the unit do not contact to
refrigerant pipes.

• Turn on the unit, check the system

carefully.

Condenser Cleaning

After air-conditioning works for
a while, it may cause scales at the
surface of pipe in the condensing unit,
which may cause by cooling water
or rust inside cooling tower. Installer
can notice from the reduction of water
velocity, or the reduction of difference
of water temperature in and out,
or condensing temperature is higher
than normal.

Therefore, to maintain efficiency of
condenser, installer must clean up the
pipe’s inside surface of condenser to
prevent scales.

To clean up condenser with chemical

To clean up condenser with chemical
is one of the methods to wipe out
scales. To select proper chemical,
installer need to consult the water
treatment expert.

Summary of Contents for WTK530

Page 1: ...stallation Manual WTK SVN001 EN Split Water Cooled Condensing Units 7 000 60 000 Btu h WTK Series 50 Hz 50Hz Models Cooling Only WTK507 WTK509 WTK512 WTK518 WTK524 WTK530 WTK536 WTK048 WTK060 April 20...

Page 2: ...e is discovered send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer Warranty Warranty is based on the general terms and conditions by country The warrant...

Page 3: ...5 Refrigerant Tube Size Selection 5 Connection of Refrigerant Tubing Flaring and Brazing Procedure 6 Water Pipe Connection 8 Gas Leakage Inspection 9 Air Evacuation and Refrigerant Charge 10 Wiring a...

Page 4: ...are specified in Product Catalogs Digit No 7 Major Development Sequence Digit No 8 Electric Power Supply Characteristics A 220V 1ph 50Hz or 200 220V 1ph 50Hz B 240V 1ph 50Hz or 220 240V 1ph 50Hz 1 22...

Page 5: ...ne Liquid Line Suction Line WTK507 1 4 3 8 1 4 3 8 1 4 3 8 1 4 1 2 1 4 1 2 WTK509 1 4 3 8 1 4 3 8 1 4 3 8 1 4 1 2 1 4 1 2 WTK512 3 8 5 8 3 8 5 8 3 8 5 8 3 8 5 8 3 8 5 8 WTK518 3 8 5 8 3 8 5 8 3 8 5 8...

Page 6: ...tube to the required length with a tube cutter It is recommended to cut approx 30 cm 50 cm 12 to 20 longer than the tubing length you estimate 2 Hold each tube downward when cutting remove burrs at th...

Page 7: ...Figure 8 Tube connector straight Expand copper tube with the tube enlarging tool Figure 9 4 Clean copper tube surfaces both inside and outside before connection expansion or brazing 5 Insulate the ent...

Page 8: ...25 4 mm steel pipe and pipe connector 1 inch 25 4 mm PVC pipe or copper pipe and pipe connector Equipment used 1 Tee 1 Plug 3 90o Elbow 1 152 mm Nipple 2 50 mm Nipple 1 1 NPT to PVC or copper adapter...

Page 9: ...side Connect gauge line to the nitrogen tank but do not open nitrogen valve at the nitrogen tank Check out brazing track and all valves such as flare union Connect the other tails of gauge line to the...

Page 10: ...liquid line until pressure of the liquid line is around 120 150 psig Don t forget to evacuate air from liquid line before Turn on evaporator and condensing unit Fill up the refrigerant into suction li...

Page 11: ...the wiring diagram To inspect system before test run After finished installing air conditioning all system shall be inspected before starting Check that all brazings are correctly made Check that uni...

Page 12: ...ND GROUNDING OF NOTES 2TC AVAILABLE IN OPTIONAL MODEL RD RED BLK BLACK COLOR CODE TERMINAL BOARD BY FACTORY TERMINAL LPCO LOW PRESSURE CUT OUT HPCO HIGH PRESSURE CUT OUT TERMINAL BOARD BY OTHER TC TIM...

Page 13: ...RMALLY OPEN FACTORY WIRING FIELD WIRING CAPACITOR CPR COMPRESSOR LEGEND HPCO HIGH PRESSURE CUT OUT LPCO LOW PRESSURE CUT OUT TERMINAL COIL C1 TC BLK BLACK RD RED COLOR CODE YL YELLOW 2 POWER WIRING AN...

Page 14: ...E SUCTION LINE POWER SUPPLY 3 4 In 3 4 FTP DRAIN PIPE DOMESTIC MODEL REFRIGERANT CONNECTION SIZE In WATER LIQUID SUCTION CONNECTION SIZE In WTK507 509 1 4 3 8 3 4 WTK512 518 3 8 5 8 3 4 EXPORT MODEL R...

Page 15: ...POWER SUPPLY 5 8 In 3 4 FTP DRAIN PIPE DOMESTIC MODEL REFRIGERANT CONNECTION SIZE In WATER LIQUID SUCTION CONNECTION SIZE In WTK524 530 3 8 5 8 3 4 WTK536 3 8 3 4 3 4 WTK048 060 1 2 7 8 7 8 EXPORT MOD...

Page 16: ...mprovement it reserves the right to change design and specifications without notice Trane Thailand 7th Floor Ploenchit Center Building 2 Sukhumvit Road Klongtoey Bangkok 10110 Amair Limited 35 Mu 8 Po...

Reviews: