6
WSHP-SVX04A-EN
Table 1: Unit weights
Size
Shipping
Weight
with pallet (lb)
Shipping
Weight
w/o pallet (lb)
WPVJ
018
249
239
024
250
240
030
298
288
036
315
305
042
324
314
048
398
388
060
439
429
072
440
430
WPHF
021, 027
279
267
035. 040
367
356
047, 057
433
403
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level. Failure to
properly lift unit could result in death or serious injury
or possible equipment or property-only damage.
Dimensions/Weights/
Clearance
Figure 2: Mechanical clearances - WPVJ
Unit Location and Clearances
Locate the unit in an indoor area. The
ambient temperature surrounding the
unit must not be less than 45°F. Do not
locate the unit in areas subject to
freezing.
Attention should be given to service
clearance and technician safety. The
unit should be easily maintained or
serviced in all applications. There
must be enough space for service per-
sonnel to perform maintenance or re-
pair. Provide sufficient room to make
water, and electrical connection(s). Lo-
cal and national codes should be fol-
lowed in providing electrical power
connections. See
Figure 1
and
2
for
mechanical clearances.
Figure 1: Mechanical clearances - WPHF
Summary of Contents for WPHF
Page 7: ...WSHP SVX04A EN 7 Dimensions WPHF 021 057 ...
Page 8: ...8 WSHP SVX04A EN Dimensions WPVJ 018 024 LH ...
Page 9: ...WSHP SVX04A EN 9 Dimensions WPVJ 018 024 RH ...
Page 10: ...10 WSHP SVX04A EN Dimensions WPVJ 030 042 LH ...
Page 11: ...WSHP SVX04A EN 11 Dimensions WPVJ 030 042 RH ...
Page 12: ...12 WSHP SVX04A EN Dimensions WPVJ 048 072 LH ...
Page 13: ...WSHP SVX04A EN 13 Dimensions WPVJ 048 072 RH ...
Page 35: ...WSHP SVX04A EN 35 Unit Wiring WPVJ Basic 24V Diagram ...
Page 36: ...36 WSHP SVX04A EN Unit Wiring WPVJ Tracer ZN510 Diagram ...
Page 37: ...WSHP SVX04A EN 37 Unit Wiring WPHF Basic 24V Diagram ...
Page 38: ...38 WSHP SVX04A EN Unit Wiring WPHF Tracer ZN510 Diagram ...